EXCELSIOR SPRINGS, MO —
OSHA Inspection: MAGNA SEATING
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of MAGNA SEATING in 301 S MCCLEARY ROAD, EXCELSIOR SPRINGS, MO 64024 (NAICS 336360). OSHA activity number 339947871.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MAGNA SEATING
- Site address
- 301 S MCCLEARY ROAD
- City
- EXCELSIOR SPRINGS
- State
- MO
- ZIP
- 64024
- Mailing
- 301 S MCCLEARY ROAD, EXCELSIOR SPRINGS, MO 64024
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 336360
- Employees
- 225
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.303 B02
- Issued
- Sep 30, 2014
- Abate by
- Nov 18, 2014
- Penalty
- Initial $3,600 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: (a) On September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.- in the Production Shop, employees were exposed to electrical hazards created when Dayton Fan model 9K950 that was listed and labeled for 3 prong electrical connection were intentionally cut off by maintenance personnel and feed directly in powered electrical junction boxes. (b) On September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.- in the Production Shop, employees were exposed to electrical hazards created when Dayton Fan model 1RWB4 that was listed and labeled for 3 prong electrical connection were intentionally cut off by maintenance personnel and feed directly in powered electrical junction boxes. (c) On September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.- in the Loading Dock area, employees were exposed to electrical hazards created when Hubbell brand Dock lights that was listed and labeled for 3 prong connection were intentionally cut off by maintenance personnel and feed directly in powered electrical junction boxes. (d) On September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.- in the Loading Dock area, Production area and storage area, employees were exposed to electrical hazards created when Fluorescent Lighting fixtures listed and labeled for 3 prong electrical connection were intentionally cut off by maintenance personnel and feed directly in powered electrical junction boxes. Abatement certification is required for this item. Use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
- — I (S) $0
- — Z (S) $3600
1910.305 B01
- Issued
- Sep 30, 2014
- Abate by
- Nov 18, 2014
- Penalty
- Initial $3,600 · Current $0 Reduced
General-duty citation text
29 CFR 1910.305(b)(1): Openings through which conductors enter boxes, cabinets, or fittings were not effectively closed: (a) On or about September 17, 2014, at 301 McCleary, Excelsior Springs, Missouri.- employees were exposed to serious electrical hazard, in that the power fourplex outlet positioned at the desk of maintenance personnel in the maintenance office, was not effectively closed. Abatement certification is required for this item; use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
- — I (S) $0
- — Z (S) $3600
1910.305 G01 IV A
- Issued
- Sep 30, 2014
- Abate by
- Nov 2, 2014
- Penalty
- Initial $3,600 · Current $2,520 Reduced
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) On or about September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.- in the Production Shop, employees were exposed to an electrical hazard when florescent light fixtures used to provide lights to workers were connected one to another (daisy chained ) with flexible cord and used as a permanent fixed wiring of a structure. Abatement certification is required for this item; use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
- — I (S) $2520
- — Z (S) $3600
1910.305 G01 IV D
- Issued
- Sep 30, 2014
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords were attached to building surfaces: (a) On or about September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.- employees in the material storage area were exposed to an electrical hazard when a relocatable power tap device was attached to the inside of a metal storage supply shelf with zip ties.
Recent events (2)
- — I (S) $0
- — Z (S) $0
More inspections at Magna Seating
View Magna Seating's full OSHA safety record →
More inspections in this industry (NAICS 336360)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339947871.