Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MAGNA SEATING

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MAGNA SEATING in 301 S MCCLEARY ROAD, EXCELSIOR SPRINGS, MO 64024 (NAICS 336360). OSHA activity number 339947871.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Magna Seating — free Get an email when a new federal OSHA severe-injury report for Magna Seating is published. One employer, no account, unsubscribe in one click.
Establishment
MAGNA SEATING
Site address
301 S MCCLEARY ROAD
City
EXCELSIOR SPRINGS
State
MO
ZIP
64024
Mailing
301 S MCCLEARY ROAD, EXCELSIOR SPRINGS, MO 64024
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
336360
Employees
225
Ownership type
A

4 citations on file for this inspection.

1910.303 B02

Deleted Serious Gravity 5 1 instance 4 exposed
Issued
Sep 30, 2014
Abate by
Nov 18, 2014
Penalty
Initial $3,600 · Current $0 Reduced
29 CFR 1910.303(b)(2):  Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:   (a) On September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.- in the Production Shop, employees were exposed to electrical hazards created when Dayton Fan model 9K950 that was listed and labeled for 3 prong electrical connection were intentionally cut off by maintenance personnel and feed directly in powered electrical junction boxes.  (b) On September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.-  in the Production Shop, employees were exposed to electrical hazards created when Dayton Fan model 1RWB4 that was listed and labeled for 3 prong electrical connection were intentionally cut off by maintenance personnel and feed directly in powered electrical junction boxes.  (c) On September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.-  in the Loading Dock area, employees were exposed to electrical hazards created when Hubbell brand Dock lights that was listed and labeled for 3 prong connection were intentionally cut off by maintenance personnel and feed directly in powered electrical junction boxes.   (d) On September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.-  in the Loading Dock area, Production area and storage area, employees were exposed to electrical hazards created when Fluorescent Lighting fixtures listed and labeled for 3 prong electrical connection were intentionally cut off by maintenance personnel and feed directly in powered electrical junction boxes.   Abatement certification is required for this item.  Use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3600

1910.305 B01

Deleted Serious Gravity 5 1 instance 5 exposed
Issued
Sep 30, 2014
Abate by
Nov 18, 2014
Penalty
Initial $3,600 · Current $0 Reduced
29 CFR 1910.305(b)(1):   Openings through which conductors enter boxes, cabinets, or fittings were not effectively closed:  (a) On or about September 17, 2014, at 301 McCleary, Excelsior Springs, Missouri.- employees were exposed to serious electrical hazard, in that the power fourplex outlet positioned at the desk of maintenance personnel in the maintenance office, was not effectively closed.     Abatement certification is required for this item; use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3600

1910.305 G01 IV A

Serious Gravity 5 1 instance 10 exposed
Issued
Sep 30, 2014
Abate by
Nov 2, 2014
Penalty
Initial $3,600 · Current $2,520 Reduced
29 CFR 1910.305(g)(1)(iv)(A):     Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:      (a) On or about September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.- in the Production Shop, employees were exposed to an electrical hazard when florescent light fixtures  used to provide lights to workers  were connected one to another (daisy chained ) with flexible cord and used as a permanent fixed wiring of a structure.       Abatement certification is required for this item; use the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET for this purpose.
Recent events (2)
  • — I (S) $2520
  • — Z (S) $3600

1910.305 G01 IV D

Serious Gravity 1 1 instance 5 exposed
Issued
Sep 30, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D):   Flexible cords were attached to building surfaces:   (a) On or about September 11, 2014, at worksite 301 McCleary, Excelsior Springs, Missouri.- employees in the material storage area were exposed to an electrical hazard when a relocatable power tap device was attached to the inside of a metal storage supply shelf with zip ties.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0