Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NATIONAL FOREST SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL FOREST SERVICE in 2311 FIREBRAND CIRCLE, MINDEN, NV 89423 (NAICS 813312). OSHA activity number 339896714.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Forest Service — free Get an email when a new federal OSHA severe-injury report for National Forest Service is published. One employer, no account, unsubscribe in one click.
Site address
2311 FIREBRAND CIRCLE
City
MINDEN
State
NV
ZIP
89423
Mailing
2311 FIREBRAND CIRCLE, MINDEN, NV 89423
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
813312
Employees
20
Ownership type
D

4 citations on file for this inspection.

1910.303 B01

Serious Gravity 5 1 instance 2 exposed
Issued
Sep 22, 2014
Abate by
Oct 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(1): 29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees.   (a) At the Sierra Front Inter Agency Dispatch Center Sleeping quarters room, an energized duplex convenience outlet receptacle located approximately four feet above the sink did not have a cover plate.
Recent events (1)
  • — Z (S) $0

1910.304 B03 I

Serious Gravity 1 1 instance 2 exposed
Issued
Sep 22, 2014
Abate by
Oct 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in wet locations were not equipped with ground-fault circuit-interrupter protection for personnel.  (a) At the Sierra Front Inter Agency Dispatch Center Sleeping quarters room, the duplex convenience outlet receptacle located approximately four feet above the sink did not have ground fault circuit interrupter protection for employees.
Recent events (1)
  • — Z (S) $0

1910.22 B01

Other-than-serious 1 instance 2 exposed
Issued
Sep 22, 2014
Abate by
Oct 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.22(b)(1): Aisles and passageways were not kept clear and in good repair, with no obstruction across or in aisles that could create a hazard.  (a) At the employees office area, room 1451, a LAN/DATA cables were laying across an aisle way and creating trip hazards.
Recent events (1)
  • — Z (O) $0

1910.157 C01

Other-than-serious 1 instance 2 exposed
Issued
Sep 22, 2014
Abate by
Oct 16, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.  (a) At the Sierra Front Inter Agency Dispatch Center Lounge/Break room, a large trash can was  sitting in front of the portable fire extinguisher.
Recent events (1)
  • — Z (O) $0

View National Forest Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339896714.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.