Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,991Inspections Most recent open 2026-08-24 Last loaded 2026-08-27

OSHA Inspection: U.S. ARMY RCTG BRIGADE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of U.S. ARMY RCTG BRIGADE in 4539 N. 5TH ST, NORTH LAS VEGAS, NV 89031 (NAICS 928110). OSHA activity number 339809576.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch U.S. Army Rctg Brigade for free Get an email when a new federal OSHA severe-injury report for U.S. Army Rctg Brigade is published. One employer, no account, unsubscribe in one click.
Site address
4539 N. 5TH ST
City
NORTH LAS VEGAS
State
NV
ZIP
89031
Mailing
4539 N. 5TH ST, NORTH LAS VEGAS, NV 89031
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
30
Ownership type
Federal government (D)

7 citations on file for this inspection.

1910.22 B01

Serious Gravity 1 1 instance 8 exposed
Issued
Jul 10, 2014
Abate by
Aug 4, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.22(b)(1): Aisles and passageways were not kept clear and in good repair, with no obstruction across or in aisles that could create a hazard.  (a) On or about June 13, 2014, in the US Army 6th Recruiting Brigade, S-3, operations area, power and data cable were obstructing the passageway, creating trip hazards.
Recent events (1)
  • · Z (S) $0

1910.36 G02

Serious Gravity 1 8 instances 8 exposed
Issued
Jul 10, 2014
Abate by
Aug 4, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  (a) On or about June 13, 2014, in the US Army 6th Recruiting Brigade, personnel office spaces, exit/egress from various office areas and spaces were 9, 11, 15, 17, 20 and 22 inches and obstructed by boxes, wooden desk, file cabinet and other furniture.
Recent events (1)
  • · Z (S) $0

1910.157 C01

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 10, 2014
Abate by
Aug 4, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.  (a) On or about June 13, 2014, in the US Army 6th Recruiting Brigade, supply office spaces, a portable fire extinguisher was left free standing next to the entry door.
Recent events (1)
  • · Z (S) $0

1910.165 E

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 10, 2014
Abate by
Aug 4, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.165(e): Manually operated actuation devices for use in conjunction with employee alarms were not unobstructed, conspicuous and readily accessible.  (a) On or about June 13, 2014, at the US Army 6th Recruiting Brigade, rear building entrance, there were boxes and other shipping materials stored in front of the manually operated pull fire alarm.
Recent events (1)
  • · Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 10, 2014
Abate by
Aug 4, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  (a) On or about June 13, 2014, at the US Army 6th Recruiting Brigade, command group office, the re-locatable power tap was used to plug in the high amperage load such as cuisine art coffee maker.
Recent events (1)
  • · Z (S) $0

1910.303 B08 II

Serious Gravity 1 1 instance 30 exposed
Issued
Jul 10, 2014
Abate by
Aug 4, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(8)(ii): Electric equipment that depends on the natural circulation of air and convection principles for equipment designed for floor mounting, clearance between top surfaces and adjacent surfaces were not provided to dissipate rising warm air.  (a) On or about June 13, 2014, at the US Army 6th Recruiting Brigade, electrical room, miscellaneous boxes/materials on the pallet were stored in front of the air cooled pad mounted transformer obstructing air circulation.
Recent events (1)
  • · Z (S) $0

1910.303 G01

Serious Gravity 1 2 instances 2 exposed
Issued
Jul 10, 2014
Abate by
Aug 4, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment.  (a) On or about June 13, 2014, at the US Army 6th Recruiting Brigade, electrical room, miscellaneous boxes/materials on the pallet were stored in front of the power panel and boxes of ceiling tiles were stored in front of the air handler #2, 1 chilled water pump and #2 hot water pump switches in the boiler room.
Recent events (1)
  • · Z (S) $0

View U.S. Army Rctg Brigade's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339809576.