OSHA Inspection: GARDEN STATE PRECAST, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of GARDEN STATE PRECAST, INC. in 1630 WYCKOFF ROAD, WALL TOWNSHIP, NJ 07719 (NAICS 327332). OSHA activity number 339785495.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Garden State Precast, INC. — free Get an email when a new federal OSHA severe-injury report for Garden State Precast, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1630 WYCKOFF ROAD
City
WALL TOWNSHIP
State
NJ
ZIP
07719
Mailing
PO BOX 702, FARMINGDALE, NJ 07727
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327332
Employees
80
Ownership type
A

16 citations on file for this inspection.

1910.23 C01

Serious Gravity 5 1 instance 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $2,380 · Current $1,428 Reduced
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards:    a)   Pit beneath conveyor system:  Open sided floor (conveyor pit) approximate 6 foot 10 inch deep was not properly guarded, approximate 41 inch high guard rail did not have a midrail, on or about 05/21/14.     NOTE:  THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (2)
  • — I (S) $1428
  • — Z (S) $2380

1910.23 D01 V

Serious Gravity 5 1 instance 60 exposed
Issued
Nov 19, 2014
Abate by
Dec 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.23(d)(1)(v): On stairways 88 or more inches wide, one handrail on each enclosed side, one stair railing on each open side, and one intermediate stair railing located approximately midway of the width:  a)    Stairway leading to maintenance building: Eight feet eight inch wide stairway with 8 risers and 7 treads did not have any stair rails, on or about 05/21/14.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.179 L01

Deleted Serious Gravity 10 2 instances 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 9, 2014
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.179(l)(1): A preventive maintenance program based on the crane manufacturer's recommendations was not established:   a)   Production Building: The employer had not established a preventive maintenance program for any of the cranes in use, on or about 05/21/14.   NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4900

1910.179 G01 V

Serious Gravity 10 1 instance 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $0 · Current $2,940
29 CFR 1910.179(g)(1)(v): Pendant control box(es) were not clearly marked for identification of functions:    a)   5 Ton Lafayette Crane & Hoist Company crane:  Labeling for the pendant was not visible until employees cleaned off some of the cement covering the markings, on or about 05/21/14.     NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $2940
  • — Z (S) $0

1910.179 J02 III

Serious Gravity 10 2 instances 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 9, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.179(j)(2)(iii): Monthly inspections of hooks, with a certification record which includes the date of inspection, the signature of the person who performed the inspection and the serial number, or other identifier, of the hook inspected, were not performed:   a)    Work area where 5 ton Lafayette crane located: Monthly inspections of the hook had been performed, on or about 05/21/14;  b)    Work area where 5 ton Lafayette crane located: No certification record for any monthly inspections, on or about 05/21/14.   NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.179 M01

Serious Gravity 10 2 instances 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.179(m)(1): A certification record which includes the date of inspection, the signature of the person who performed the inspection and an identifier for the ropes which were inspected were not being kept on file where readily available to appointed personnel:  a)    Work area where 5 ton Lafayette crane located: Employer had not conducted an inspections of the running ropes for any of the cranes used by company employees, on or about 05/21/14.   b)     Work area where 5 ton Lafayette crane located: Employer did not have any certification records for any monthly inspections, on or about 05/21/14.  NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B01

Serious Gravity 10 5 instances 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $4,900 · Current $2,940 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees, in that the employer did not ensure the safety of the equipment pursuant to the considerations in sections (i) through (viii) of 29 CR 1910.303(b)(1):    A)  Production building, interior, where molds are predominately poured: 120 vac 15 amp duplex outlet not properly secured to the structure, on or about 05/21/14;    B)  Production building, interior south wall, where molds are predominately poured: Yellow extension cord used to provide power to the vibrator was missing the ground prong, on or about 05/21/14;    C)  Production building, interior south wall, where molds are predominately poured: 120 vac 15 amp duplex outlet used in a wet and damp environment was not protected by an operational GFCI, on or about 95/21/14;    D)  Production building, interior, where molds are predominately poured: New 120 vac 15 amp permanent wiring not properly hooked up; Sperry Model HGT6120 Ground & Outlet Tester indicated circuit had an open neutral, on or about 05/28/14;    E)   Production building, interior, where molds are predominately poured: Circuit breaker panel in use with missing circuit breaker and or blank, on or about 05/21/14.      NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $2940
  • — Z (S) $4900

1910.303 B02

Serious Gravity 10 2 instances 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a)    Inside production area: Duplex outlet on a 120 vac 15 amp circuit used to provide power to the electric Northrock Concrete vibrator was not appropriate for damp and wet locations, on or about 05/21/14;  b)    Inside production area: Duplex outlet used to power the Northrock Concrete vibrator on a 120 vac 15 amp circuit, was falling apart, on or about 05/21/14.  NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 B07 I

Serious Gravity 5 1 instance 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings shall be effectively closed to afford protection substantially equivalent to the wall of the equipment:  A)  Production building, vicinity of mixer: Cutler-Hammer circuit breaker panel in use with missing circuit breaker and or blank, on or about 05/21/14.  NOTE:  THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 F02

Serious Gravity 5 2 instances 8 exposed
Issued
Nov 19, 2014
Abate by
Jan 9, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    A)  Inside production area, adjacent to mixer: All circuit breakers for the Cutler-Hammer Circuit breaker panel in use were not labeled to indicate their purpose (24 circuit breakers), on or about 05/21/14;    B)  Inside production area: All circuit breakers for the Square D Circuit breaker panel in use were not labeled to indicate their purpose (20 circuit breakers), on or about 05/21/14.      NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.303 G02 I

Serious Gravity 10 2 instances 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  a)  Inside production area, where molds are predominately poured: Circuit breaker panel in use with missing circuit breaker and or blank, on or about 05/21/14;  b)  Inside production area, main interior production area, half way down south wall in the northern half of the production area; where molds are predominately poured: no cover for the 120 vac 15 amp duplex outlet, on or about 05/21/14.    NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B01 II

Deleted Serious Gravity 5 1 instance 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $2,975 · Current $0 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:  a)   Inside production area, adjacent to mixer: Cutler-Hammer circuit breaker panel was in use with a missing circuit breaker and or blank, on or about 05/21/14.    NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $2975

1910.305 E01

Deleted Serious Gravity 10 1 instance 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:  a)   Inside production area, where molds are predominately poured: 120 vac 15 amp duplex outlet not properly secured to the structure, on or about 05/21/14.   NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A02 I

Deleted Serious Gravity 10 2 instances 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $4,900 · Current $0 Reduced
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):  a)   Inside production area: Yellow extension cord without ground prong was plugged into the 120 vac 15 amp duplex to power Northrock Concrete vibrator had not been removed from service, on or about 05/21/14;  b)   Inside production area: Power cord for the 120 vac 15 amp Northrock Concrete vibrator missing ground prong had not been removed from service, on or about 05/21/14.   NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4900

1910.334 A02 II

Deleted Serious Gravity 10 2 instances 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(ii): There was a defect or evidence of damage that could have exposed an employee to injury and the defective or damaged item was not removed from service:  a)   Inside production area: Yellow extension cord without ground prong was plugged into the 120 vac 15 amp duplex to power Northrock Concrete vibrator, on or about 05/21/14;  b)   Inside production area: Power cord for the 120 vac 15 amp Northrock Concrete vibrator missing ground prong, on or about 05/21/14.  NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.334 A03 I

Deleted Serious Gravity 10 2 instances 8 exposed
Issued
Nov 19, 2014
Abate by
Dec 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(3)(i): A flexible cord used with grounding type equipment did not contain an equipment grounding conductor:  a)   Inside production area: Yellow extension cord without ground prong was plugged into the 120 vac 15 amp duplex to power Northrock Concrete vibrator, on or about 05/21/14; b)   Inside production area: Power cord for the 120 vac 15 amp Northrock Concrete vibrator missing ground prong, on or about 05/21/14.  NOTE:  IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM, FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Garden State Precast, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339785495.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.