Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NATIONAL FOREST SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL FOREST SERVICE in 2980 N. RANCHO DRIVE, LAS VEGAS, NV 89130 (NAICS 813312). OSHA activity number 340206465.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Forest Service — free Get an email when a new federal OSHA severe-injury report for National Forest Service is published. One employer, no account, unsubscribe in one click.
Site address
2980 N. RANCHO DRIVE
City
LAS VEGAS
State
NV
ZIP
89130
Mailing
4701 N. TORREY PINES DRIVE, LAS VEGAS, NV 89130
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
813312
Employees
200
Ownership type
D

8 citations on file for this inspection.

1910.37 B06

Serious Gravity 5 5 instances 5 exposed
Issued
Feb 5, 2015
Abate by
Mar 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(6): Each exit sign must be illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color. Self-luminous or electroluminescent signs that have a minimum luminance surface value of at least .06 footlamberts (0.21 cd/m2) are permitted.  Each exit sign was not illuminated as required:  (a) At the expanded dispatch room west exit door.  (b) At the west radio room.  (c) At the north Initial Attack dispatch room.  (d) At the Helitack bay area.  (e) At the Helitack briefing room.
Recent events (1)
  • — Z (S) $0

1910.165 E

Serious Gravity 1 1 instance 5 exposed
Issued
Feb 5, 2015
Abate by
Feb 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.165(e): Manually operated actuation devices for use in conjunction with employee alarms were not unobstructed, conspicuous and readily accessible.  (a) At the Helitack Briefing room, the manually activated fire alarm annunciator was blocked by a water dispenser.
Recent events (1)
  • — Z (S) $0

1910.176 B

Serious Gravity 1 2 instances 2 exposed
Issued
Feb 5, 2015
Abate by
Feb 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.176(b): Material stored in tiers was not stacked, blocked, interlocked or limited in height so that it was stable and secure against sliding and collapse.  (a) At the Helitack Bay room, brown storage boxes, gray plastic containers, and blue ice containers/coolers were not stable when stored on top of shelves.  (b) At the janitorial closet, boxes of paper towels and bath tissues were not stable when stored on top of the wooden shelves.
Recent events (1)
  • — Z (S) $0

1910.303 B01

Serious Gravity 10 1 instance 5 exposed
Issued
Feb 5, 2015
Abate by
Feb 13, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees.  (a) At the expanded dispatch room, the wall outlet receptacle did not have a cover, energized wire showing.
Recent events (1)
  • — Z (S) $0

1910.303 G01 II

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 5, 2015
Abate by
Feb 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage.  (a) At the electrical room, five partial one gallon paint cans were stored in front of electrical power panels.
Recent events (1)
  • — Z (S) $0

1910.303 H05 III B

Serious Gravity 1 1 instance 2 exposed
Issued
Feb 5, 2015
Abate by
Feb 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(h)(5)(iii)(B): Permanent and conspicuous warning signs were not provided, reading substantially as follows: "DANGER -- HIGH VOLTAGE -- KEEP OUT."  (a) At the emergency generator spaces, no warning signs were posted.
Recent events (1)
  • — Z (S) $0

1910.37 B05

Repeat Gravity 1 1 instance 5 exposed
Issued
Feb 5, 2015
Abate by
Feb 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet).  (a) At the Helitack bay two doors leading to the office and the briefing room were not marked or labeled "NOT AN EXIT".  The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29CFR 1910.37(b)(5) which was contained in OSHA inspection number 315459, citation number 2, item number 2 and was affirmed as a final order on 3/29/2011, with respect to a workplace located at 351 Pacu Lane Bishop, CA 93514.
Recent events (1)
  • — Z (R) $0

1910.157 C01

Repeat Gravity 1 2 instances 5 exposed
Issued
Feb 5, 2015
Abate by
Feb 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries.  (a) At the Helitack Bay area, the portable fire extinguisher was blocked by the freezer.  (b) A portable ABC fire extinguisher was free standing next to the gray file cabinet along the walkway of the break room.  The Bureau of Land Management was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.157(c)(1), which was contained in OSHA inspection number 315492298, citation number 1B, item number 2 and was affirmed as a final order on 8/30/2011, with respect to a workplace located at BLM, Caliente, 1400 S. Front Street, Caliente, NV 89008.
Recent events (1)
  • — Z (R) $0

View National Forest Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340206465.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.