OSHA Inspection: COMPASS MINERALS AMERICA INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of COMPASS MINERALS AMERICA INC. in 4500 13TH COURT, KENOSHA, WI 53140 (NAICS 212393). OSHA activity number 339910820.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Compass Minerals America INC. — free Get an email when a new federal OSHA severe-injury report for Compass Minerals America INC. is published. One employer, no account, unsubscribe in one click.
Site address
4500 13TH COURT
City
KENOSHA
State
WI
ZIP
53140
Mailing
4500 13TH COURT, KENOSHA, WI 53140
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
212393
Employees
70
Ownership type
A

5 citations on file for this inspection.

1910.212 A04

Serious Gravity 5 1 instance 10 exposed
Issued
Feb 11, 2015
Abate by
Jun 1, 2015
Penalty
Initial $3,825 · Current $3,825
29 CFR 1910.212(a)(4):     Revolving drum(s), barrel(s), or container(s) were not guarded by enclosure(s) which were interlocked with the drive mechanism so that the barrel(s), drum(s), or container(s) could not revolve unless the enclosure(s) were in place:    (a) Line 5/6 mixing barrel was not adequately guarded to prevent inadvertent contact with the rotating mixing barrel. Barrier guarding installed did not prevent employees working around the rotating barrel mixer from inadvertently coming into contact with the rotating barrel.    (b) Line 8/9 mixing barrel was not adequately guarded to prevent inadvertent contact with the rotating mixing barrel. Barrier guarding installed did not prevent employees working around the rotating barrel mixer from inadvertently coming into contact with the rotating barrel.
Recent events (2)
  • — I (S) $3825
  • — Z (S) $3825

1910.303 B07 IV

Serious Gravity 5 1 instance 60 exposed
Issued
Feb 11, 2015
Abate by
Mar 31, 2015
Penalty
Initial $3,825 · Current $3,825
29 CFR 1910.303(b)(7)(iv): There were damaged parts that may adversely affect safe operation or mechanical strength of electric equipment, such as parts that were broken, bent, cut or deteriorated by corrosion, chemical action, or overheating:    (a) Breaker Panel - Rail Unloading Area: The Main Breaker panel supplying power to several disconnect boxes and other electrical equipment had a damaged enclosure door. The door did not have a securing mechanism to secure the panel door in a closed position and allow only qualified/authorized personnel to enter the breaker panel.  The breaker panel door securing and locking device was broken out of the door and did not allow the door to be secured and locked in a closed position.    (b)  Main Breaker Panel - Rail Unloading Area: The Main Breaker panel supplying power to several disconnect boxes and other electrical equipment had a damaged enclosure door. The door did not have a securing mechanism to secure the panel door in a closed position and allow only qualified/authorized personnel to enter the breaker panel.   The breaker panel door securing and locking device was broken out of the door and did not allow the door to be secured and locked in a closed position.
Recent events (2)
  • — I (S) $3825
  • — Z (S) $3825

1910.303 E

Other-than-serious 2 instances 60 exposed
Issued
Feb 11, 2015
Abate by
Mar 10, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(e): The manufacturer's name, trademark, or other descriptive marking by which the organization responsible for the product may be identified was not placed on the electrical equipment that was used:    (a) South RANCO Control System for Bin #1 and Bin #2: Electrical disconnect box for the horizontal auger did not have markings to identify the purpose, voltage, current and other ratings as necessary.     (b) Main Breaker Panel - Rail Unloading Area: The Main Breaker panel supplying power to several disconnect boxes and other electrical equipment was not identified with the purpose, voltage, current, wattage or other ratings as necessary.     (c) Breaker Panel - Rail Unloading Area: The 440 volt AC breaker panel supplying power to several disconnect boxes and other electrical equipment was not identified with the purpose, current, wattage or other ratings as necessary.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.303 F03

Other-than-serious 2 instances 10 exposed
Issued
Feb 11, 2015
Abate by
Mar 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(3): The markings required by paragraphs (f)(1) and (f)(2) of 29 CFR 1910.303 were not sufficiently durable to withstand the environment involved:    (a) South RANCO Control System for Bin #1 and Bin #2: Electrical disconnect box for the horizontal auger did not have  markings that were of a durable material to withstand the corrosive environment created by salt aggregate processing.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 A01 I

Serious Gravity 5 2 instances 10 exposed
Issued
Feb 11, 2015
Abate by
Feb 18, 2015
Penalty
Initial $3,825 · Current $0 Reduced
29 CFR 1910.305(a)(1)(i): Metal raceways, cable trays, cable armor, cable sheath, enclosures, frames, fittings, and noncurrent-carrying parts that are to serve as grounding conductors, with or without the use of supplementary equipment grounding conductors, were not effectively bonded where necessary to ensure electrical continuity and did not have the capacity to conduct safely any fault current likely to have been imposed on them:    (a) Bin #2 Area: Liquidtight Flexible Metal Conduit (LFMC) located to the right of bin #2 conveyor salt shoot was broken away from the connection fitting exposing electrical wiring and exposing employees to an electrical shock hazard.    (b) Ranco Bin D Utility: Liquidtight Flexible Metal Conduit (LFMC) run from 24' blend auger disconnect to the 13-124 motor was broken away from the motor fitting connection exposing the electrical wiring. This exposed employees to an electrical shock hazard.