OSHA Inspection: SUPERVALU, INC.

Fatality or catastrophe inspection · Safety discipline

On , OSHA opened a fatality or catastrophe safety inspection of SUPERVALU, INC. in SUPERVALU - LEWIS GROCER DIVISION 301 MARTIN LUTHER KING BLVD., INDIANOLA, MS 38751 (NAICS 493120). OSHA activity number 339801250.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Supervalu, INC. for free Get an email when a new federal OSHA severe-injury report for Supervalu, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
SUPERVALU, INC.
Site address
SUPERVALU - LEWIS GROCER DIVISION 301 MARTIN LUTHER KING BLVD.
City
INDIANOLA
State
MS
ZIP
38751
Mailing
7075 FLYING CLOUD DR., EDEN PRAIRIE, MN 55344
Inspection type
Fatality or catastrophe (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
493120
Employees
200
Ownership type
Private (A)

2 citations on file for this inspection.

1910.303 B07 I

Other-than-serious 1 instance 10 exposed
Issued
Aug 13, 2014
Abate by
Aug 20, 2014
Penalty
Initial $3,300 · Current $2,310 Reduced
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:     (a) Slot 47 (5841) - On or about June 11, 2014 employees were exposed to electric shock hazards while working near a 480V disconnect box with a 1 and 3/16 inch hole in the sidewall. The hole was not effectively closed.     (b)  Maintenance Shop - On or about June 11, 2014 employees were exposed to electric shock hazards while working near a 480V to 240V transformer with 2 holes in the sidewall over 2 inches in diameter. The holes were not effectively closed.
Recent events (2)
  • · I (O) $2310
  • · Z (S) $3300

1910.303 G01 I A

Other-than-serious 1 instance 3 exposed
Issued
Aug 13, 2014
Abate by
Aug 20, 2014
Penalty
Initial $4,400 · Current $3,080 Reduced
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910:    (a)  Behind Slot 47 (5841) - On or about June 11, 2014 employees were exposed to electric shock hazards while working near Slot 47 and there was insufficient (12.5 to 15 inches) working space in front of a 480V electrical disconnect for a wall fan and motor starter.