VALYERMO, CA ·
OSHA Inspection: U.S. DEPT. OF AGRICULTURE FOREST SERVICE - ANGELES NATIONAL FOREST
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of U.S. DEPT. OF AGRICULTURE FOREST SERVICE - ANGELES NATIONAL FOREST in VALYERMO FIRE STATION 37 29835 VALYERMO RD. PO BOX 15, VALYERMO, CA 93563 (NAICS 922160). OSHA activity number 339821902.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- VALYERMO FIRE STATION 37 29835 VALYERMO RD. PO BOX 15
- City
- VALYERMO
- State
- CA
- ZIP
- 93563
- Mailing
- 701 N. SANTA ANITA AVE, ARCADIA, CA 91006
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (J)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 922160
- Employees
- 11
- Ownership type
- Federal government (D)
Citations
8 citations on file for this inspection.
1910.303 B02
- Issued
- Nov 24, 2014
- Abate by
- Dec 19, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Engine bay: A receptacle outlet box designed for permanent mounting and conduit connections was used as a pendant cord to provide 120VAc service.
Recent events (1)
- · Z (S) $0
1910.303 B07 IV
- Issued
- Nov 24, 2014
- Abate by
- Dec 19, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(7)(iv): Electrical equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating. (a) Engine bay: A light switch cover plate was broken at one corner exposing employees to inadvertent contact with the conductors inside the box. (b) Garage: A receptacle cover plate was broken with half the cover missing exposing employees to inadvertent contact with the conductors inside the box.
Recent events (1)
- · Z (S) $0
1910.303 G01 II
- Issued
- Nov 24, 2014
- Abate by
- Dec 19, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage: Garage: Access to a circuit breaker box was obstructed by boxes, pallets, and paint cans stored in front of the panel.
Recent events (1)
- · Z (S) $0
1910.242 B
- Issued
- Nov 24, 2014
- Abate by
- Dec 19, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.: Engine bay: Compressed air used by the employees for cleaning was not reduced to less than 30 p.s.i. and the use of eye protection was not enforced. The USDA Forest Service was previously cited for a repeat violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.242(b), which was contained in OSHA inspection number 957451, citation number 2, item number 4, and was affirmed as a final order on April 7, 2014, with respect to a workplace located at 1634 Black Canyon Rd., Goose Valley Fire Station, Ramona, CA 92065 The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.242(b), which was contained in OSHA inspection number 642738, citation number 1, item number 1, and was affirmed as a final order on December 5, 2012, with respect to a workplace located at 701 N. Santa Anita Ave, Fire Station 17/112, Arcadia, CA 91006.
Recent events (1)
- · Z (R) $0
1910.243 C03
- Issued
- Nov 24, 2014
- Abate by
- Dec 19, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.243(c)(3): Abrasive wheels used on vertical portable grinder(s) (right angle head grinders) were not provided with safety guard(s) having a maximum exposure angle of 180 degrees and located between the operator and wheel: Engine bay: The guard of a portable angle grinder was removed from the grinder. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910. 243(c)(3), which was contained in OSHA inspection number 911908, citation number 1, item number 2, and was affirmed as a final order on August 5, 2013, with respect to a workplace located at 28104 Highway 18, Rock Camp Station, Lake Arrowhead, CA 92352.
Recent events (1)
- · Z (R) $0
1910.304 B03 I
- Issued
- Nov 24, 2014
- Abate by
- Dec 19, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops did not have ground-fault circuit-interrupter protection for personnel: Bathroom: the GFCI protected receptacle outlet was not operational, failing to activate when the grounding path was interrupted. The USDA Forest Service was previously cited for a repeat violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.304(b)(3)(i), which was contained in OSHA inspection number 957389, citation number 1, item number 3, and was affirmed as a final order on March 27, 2014, with respect to a workplace located at 3348 Alpine Blvd., Alpine, CA 91901. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.304(b)(3)(i), which was contained in OSHA inspection number 911911, citation number 1, item number 10, and was affirmed as a final order on August 6, 2013, with respect to a workplace located at 41374 North Shore Drive, Fawnskin, CA 92333.
Recent events (1)
- · Z (R) $0
1910.305 G01 IV A
- Issued
- Nov 24, 2014
- Abate by
- Dec 19, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure: (a) Office: A flexible cord was used for over one year to provide 120VAC service to a microwave oven. (b) Office: A flexible cord was used for over one year to provide 120VAC service to a refrigerator. The USDA Forest Service was previously cited for a repeat violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 958132, citation number 2, item number 4, and was affirmed as a final order on April 14, 2014, with respect to a workplace located at 32353 Ortega Highway, Lake Elsinore, CA 92530. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.305(g)(1)(iv)(A), which was contained in OSHA inspection number 911911, citation number 1, item number 15, and was affirmed as a final order on August 6, 2013, with respect to a workplace located at 41374 North Shore Drive, Fawnskin, CA 92333.
Recent events (1)
- · Z (R) $0
1910.334 A02 II
- Issued
- Nov 24, 2014
- Abate by
- Dec 19, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.334(a)(2)(ii): If there is a defect or evidence of damage that might expose an employee to injury, the defective or damaged item shall be removed from service, and no employee may use it until repairs and tests necessary to render the equipment safe have been made. (a) Engine bay: The cord of a disc sander was damaged exposing the conductors of the cord. (b) Engine bay: The cord of a cut saw was damaged exposing the conductors of the cord. (c) Engine bay: The grounding pin was removed from the plug end of a drill. (d) Barracks: The cord of a vacuum was damaged exposing the conductors of the cord. The USDA Forest Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910. 334(a)(2)(ii), which was contained in OSHA inspection number 911912, citation number 1, item number 11, and was affirmed as a final order on August 6, 2013, with respect to a workplace located at 28500 Highway 243, Keenwild Station, Mountain Center, CA 92561.
Recent events (1)
- · Z (R) $0
More inspections at U.S. Dept. of Agriculture Forest Service - Angeles National Forest
View U.S. Dept. of Agriculture Forest Service - Angeles National Forest's full OSHA safety record →
More inspections in this industry (NAICS 922160)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339821902.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.