Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: TAMPA STEEL ERECTING COMPANY

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of TAMPA STEEL ERECTING COMPANY in 5127 BLOOMINGDALE AVENUE, TAMPA, FL 33619 (NAICS 332312). OSHA activity number 339966939.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Tampa Steel Erecting Company — free Get an email when a new federal OSHA severe-injury report for Tampa Steel Erecting Company is published. One employer, no account, unsubscribe in one click.
Site address
5127 BLOOMINGDALE AVENUE
City
TAMPA
State
FL
ZIP
33619
Mailing
5127 BLOOMINGDALE AVENUE, TAMPA, FL 33619
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
97
Ownership type
A

10 citations on file for this inspection.

1910.23 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 20, 2015
Penalty
Initial $3,080 · Current $3,000 Reduced
29 CFR 1910.23(a)(2): Ladderway floor opening(s) or platform(s) were not guarded by a standard railing with standard toeboard(s) on all exposed sides (except at the entrance to opening) with passage through the railing either provided with a swinging gate or so offset that a person could walk directly into the opening:    a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about September 24, 2014. Employees were working in the area of the media blasting machine that did not have a swinging gate. Employees were exposed to a 7 feet fall hazard.
Recent events (3)
  • — J (S) $3000
  • — C (S) $3080
  • — Z (S) $3080

1910.242 B

Other-than-serious 50 instances 92 exposed
Issued
Mar 20, 2015
Abate by
Mar 26, 2015
Penalty
Initial $5,390 · Current $1,700 Reduced
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:    a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about, 24 September, 2014. Employees were using compressed air to clean material and clothing that was at a pressure greater than 30 p.s.i. Air pressure that was used was approximately 120 p.s.i.
Recent events (3)
  • — J (O) $1700
  • — C (S) $5390
  • — Z (S) $5390

1910.303 B07 I

Serious Gravity 5 1 instance 10 exposed
Issued
Mar 20, 2015
Penalty
Initial $3,080 · Current $3,080
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment.     a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about, 24 September, 2014. At the main power panel that housed the main breakers for the stationary welding machines, one of the breakers was missing.
Recent events (3)
  • — J (S) $3080
  • — C (S) $3080
  • — Z (S) $3080

1910.304 G06 VI C 5

Serious Gravity 10 1 instance 1 exposed
Issued
Mar 20, 2015
Abate by
Mar 26, 2015
Penalty
Initial $6,930 · Current $6,390 Reduced
29 CFR 1910.304(g)(6)(vi)(C)(5): The employer did not ensure that exposed noncurrent-carrying metal parts of cord-and-plug connected equipment that may become energized was grounded when the equipment was used in damp or wet locations by employees standing on the ground.     a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about 24 September, 2014. Employees were using 2 wire non grounded handheld lamps. the lamp cord was repaired and the polarity was reversed. Employee was in the process of changing the light bulb inside of one of the metal archways when contact was made with the metal casing that was energized and employee was electrocuted.
Recent events (3)
  • — J (S) $6390
  • — C (S) $6930
  • — Z (S) $6930

1910.305 A02 IX

Other-than-serious 6 instances 3 exposed
Issued
Mar 20, 2015
Abate by
Apr 1, 2015
Penalty
Initial $4,620 · Current $1,000 Reduced
29 CFR 1910.305(a)(2)(ix): All lamps for general illumination were not protected from accidental contact or breakage by a suitable fixture or lampholder with a guard. Brass shell, paper-lined sockets, or other metal-cased sockets may not be used unless the shell is grounded.       a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about 24 September, 2014. Employees working in the material and tool storage room were stacking materials on shelves where the illumination lamps were not protected from accidental contact or breakage.
Recent events (3)
  • — J (O) $1000
  • — C (S) $4620
  • — Z (S) $4620

1910.215 A04

Other-than-serious 1 instance 2 exposed
Issued
Mar 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:  a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about 24 September, 2014. Employees were using a bench grinder with a work rest that was not properly adjusted closely to the wheel. The work rest measured approximately 3/16 inch from the wheel.
Recent events (3)
  • — J (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.215 B09

Other-than-serious 1 instance 2 exposed
Issued
Mar 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:   a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about 24 September, 2014. Employees were using a bench top grinder that did not have the adjustable tongue less than 1/4 inch opening above the abrasive wheel. The tongue guard was adjusted to approximately 1/2 inch above the abrasive wheel.
Recent events (3)
  • — J (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.253 B02 II

Other-than-serious 2 instances 4 exposed
Issued
Mar 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(2)(ii): Assigned storage spaces for cylinders were not located where cylinders could not be knocked over or damaged by passing or falling objects, or subject to tampering by unauthorized persons:  a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about September 24, 2014. Two compressed gases tanks, acetylene and carbon dioxide, were stored in the pipe shop and not protected from being knocked over or damage by passing or falling objects.
Recent events (3)
  • — J (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.303 F02

Other-than-serious 21 instances 2 exposed
Issued
Mar 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about 24 September, 2014. Panel box breakers supplying power to outlets in the North pipe shop were not labeled to identify purpose of each breaker.
Recent events (3)
  • — J (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.305 G02 III

Other-than-serious 1 instance 5 exposed
Issued
Mar 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about 24 September, 2014. Employees were getting ice from the ice machine located in the north pipe shop break room area. The power supply cord for the ice machine located in the north pipe shop was missing strain relief.
Recent events (3)
  • — J (O) $0
  • — C (O) $0
  • — Z (O) $0

View Tampa Steel Erecting Company's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339966939.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.