BILLINGS, MT —
OSHA Inspection: S BAR S SUPPLY COMPANY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of S BAR S SUPPLY COMPANY in 2032 OLD HARDIN ROAD, BILLINGS, MT 59101 (NAICS 444110). OSHA activity number 339877144.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- S BAR S SUPPLY COMPANY
- Site address
- 2032 OLD HARDIN ROAD
- City
- BILLINGS
- State
- MT
- ZIP
- 59101
- Mailing
- 2032 OLD HARDIN ROAD, BILLINGS, MT 59101
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 444110
- Employees
- 43
- Ownership type
- A
Citations
9 citations on file for this inspection.
1910.23 C01
- Issued
- Jan 9, 2015
- Abate by
- Mar 4, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.23(c)(1): Open-sided floors and/or platforms four feet or more above adjacent floor or ground level were not guarded with standard railings (or equivalent) and toeboards: (a) Shop: On or about July 30, 2014 and times prior, employees were exposed to fall of approximately eight feet to the floor below while working on the shed installing asphalt shingles. (b) Shop: On or about July 30, 2014 and times prior, employees were exposed to fall of approximately ten feet to the floor below while working on the shed installing asphalt shingles. (c) Shop: On or about July 30, 2014 and times prior, employees were exposed to fall of approximately twelve feet to the floor below while working on the shed installing asphalt shingles.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.147 C08
- Issued
- Jan 9, 2015
- Abate by
- Feb 5, 2015
- Penalty
- Initial $3,500 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(8): Energy isolation. Lockout or tagout shall be performed only by the authorized employees who are performing the servicing or maintenance. (a) Shop: On or about July 30, 2014 and at times prior, employees were exposed to amputation hazards from the unexpected release of energy while cleaning, repairing and/or replacing parts on equipment but not limited to the Spida Raft Cutter Saw and the Vickers Truss Press.
Recent events (2)
- — I (O) $0
- — Z (S) $3500
1910.151 C
- Issued
- Jan 9, 2015
- Abate by
- Feb 5, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: (a) Receiving: On or about July 30, 2014 and times prior, employees were exposed to injuries to eyes while working on adding fluids to lead/acid batteries of the Nissan Model TN01L18HV Type E Powered Industrial Truck.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.305 A02 X
- Issued
- Jan 9, 2015
- Abate by
- Mar 4, 2015
- Penalty
- Initial $2,800 · Current $1,400 Reduced
General-duty citation text
29 CFR 1910.305(a)(2)(x): Flexible cords and cables were not protected from accidental damage, as might be caused, for example, by sharp corners, projections, and doorways or other pinch points: (a) Shop: On or about July 30, 2014 employees were using the Spida Raft Cutter Saw with damaged electrical conduit. (b) Shop: On or about July 30, 2014 employees were using the Vickers Truss Press with damaged outer sheathing.
Recent events (2)
- — I (S) $1400
- — Z (S) $2800
1910.305 B01 I
- Issued
- Jan 9, 2015
- Abate by
- Feb 5, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(i): Openings through which conductors entered cutout boxes, cabinets, or fittings were not effectively closed: (a) Shop: On or about July 30, 2014 and at times prior, employees were exposed to electric shock due to using the Spida Raft Cutter Saw with damaged fitting.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Jan 9, 2015
- Abate by
- Feb 5, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for the fixed wiring of a structure: (a) Rental Tool Area: On or about July 30, 2014 and times prior, employees were exposed to electric shock while using a 24 Volt Dual Mode Automatic Battery Charger. (b) Power Tool Area: On or about July 30, 2014 and times prior, employees were exposed to electric shock while using a Model 4000 Key Machine. (c) Shop: On or about July 30, 2014 and times prior, employees were exposed to electric shock while using a DeWalt Chop Saw.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Jan 9, 2015
- Abate by
- Feb 5, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors: (a) Shop: On or about July 30, 2014 and times prior, employees were exposed to electric shock while using a DeWalt Chop Saw.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G01 IV D
- Issued
- Jan 9, 2015
- Abate by
- Feb 5, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces: (a) Rental Tool Area: On or about July 30, 2014 and times prior, employees were exposed to electric shock while using a 24 Volt Dual Mode Automatic Battery Charger for the floor scrubber.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 J02 III
- Issued
- Jan 9, 2015
- Abate by
- Feb 5, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iii): Nongrounding-type receptacles and connectors were used for grounding-type attachment plugs: (a) Cashier Station: On or about July 30, 2014 and times prior, employees were exposed to electric shock while using the commercial beverage cooler. (b) Power Tool Area: On or about July 30, 2014 and times prior, employees were exposed to electric shock while using a Model 4000 Key Machine.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at S BAR S Supply Company
View S BAR S Supply Company's full OSHA safety record →
More inspections in this industry (NAICS 444110)
More inspections in MT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339877144.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.