CAMERON, WV ·
OSHA Inspection: DAVIS H. ELLIOT COMPANY, INC.
Fatality or catastrophe inspection · Safety discipline
At a glance
On , OSHA opened a fatality or catastrophe safety inspection of DAVIS H. ELLIOT COMPANY, INC. in 57 GOSHORN ROAD, CAMERON, WV 26033 (NAICS 238210). OSHA activity number 340060730.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- DAVIS H. ELLIOT COMPANY, INC.
- Site address
- 57 GOSHORN ROAD
- City
- CAMERON
- State
- WV
- ZIP
- 26033
- Mailing
- 675 BLUE SKY PARKWAY, LEXINGTON, KY 40502
What kind of inspection was it?
- Inspection type
- Fatality or catastrophe (M)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 5
- Ownership type
- Private (A)
Citations
4 citations on file for this inspection.
1910.269 A04 VIII
- Issued
- Apr 13, 2015
- Abate by
- Jun 23, 2017
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.269(a)(4)(viii): The employer did not determine existing environmental conditions related to the safety of the work to be performed before work on or near electric lines or equipment was started: a.) Davis H. Elliot Company, Inc., Cameron WV: On or about 11/04/14, the employer did not determine the existing environmental conditions that could have effected safety, in that they did not evaluate the terrain to determine if changes in elevation could create conditions that could cause the neutral line that was being strung along the ground to contact an overhead 7200 volt energized primary line. ABATEMENT DOCUMENTATION IS REQUIRED.
Recent events (3)
- · R (S) $7000
- · C (S) $7000
- · Z (S) $7000
1910.269 C04 II A
- Issued
- Apr 13, 2015
- Abate by
- May 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.269(c)(4)(ii)(A): A more extensive briefing was not conducted when the work was complicated or particularly hazardous: a.) Davis H. Elliot Company, Inc., Goshorn Road, Cameron WV: On or about 11/04/14, during the job briefing, the employer did not address the possibility of the neutral line being strung along the ground making contact with the overhead 7200 volt energized line. ABATEMENT DOCUMENTATION IS REQUIRED.
Recent events (3)
- · F (S) $0
- · C (S) $0
- · Z (S) $0
1910.269 L03 III
- Issued
- Apr 13, 2015
- Abate by
- Jun 23, 2017
- Penalty
- Initial $7,000 · Current $7,000
General-duty citation text
29 CFR 1910.269(l)(3)(iii): The employer did not ensure that no employee(s) approached or took conductive objects closer to exposed energized parts than the employers established minimum approach distance: a.) Davis H. Elliot Company, Inc., Goshorn Road Cameron WV: On or about 11/03/14, the employer did not ensure employees maintained the established minimum approach distance of 1'1" when a neutral line being pulled on the ground made contact with the energized 7200 volt primary line. ABATEMENT DOCUMENTATION IS REQUIRED.
Recent events (3)
- · R (S) $7000
- · C (S) $7000
- · Z (S) $7000
1910.269 Q02 I
- Issued
- Apr 13, 2015
- Abate by
- Jun 23, 2017
- Penalty
- Initial $7,000 · Current $0 Reduced
General-duty citation text
29 CFR 1910.269(q)(2)(i): The employer did not use the tension-stringing method, barriers, or other equivalent measures to minimize the possibility that conductors and cables being installed or removed would contact energized power lines or equipment. a.) Davis H. Elliot Company, Inc., 57 Goshorn Road, Cameron WV: On or about 11/04/14, the company did not employ the tension-stringing method, install insulating barriers, or use other equivalent methods to prevent the neutral line being strung along the ground from contacting a 7200 volt energized primary line. The neutral line contacted the energized line as it was pulled, under tension, through mountainous terrain. ABATEMENT DOCUMENTATION IS REQUIRED.
Recent events (3)
- · R (S) $0
- · C (S) $7000
- · Z (S) $7000
More inspections at Davis H. Elliot Company, INC.
View Davis H. Elliot Company, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in WV
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 340060730.