DANVILLE, PA —
OSHA Inspection: FABTEX, INCORPORATED
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of FABTEX, INCORPORATED in 111 WOODBINE LANE, DANVILLE, PA 17821 (NAICS 314121). OSHA activity number 340023688.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- FABTEX, INCORPORATED
- Site address
- 111 WOODBINE LANE
- City
- DANVILLE
- State
- PA
- ZIP
- 17821
- Mailing
- 111 WOODBINE LANE, DANVILLE, PA 17821
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 314121
- Employees
- 90
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.213 H04
- Issued
- Apr 2, 2015
- Abate by
- Apr 22, 2015
- Penalty
- Initial $2,380 · Current $1,665 Reduced
General-duty citation text
29 CFR 1910.213(h)(4): Radial saw(s) were not installed in a manner so as to cause the cutting head to return gently to the starting position when released by the operator. a) Top Treatment, 111 Woodbine Lane, Danville, PA - Employees cut wood daily with a Craftsman 10" Radial Arm Saw whose cutting head did not retract to the starting position when released. Employees were exposed to amputation hazards while pushing the cutting head back to the starting position, on or about October 21, 2014. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
- — I (S) $1665
- — Z (S) $2380
1910.303 B02
- Issued
- Apr 2, 2015
- Abate by
- Jun 30, 2015
- Penalty
- Initial $1,785 · Current $1,250 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. a) Cutting, 111 Woodbine Lane, Danville, PA - Employees used in-house made junction boxes with plug-in jacks daily to provide electrical power from a trolley busway to equipment. The electrical components of the junction boxes (metallic outlet box, metal connectors, flexible cord) were not used in accordance with each component listing and exposed the employees to a contact with electrical current hazard, as observed on or about October 21, 2014. b) Drapery, 111 Woodbine Lane, Danville, PA - Employees used in-house made junction boxes with plug-in jacks daily to provide electrical power from a trolley busway to equipment. The electrical components of the junction boxes (metallic outlet box, metal connectors, flexible cord) were not used in accordance with each component listing and exposed the employees to a contact with electrical current hazard, as observed on or about October 21, 2014. c) Bedding, 111 Woodbine Lane, Danville, PA - Employees used in-house made junction boxes with plug-in jacks daily to provide electrical power from a trolley busway to equipment. The electrical components of the junction boxes (metallic outlet box, metal connectors, flexible cord) were not used in accordance with each component listing and exposed the employees to a contact with electrical current hazard, as observed on or about October 21, 2014. d) Inspection station directly northeast of the Utica Mill Specialty Machinery Slitter, Bedding, 111 Woodbine Lane, Danville, PA - Employees operated a fluorescent light daily by plugging/unplugging a flexible cord (w/attachment plug) that provided electrical power to the light by a connection within a metallic outlet box. The electrical components (flexible cord, attachment plug, metallic outlet box) were not used in accordance with each component listing and exposed the employees to a contact with electrical current hazard, as observed on or about October 21, 2014. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
- — I (S) $1250
- — Z (S) $1785
1910.305 G01 IV A
- Issued
- Apr 2, 2015
- Abate by
- Jun 30, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure. a) Cutting, 111 Woodbine Lane, Danville, PA - Employees used flexible cord attached to in-house made junction boxes on a trolley busway system daily to provide electrical power from a trolley busway to equipment. The flexible cords were used as a substitute for fixed wiring and exposed the employees to a contact with electrical current hazard, as observed on or about October 21, 2014. b) Drapery, 111 Woodbine Lane, Danville, PA - Employees used flexible cord attached to in-house made junction boxes on a trolley busway system daily to provide electrical power from a trolley busway to equipment. The flexible cords were used as a substitute for fixed wiring and exposed the employees to a contact with electrical current hazard, as observed on or about October 21, 2014. c) Bedding, 111 Woodbine Lane, Danville, PA - Employees used flexible cord attached to in-house made junction boxes on a trolley busway system daily to provide electrical power from a trolley busway to equipment. The flexible cords were used as a substitute for fixed wiring and exposed the employees to a contact with electrical current hazard, as observed on or about October 21, 2014. d) Inspection station directly northeast of the Utica Mill Specialty Machinery Slitter, Bedding, 111 Woodbine Lane, Danville, PA - Employees operated a fluorescent light daily by plugging/unplugging a flexible cord (w/attachment plug) that provided electrical power to the light. The flexible power cord was used as a substitute for fixed wiring and exposed the employees to a contact with electrical current hazard, as observed on or about October 21, 2014. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.215 A04
- Issued
- Apr 2, 2015
- Abate by
- Apr 22, 2015
- Penalty
- Initial $1,785 · Current $1,250 Reduced
General-duty citation text
29 CFR 1910.215(a)(4): Grinding machinery was not used with work rest(s) to support offhand grinding work. a) Maintenance Area, 111 Woodbine Lane, Danville, PA - Employees sharpened scissors and cutting blades daily without work rests attached to a Craftsman 6" Bench Grinder. Employees were exposed to caught-in and struck-by hazards, on or about October 21, 2014. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
- — I (S) $1250
- — Z (S) $1785
1910.212 B
- Issued
- Apr 2, 2015
- Abate by
- Apr 22, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving. a) Maintenance Shop, 111 Woodbine Lane, Danville, PA - Employees operated the C.D.E. Enterprises 16-Speed Drill Press Model 1413 (Serial No. 95640) that was not securely anchored to prevent walking or moving. Employees were exposed to a struck-by hazard on or about October 21, 2014. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.242 B
- Issued
- Apr 2, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i. a) Facility, 111 Woodbine Lane, Danville, PA - Employees used compressed air guns to clean dust, threads and fluff from work areas and machines. Employees were exposed to struck-by hazards caused by high pressure air, on or about October 21, 2014. In accordance with 29 CFR 1903.19(c), abatement certification is not required for this violation. The hazardous conditions were corrected during the inspection.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Fabtex, Incorporated
View Fabtex, Incorporated's full OSHA safety record →
More inspections in this industry (NAICS 314121)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340023688.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.