Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ELECTRIC HEATER COMPANY

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ELECTRIC HEATER COMPANY in 45 SEYMOUR STREET, STRATFORD, CT 06615 (NAICS 333318). OSHA activity number 339805798.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Electric Heater Company — free Get an email when a new federal OSHA severe-injury report for Electric Heater Company is published. One employer, no account, unsubscribe in one click.
Site address
45 SEYMOUR STREET
City
STRATFORD
State
CT
ZIP
06615
Mailing
45 SEYMOUR STREET, STRATFORD, CT 06615
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333318
Employees
57
Ownership type
A

7 citations on file for this inspection.

1910.243 C01

Serious Gravity 5 2 instances 2 exposed
Issued
Sep 4, 2014
Abate by
Sep 10, 2014
Penalty
Initial $2,800 · Current $1,820 Reduced
29 CFR 1910.243(c)(1): Abrasive wheel(s) were used on portable grinder(s) which were not provided with safety guard(s) meeting the requirements specified in 29 CFR 1910.243(c)(1) through (c)(4)(a)     Workplace:  The employees were exposed to flying millings and lacerations from the unguarded hand held right angle grinders.
Recent events (2)
  • — I (S) $1820
  • — Z (S) $2800

1910.244 A02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 4, 2014
Abate by
Sep 10, 2014
Penalty
Initial $4,200 · Current $2,900 Reduced
29 CFR 1910.244(a)(2)(i): In the absence of a firm foundation, the base of the jack was not blocked:    Workplace:  Neither the base of the hydraulic jack, used by employees during the process of welding a tank was placed on a firm foundation nor was blocked appropriately.    On/about 6/9/2014, the base of the jack slipped off during the operation, and the piston of the jack flew out and struck an employee's head. The employee sustained serious injury from the incident.
Recent events (2)
  • — I (S) $2900
  • — Z (S) $4200

1910.303 B02

Serious Gravity 5 2 instances 2 exposed
Issued
Sep 4, 2014
Abate by
Sep 10, 2014
Penalty
Initial $2,800 · Current $1,820 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling exposing employees to electrical hazards:       Workplace:      1.    A junction box, having many knockouts and 2/duplex outlets was not installed and used in accordance with listing and labeling as to be used as an extension power cord. It was exposed to a physical damage.      2.    An EMT Conduit Set Screw Connector was used to connect a flexible cord of the welding mach9ine to the service switch.
Recent events (2)
  • — I (S) $1820
  • — Z (S) $2800

1910.304 G06 VI

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 4, 2014
Abate by
Sep 10, 2014
Penalty
Initial $2,800 · Current $1,820 Reduced
29 CFR 1910.304(g)(6)(vi): Exposed noncurrent-carrying metal parts of cord-and plug-connected equipment that may become energized shall be grounded:      Workplace:  The attachment plug of the hand-held portable right angle grinder was missing the grounding pin.
Recent events (2)
  • — I (S) $1820
  • — Z (S) $2800

1910.305 B01 II

Serious Gravity 5 2 instances 2 exposed
Issued
Sep 4, 2014
Abate by
Sep 10, 2014
Penalty
Initial $2,800 · Current $1,820 Reduced
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed:    Workplace:       1.    The junction box, used for outlets was missing a duplex outlet with two (2) unused openings.      2.    The service disconnect switch box for the TIG welder had an unused opening on the bottom .
Recent events (2)
  • — I (S) $1820
  • — Z (S) $2800

1910.305 G01 III

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 4, 2014
Abate by
Sep 10, 2014
Penalty
Initial $2,800 · Current $1,820 Reduced
29 CFR 1910.305(g)(1)(iii): Flexible cords used as permitted in paragraphs (g)(1)(ii)(C), (g)(1)(ii)(G), or (g)(1)(ii)(I) of this section, the flexible cables were not equipped with an attachment plug and energized from an approved receptacle outlet:    Workplace:  The flexible cord of the portable TIG welding machine was wired directly into a wall-mounted service electric switch boix.
Recent events (2)
  • — I (S) $1820
  • — Z (S) $2800

1910.305 G02 III

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 4, 2014
Abate by
Sep 10, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:     Workplace:  The flexible cord of the portable TIG welding machine was wired directly into a wall-mounted electric box without providing an adequate tension/strain relief at the opening/fitting.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Electric Heater Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339805798.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.