Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: STALLION OILFIELD SERVICES

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of STALLION OILFIELD SERVICES in PEACEMAKER UL 3023 RIG 47, FORT STOCKTON, TX 79735 (NAICS 213112). OSHA activity number 339886913.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Stallion Oilfield Services — free Get an email when a new federal OSHA severe-injury report for Stallion Oilfield Services is published. One employer, no account, unsubscribe in one click.
Site address
PEACEMAKER UL 3023 RIG 47
City
FORT STOCKTON
State
TX
ZIP
79735
Mailing
3708 E. STATE HWY 158, MIDLAND, TX 79706
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213112
Employees
15
Ownership type
A

2 citations on file for this inspection.

1910.304 B03 II A

Other-than-serious 1 instance 12 exposed
Issued
Jan 27, 2015
Abate by
Feb 3, 2015
Penalty
Initial $5,500 · Current $2,600 Reduced

Hazardous substances 8870

29 CFR 1910.304(b)(3)(ii)(A): All 125-volt, single-phase, 15, 20 and 30-ampere receptacle outlets that were not part of the permanent wiring of the building or structure and that were in use by personnel did not have ground-fault circuit-interrupter protection for personnel:    BEHIND MOBILE HOMES: On or about July 30, 2014 the employer did not ensure that extension cords were connected to an operational ground-fault circuit interrupter, exposing employees to an electrical shock hazard.
Recent events (3)
  • — C (S) $5500
  • — F (O) $2600
  • — Z (S) $5500

1910.304 G05

Serious Gravity 5 1 instance 12 exposed
Issued
Jan 27, 2015
Abate by
Jun 4, 2015
Penalty
Initial $5,500 · Current $4,000 Reduced
29 CFR 1910.304(g)(5): Grounding path. The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    BEHIND MOBILE HOMES: On or about July 30, 2014,  an extension cord powering water and sump pumps did not have a ground pin. The path to ground was not continuous and effective, exposing employees to electrical hazards.
Recent events (3)
  • — C (S) $5500
  • — F (S) $4000
  • — Z (S) $5500

View Stallion Oilfield Services's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339886913.