OSHA Inspection: NEW PENN MOTOR EXPRESS, INC.

Follow-up inspection · Health discipline

On , OSHA opened a follow-up health inspection of NEW PENN MOTOR EXPRESS, INC. in 28 STERLING ROAD, N BILLERICA, MA 01862 (NAICS 484121). OSHA activity number 339968794.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch NEW Penn Motor Express, INC. — free Get an email when a new federal OSHA severe-injury report for NEW Penn Motor Express, INC. is published. One employer, no account, unsubscribe in one click.
Site address
28 STERLING ROAD
City
N BILLERICA
State
MA
ZIP
01862
Mailing
625 SOUTH 5TH AVENUE, LEBANON, PA 17042
Inspection type
Follow-up (F)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
484121
Employees
132
Ownership type
A

6 citations on file for this inspection.

1910.303 B07 IV

Other-than-serious 1 instance 50 exposed
Issued
Jan 26, 2015
Abate by
Mar 13, 2015
Penalty
Initial $4,000 · Current $1,000 Reduced
29 CFR 1910.303(b)(7)(iv): Electrical equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating:    (a)  Location - Dock Area  On or about 9/23/14, an electrical outlet box and its conduit were damaged and hanging where both had been knocked off the wall.
Recent events (2)
  • — I (O) $1000
  • — Z (S) $4000

1910.303 G01 II

Serious Gravity 5 1 instance 50 exposed
Issued
Jan 26, 2015
Abate by
Mar 13, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:    (a) Location - Dock Area  On or about 9/23/14, pallet jacks were stored in front of electrical panel boxes and motor starts.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.304 G05

Serious Gravity 5 1 instance 50 exposed
Issued
Jan 26, 2015
Abate by
Mar 13, 2015
Penalty
Initial $4,000 · Current $2,500 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    (a)  Location - Dock Area  On or about 9/23/14, two electrical plugs had missing grounding pins.
Recent events (2)
  • — I (S) $2500
  • — Z (S) $4000

1910.305 G01 IV A

Serious Gravity 1 1 instance 50 exposed
Issued
Jan 26, 2015
Abate by
Mar 13, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    (a) Location - Dock Area  On or about 9/23/14, an extension cord was permanently installed in lieu of available electrical outlets.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Serious Gravity 1 1 instance 50 exposed
Issued
Jan 26, 2015
Abate by
Mar 13, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and cables were run through holes in walls, ceilings, or floors:  (a) Location - Dock Area On or about 9/23/14, an electrical cord was run around and/or through building components including, but not limited to, pipes, conduit, the ceiling and a wall.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.20 B02

Serious Gravity 5 1 instance 50 exposed
Issued
Jan 26, 2015
Abate by
Jun 15, 2015
Penalty
Initial $6,000 · Current $3,000 Reduced
29 CFR 1926.20(b)(2): The employer did not initiate and/or maintain a safety program which provides for frequent and regular inspections of jobsites, materials, and equipment to be made by a competent person:    (a)  Location - Tractor Trailer Dock Parking Area  On or about 9/23/14, multiple holes in the tractor trailer dock parking area were left open for over one month after loose and cracking cement had been cut out.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $6000

View NEW Penn Motor Express, INC.'s full OSHA safety record →