Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: H.M. RICHARDS, INC.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of H.M. RICHARDS, INC. in 145 TOWERY ROAD, GUNTOWN, MS 38849 (NAICS 337121). OSHA activity number 339975708.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch H.M. Richards, INC. — free Get an email when a new federal OSHA severe-injury report for H.M. Richards, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
H.M. RICHARDS, INC.
Site address
145 TOWERY ROAD
City
GUNTOWN
State
MS
ZIP
38849
Mailing
P. O. BOX 373, BALDWYN, MS 38824
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
Yes
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337121
Employees
912
Ownership type
A

10 citations on file for this inspection.

1910.212 A03 II

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 27, 2015
Penalty
Initial $5,500 · Current $4,000 Reduced
29 CFR 1910.212(a)(3)(ii): Point(s) of operation of machinery were not guarded to prevent employee(s) from having any part of their body in the danger zone(s) during operating cycle(s):    a) 414 CR 2790 in Guntown, MS - On or about October 7, 2014, in the mill department, the "T" nut machine was not guarded to prevent employee's hand from contacting the point of operation.
Recent events (2)
  • — I (S) $4000
  • — Z (S) $5500

1910.215 B09

Other-than-serious 2 instances 9 exposed
Issued
Feb 27, 2015
Abate by
Mar 23, 2015
Penalty
Initial $3,300 · Current $1,000 Reduced
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:    a) 414 CR 2790 in Guntown, MS - In the maintenance shop, on or about October 7, 2014, the distance of the adjustable tongue guard on the Performance Tool 6 inch bench grinder was .75 inch on the left and .5 inch on the right.    b) 414 CR 2790 in Guntown, MS - In the maintenance shop, on or about October 7, 2014, the distance of the adjustable tongue guard on the scissor grinder was .375 inch on the left and 1 inch on the right.
Recent events (2)
  • — I (O) $1000
  • — Z (S) $3300

1910.303 G02 I

Serious Gravity 10 1 instance 40 exposed
Issued
Feb 27, 2015
Penalty
Initial $7,000 · Current $4,200 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision:    a) 145 Towery Road in Guntown, MS - On or about October 2, 2014, employees were exposed to electrical burns and shocks because an energized wire was hanging in the door opening and path through the door used to enter and exit the building.
Recent events (2)
  • — I (S) $4200
  • — Z (S) $7000

1910.304 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Feb 27, 2015
Penalty
Initial $4,400 · Current $2,450 Reduced
29 CFR 1910.304(a)(1): Conductors used as grounded conductors were not identifiable and distinguishable from all other conductors:    a) 145 Towery Road in Guntown, MS - On or about October 1, 2014, the grounded conductor was the same color as the other conductors and there was no other markings for identification.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $4400

1910.304 G05

Serious Gravity 5 1 instance 3 exposed
Issued
Feb 27, 2015
Penalty
Initial $4,400 · Current $2,450 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    a) 414 CR 2790 in Guntown, MS - On or about October 7, 2014, in the shipping department, the floor fan was missing the ground pin on the plug.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $4400

1910.332 B01

Serious Gravity 10 1 instance 9 exposed
Issued
Feb 27, 2015
Abate by
Mar 23, 2015
Penalty
Initial $7,000 · Current $6,000 Reduced
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:    a) 145 Towery Road in Guntown, MS - On or about October 1, 2014 at the gang rib saw number 1, employees were not trained as a qualified person to perform the assigned job assignment such as; working with electrical equipment, removing wiring, testing fuses, checking voltages.
Recent events (2)
  • — I (S) $6000
  • — Z (S) $7000

1910.334 C01

Serious Gravity 10 250 instances 9 exposed
Issued
Feb 27, 2015
Abate by
Mar 23, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.334(c)(1): Unqualified persons performed testing work on electric circuits or equipment.  a) 414 CR 2790 in Guntown, MS - On or about October 9, 2014, employees use a volt-ohm meter to test for voltages on sewing machines and other types of equipment, change fuses, check voltages of 110 to 480 volts 3 phase, circuit boards, ran electric from buss plugs to equipment such as sewing machines, saws, routers, etc.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02

Serious Gravity 10 1 instance 1 exposed
Issued
Feb 27, 2015
Penalty
Initial $7,000 · Current $6,000 Reduced
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2):    a) 145 Towery Road in Guntown, MS - On or about October 1, 2014, the buss plug disconnect to the gang rip saw #1 did not have a written Lockout/Tagout procedure that included among others; the deenergizing of equipment, application of locks and tags, and verification of the deenergized condition for performing the task of removing the feeder wires from the saw.
Recent events (2)
  • — I (S) $6000
  • — Z (S) $7000

1910.303 F02

Serious Gravity 1 2 instances 9 exposed
Issued
Feb 27, 2015
Penalty
Initial $16,500 · Current $7,000 Reduced
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:    a) 145 Towery Road in Guntown, MS - On or about October 2, 2014, a circuit breaker panel was not labeled to indicate the purpose of each breaker of which a couple of circuit breakers went to a floor mounted scissor lift.    b) 414 CR 2790 in Guntown, MS - On or about October 7, 2014, a main 1600 amp switchboard located in upholstery at the end of the tunnel had 2 circuit breakers feeding sub-panels were not labeled.    H.M. Richards, Inc. was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.303(f)(2), which was contained in OSHA inspection number 315302596, citation number 1, item number 1 and was affirmed as a final order on May 17, 2011, with respect to a workplace located at 414 County Road 2790 in Guntown, MS 38849.
Recent events (2)
  • — I (S) $7000
  • — Z (R) $16500

1910.305 G02 III

Other-than-serious 1 instance 3 exposed
Issued
Feb 27, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  a) 414 CR 2790 in Guntown, MS - On or about October 7, 2014, in the shipping department, the flexible cord on a 42 inch diameter fan on the floor had a defective strain relief on the plug end and where the cord entered the fan housing.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View H.M. Richards, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 339975708.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.