ARCADIA, CA ·
OSHA Inspection: U.S. DEPT. OF AGRICULTURE FOREST SERVICE - ANGELES NATIONAL FOREST
Follow-up inspection · Safety discipline
At a glance
On , OSHA opened a follow-up safety inspection of U.S. DEPT. OF AGRICULTURE FOREST SERVICE - ANGELES NATIONAL FOREST in SUPERVISOR'S OFFICE, BLDG 2038 701 N. SANTA ANITA AVE, ARCADIA, CA 91006 (NAICS 924120). OSHA activity number 339820607.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- SUPERVISOR'S OFFICE, BLDG 2038 701 N. SANTA ANITA AVE
- City
- ARCADIA
- State
- CA
- ZIP
- 91006
- Mailing
- 701 N. SANTA ANITA AVE, ARCADIA, CA 91006
What kind of inspection was it?
- Inspection type
- Follow-up (F)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 924120
- Employees
- 45
- Ownership type
- Federal government (D)
Citations
3 citations on file for this inspection.
1910.303 B02
- Issued
- Sep 25, 2014
- Abate by
- Oct 7, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Publications information office: Two power strips were connected in series to provide 120VAC electrical service at the work station. The USDA Forest Service was previously cited for a repeat violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 957347, citation number 1, item number 2, and was affirmed as a final order on March 21, 2014, with respect to a workplace located at 10845 Rancho Bernardo Rd., Suite 200, San Diego, CA 92127. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 911911, citation number 1, item number 10, and was affirmed as a final order on August 6, 2013, with respect to a workplace located at 41374 North Shore Drive, Fawnskin, CA 92333. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 642658, citation number 1, item number 1, and was affirmed as a final order on March 13, 2012, with respect to a workplace located at 701 N. Santa Anita, Ave., Arcadia, CA 91006.
Recent events (1)
- · Z (R) $0
1910.304 B04 II B
- Issued
- Sep 25, 2014
- Abate by
- Oct 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4: Heritages resources: A 15 amp branch circuit supplying two or more receptacle outlets was supplying a load of 16.2 amps where table S-4 indicates the maximum load is 12 amps. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.304(b)(4)(ii)(B), which was contained in OSHA inspection number 910625, citation number 1, item number 5, and was affirmed as a final order on August 1, 2013, with respect to a workplace located at 602 S. Tippecanoe Ave., San Bernardino, CA 92408.
Recent events (1)
- · Z (R) $0
1910.305 G01 IV A
- Issued
- Sep 25, 2014
- Abate by
- Oct 22, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure: Heritage resources: A flexible cord was used for over one year to provide 120VAC service to office printers. The USDA Forest Service was previously cited for a repeat violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 958132, citation number 2, item number 4, and was affirmed as a final order on April 14, 2014, with respect to a workplace located at 32353 Ortega Highway, Lake Elsinore, CA 92530. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 911911, citation number 1, item number 15, and was affirmed as a final order on August 6, 2013, with respect to a workplace located at 41374 North Shore Drive, Fawnskin, CA 92333.
Recent events (1)
- · Z (R) $0
More inspections at U.S. Dept. of Agriculture Forest Service - Angeles National Forest
View U.S. Dept. of Agriculture Forest Service - Angeles National Forest's full OSHA safety record →
More inspections in this industry (NAICS 924120)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339820607.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.