Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,214Inspections Most recent open 2026-07-16 Last loaded 2026-07-20

OSHA Inspection: USDA-RURAL DEVELOPMENT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of USDA-RURAL DEVELOPMENT in #47 AVE. FERNANDO RIBAS, UTUADO, PR 00641 (NAICS 924120). OSHA activity number 339794844.

Watch Usda-Rural Development — free Get an email when a new federal OSHA severe-injury report for Usda-Rural Development is published. One employer, no account, unsubscribe in one click.
Site address
#47 AVE. FERNANDO RIBAS
City
UTUADO
State
PR
ZIP
00641
Mailing
#47 AVE. FERNANDO RIBAS, UTUADO, PR 00641
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
924120
Employees
6
Ownership type
D

3 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 3 instances 3 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:   a) On or about 06/02/14, at #47 Fernando Ribas Ave., Utuado, PR, in the Construction Analyst area, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle.   b) On or about 06/02/14, at #47 Fernando Ribas Ave., Utuado, PR, in the Specialist area 1, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle.   c) On or about 06/02/14, at #47 Fernando Ribas Ave., Utuado, PR, in the Specialist area 2, an uninterruptible power supply was not connected to a permanently installed branch circuit receptacle.     PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:  On or about 06/02/14, at #47 Fernando Ribas Ave., Utuado, PR, in the main entrance area, an electrical outlet box was not covered.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV A

Serious Gravity 1 1 instance 6 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:  On or about 06/02/14, at #47 Fernando Ribas Ave., Utuado, PR, in the main entrance area, a flexible cord was used in lieu of permanent wiring.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

View USDA-RURAL DEVELOPMENT's full OSHA safety record →