GRAND CANYON, AZ ·
OSHA Inspection: NATIONAL PARK SERVICE GRAND CANYON, TRAIL CREW OPERATIONS
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE GRAND CANYON, TRAIL CREW OPERATIONS in BUILDING 90, SUNSET STREET, GRAND CANYON, AZ 86023 (NAICS 712190). OSHA activity number 339941460.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- BUILDING 90, SUNSET STREET
- City
- GRAND CANYON
- State
- AZ
- ZIP
- 86023
- Mailing
- P.O. BOX 129, GRAND CANYON, AZ 86023
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 712190
- Employees
- 45
- Ownership type
- Federal government (D)
Citations
12 citations on file for this inspection.
1910.23 D01
- Issued
- Jan 5, 2015
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(d)(1): Every flight of stairs having four or more risers was not be equipped with standard stair railings or standard handrails as specified in paragraphs (d)(1)(i) through (v) of this section, the width of the stair to be measured clear of all obstructions except handrails. (a) At the NPS Trails Operations Building 90, the front stairways with 6 risers did not have a hand rail.
Recent events (1)
- · Z (S) $0
1910.23 E01
- Issued
- Jan 5, 2015
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.23(e)(1): The railing did not have a vertical height of 42 inches nominal from upper surface of top rail to floor, platform, runway, or ramp level and the intermediate rail was not approximately halfway between the top rail and the floor, platform, runway, or ramp. (a) At the NPS Trails Crew Barn, Building 75 Blacksmith and Building 78, Mezzanine Storage areas did not have standard railing to the correct height.
Recent events (1)
- · Z (S) $0
1910.37 B02
- Issued
- Jan 5, 2015
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit." (a) At the NPS Trails Crew Operations Building 90, exits were not clearly marked by a sign reading "EXIT".
Recent events (1)
- · Z (S) $0
1910.37 B05
- Issued
- Jan 5, 2015
- Abate by
- Jan 20, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet). (a) At the NPS Trail Crew Operations Barn, the door leading to the horse coral was not marked or labeled "NOT AN EXIT".
Recent events (1)
- · Z (S) $0
1910.157 E02
- Issued
- Jan 5, 2015
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly. (a) At the NPS Trail Crew Operations Building 90, inspection tags on fire extinguishers indicated the last inspection dates were January and June 2014 respectively.
Recent events (1)
- · Z (S) $0
1910.242 B
- Issued
- Jan 5, 2015
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 psi. (a) At the NPS Trail Crew Operations Building 75 Blacksmith Shop, compressed air used to clean the dust off of a chain saw was not reduced to 30 psi.
Recent events (1)
- · Z (S) $0
1910.303 B02
- Issued
- Jan 5, 2015
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. (a) At the NPS Trail Crew Operations, Building 78, a re-locatable power tap was used in the remodeling site to plug in two chop saws.
Recent events (1)
- · Z (S) $0
1910.303 G02 I D
- Issued
- Jan 5, 2015
- Abate by
- Jan 20, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i)(D): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by elevation of 2.44 m (8.0 ft) or more above the floor or other working surface. (a) At the NPS Trails Crew Operations, Blacksmith Building 75, fluorescent lights did not have covers. (b) Building 78, incandescent light bulbs did not have covers. (c) Building 79, Leather Shop, fluorescent lights did not have covers.
Recent events (1)
- · Z (S) $0
1910.304 B03 I
- Issued
- Jan 5, 2015
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or wet locations were not equipped with ground-fault circuit-interrupter protection for personnel. (a) At the NPS Trails Crew Operations, Blacksmith Shop Building 75, electrical outlet receptacle next to the sink was non GFCI.
Recent events (1)
- · Z (S) $0
1910.304 G05
- Issued
- Jan 5, 2015
- Abate by
- Jan 9, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective. (a) At the NPS Trails Crew Operations, Barn, a yellow extension cord used for lighting the loft was missing a ground pin.
Recent events (1)
- · Z (S) $0
1910.305 B02
- Issued
- Jan 5, 2015
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose. (a) At the NPS Trails Crew Operations, Hay Barn, the outdoor power supply outlet for the hay conveyor used to feed the horses did not have a cover.
Recent events (1)
- · Z (S) $0
1910.22 D01
- Issued
- Jan 5, 2015
- Abate by
- Jan 29, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate. (a) At the NPS Trails Crew Operations Barn and Building 75 Blacksmith, Mezzanine Storage areas did not have the maximum load capacity posted or marked.
Recent events (1)
- · Z (O) $0
More inspections at National Park Service Grand Canyon, Trail Crew Operations
View National Park Service Grand Canyon, Trail Crew Operations's full OSHA safety record →
More inspections in this industry (NAICS 712190)
More inspections in AZ
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 339941460.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.