RENO, NV ·
OSHA Inspection: NEVADA AIR NATIONAL GUARD
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NEVADA AIR NATIONAL GUARD in 1776 NATIONAL GUARD WAY - BLDG 700, RENO, NV 89502 (NAICS 928110). OSHA activity number 339895260.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NEVADA AIR NATIONAL GUARD
- Site address
- 1776 NATIONAL GUARD WAY - BLDG 700
- City
- RENO
- State
- NV
- ZIP
- 89502
- Mailing
- 1776 NATIONAL GUARD WAY, RENO, NV 89502
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 928110
- Employees
- 198
- Ownership type
- Federal government (D)
Citations
2 citations on file for this inspection.
1910.101 B
- Issued
- Aug 29, 2014
- Abate by
- Sep 24, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tank cars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6. (a) At the vehicle maintenance hot work area, oxygen and acetylene compressed gas cylinders were in storage more than a month and the pressure regulators were not dis-connected.
Recent events (1)
- · Z (S) $0
1910.253 B04 III
- Issued
- Aug 29, 2014
- Abate by
- Sep 24, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one half hour. (a) At the vehicle maintenance hot work area, oxygen and acetylene compressed gas cylinders were stored together more than a month.
Recent events (1)
- · Z (S) $0
More inspections at Nevada AIR National Guard
View Nevada AIR National Guard's full OSHA safety record →
More inspections in this industry (NAICS 928110)
More inspections in NV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339895260.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.