Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,288Inspections Most recent open 2026-07-24 Last loaded 2026-07-29

OSHA Inspection: USDA-FARM SERVICE AGENCY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of USDA-FARM SERVICE AGENCY in CALLE SANTA TERESA JOURNET #637 EDIF BECHARA OFICINA 2012, MAYAGUEZ, PR 00682 (NAICS 926110). OSHA activity number 340098656.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Usda-Farm Service Agency — free Get an email when a new federal OSHA severe-injury report for Usda-Farm Service Agency is published. One employer, no account, unsubscribe in one click.
Site address
CALLE SANTA TERESA JOURNET #637 EDIF BECHARA OFICINA 2012
City
MAYAGUEZ
State
PR
ZIP
00682
Mailing
CALLE SANTA TERESA JOURNET #637 EDIF BECHARA OFICINA 2012, MAYAGUEZ, PR 00682
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
926110
Employees
5
Ownership type
D

5 citations on file for this inspection.

1910.37 A04

Serious Gravity 1 1 instance 5 exposed
Issued
Dec 18, 2014
Abate by
Jan 15, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(4): Safeguard(s) designed to protect employees during an emergency (e.g., sprinkler systems, alarm systems, fire doors, exit lighting), were not in proper working order at all times:   a) On or about 11/20/14, at #637 Santa Teresa Journet, Suite 2021, Edif. Bechara, Mayaguez, PR, in the break room area, the emergency exit light fixture was not in working conditions.   b) On or about 11/20/14, at #637 Santa Teresa Journet, Suite 2021, Edif. Bechara, Mayaguez, PR, in the storage room area, the emergency exit light fixture was not in working conditions.    PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.304 B03 I

Serious Gravity 1 1 instance 3 exposed
Issued
Dec 18, 2014
Abate by
Jan 15, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops shall have ground-fault circuit-interrupter protection for personnel:  On or about 11/20/14, at #637 Santa Teresa Journet, Suite 2021, Edif. Bechara, Mayaguez PR, in the male bathroom area, electrical receptacles were not equipped with ground-fault circuit-interrupter protection.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 1 instance 5 exposed
Issued
Dec 18, 2014
Abate by
Jan 15, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:  On or about 11/20/14, at #637 Santa Teresa Journet, Suite 2021, Edif. Bechara, Mayaguez PR, in the Program Technician work area, an electrical outlet box was not covered.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.157 C01

Other-than-serious 1 instance 5 exposed
Issued
Dec 18, 2014
Abate by
Jan 15, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury:  On or about 11/20/14, at #637 Santa Teresa Journet, Suite 2021, Edif. Bechara, Mayaguez, PR, in the copy machine area, a portable fire extinguisher was not mounted.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (O) $0

1910.157 E03

Other-than-serious 1 instance 5 exposed
Issued
Dec 18, 2014
Abate by
Jan 15, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  On or about 11/20/14, at #637 Santa Teresa Journet, Suite 2021, Edif. Bechara, Mayaguez PR, throughout the facility, the portable fire extinguishers were not maintained annually.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.