OSHA Inspection: SUBURBAN PROPANE

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SUBURBAN PROPANE in 5620 JACKSBORO HWY, FORT WORTH, TX 76114 (NAICS 454310). OSHA activity number 340102813.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Suburban Propane for free Get an email when a new federal OSHA severe-injury report for Suburban Propane is published. One employer, no account, unsubscribe in one click.
Establishment
SUBURBAN PROPANE
Site address
5620 JACKSBORO HWY
City
FORT WORTH
State
TX
ZIP
76114
Mailing
5620 JACKSBORO HWY, FORT WORTH, TX 76114
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
454310
Employees
9
Ownership type
Private (A)

15 citations on file for this inspection.

5(a)(1)

Deleted Serious Gravity 5 1 instance 12 exposed
Issued
May 19, 2015
Abate by
Jul 9, 2015
Penalty
Initial $5,000 · Current $0 Reduced
OSH ACT of 1970 Section (5)(a)(1): The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that employees were exposed to fire and explosion hazards as a result of the release of propane gas.  On or about November 25, 2014 and at times prior thereto, the employer did not ensure that hoses and piping subject to pressure, temperature, and/or physical harm were not damaged or leaking propane gas into the air at the facility.
Recent events (3)
  • · F (S) $0
  • · C (S) $5000
  • · Z (S) $5000

1910.22 A01

Serious Gravity 5 2 instances 6 exposed
Issued
May 19, 2015
Abate by
Jun 5, 2015
Penalty
Initial $4,000 · Current $7,000
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition.    On or about November 25, 2014 and at times prior thereto, employees were not provided with a clean and orderly work environment exposing employees to trip and fall hazards such as:          a)  In the administration building, empty boxes, file boxes, and electrical cords.        b)  In the maintenance shop, tools and containers.
Recent events (3)
  • · F (S) $7000
  • · C (S) $4000
  • · Z (S) $4000

1910.110 B05 II

Deleted Serious Gravity 5 1 instance 12 exposed
Issued
May 19, 2015
Abate by
Jun 5, 2015
Penalty
Initial $5,000 · Current $0 Reduced
29 CFR 1910.110(b)(5)(ii): Markings specified shall be on a metal nameplate attached to the container and located in such a manner as to remain visible after the container is installed.  On or about November 25, 2014 and at times prior thereto, the storage tank labels were not visible on liquid petroleum vessels such as but not limited to, tank 1 (18,000 gallons) and tank 2 (30,000 gallons) exposing employees to chemical, fire, and explosion hazards.
Recent events (3)
  • · F (S) $0
  • · C (S) $5000
  • · Z (S) $5000

1910.110 B06 VI

Other-than-serious 1 instance 12 exposed
Issued
May 19, 2015
Abate by
Jun 5, 2015
Penalty
Initial $3,000 · Current $4,000
29 CFR 1910.110(b)(6)(vi): Readily ignitable material such as weeds and long dry grass shall be removed within 10 feet of any container.    On or about November 25, 2014 and at times prior thereto, the weeds around liquefied petroleum vessels of the ASME listed tanks such as, but not limited to tank 1 (18,000 gallon), tank 2 (30,000 gallon), and the residential tanks stored out in the yard were not cut and removed.  The tank's propane level ranged from 5 to 60 percent exposing employees to fire and explosion hazards.
Recent events (3)
  • · F (O) $4000
  • · C (S) $3000
  • · Z (S) $3000

1910.110 D10

Serious Gravity 5 1 instance 12 exposed
Issued
May 19, 2015
Abate by
Jun 5, 2015
Penalty
Initial $5,000 · Current $7,000
29 CFR 1910.110(d)(10): Precautions were not taken to prevent damage to LP gas system(s) from vehicular traffic:    On or about November 25, 2014 and at times prior thereto, the ASME listed liquid petroleum storage tank 1 (18,000 gallon) and tank 2 (30,000 gallon) were not protected from vehicular traffic exposing employees to fire and explosion hazards.
Recent events (3)
  • · F (S) $7000
  • · C (S) $5000
  • · Z (S) $5000

1910.303 B02

Deleted Serious Gravity 1 2 instances 12 exposed
Issued
May 19, 2015
Abate by
Jul 9, 2015
Penalty
Initial $3,000 · Current $0 Reduced
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  Main Administration Room, on or about November 25, 2014 and at times prior thereto, the employer did not ensure that multiple relocatable power taps were used as the manufacturer required exposing employees to electrical shock hazards.
Recent events (3)
  • · F (S) $0
  • · C (S) $3000
  • · Z (S) $3000

1910.303 G01 II

Deleted Serious Gravity 5 2 instances 12 exposed
Issued
May 19, 2015
Abate by
Jun 5, 2015
Penalty
Initial $4,000 · Current $0 Reduced
29 CFR 1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  On or about November 25, 2014 and at times prior thereto, sufficient access and working space was not maintained around electrical power exposing employees to electrical shock hazard.       a)  Administration file room, file cabinets and boxes of files blocked access to the electrical panel that provided all electrical power in the administration building, including lights, heaters, and outlets.       b)  Maintenance shop, the welding machine, industrial fan, and boxes blocked access to the electrical panel that provided all the electrical in the shop.
Recent events (3)
  • · F (S) $0
  • · C (S) $4000
  • · Z (S) $4000

1910.304 B04 II B

Serious Gravity 5 1 instance 12 exposed
Issued
May 19, 2015
Abate by
Jun 5, 2015
Penalty
Initial $5,000 · Current $7,000
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord and plug connected load in excess of the maximum specified in Table S-4;     Main Administration room, on or about November 25, 2014 and at times prior thereto, an electrical receptacle was overloaded with total cord and plug connected loads in excess of Table S-4 exposing employees to electrical shock and fire hazards.
Recent events (3)
  • · F (S) $7000
  • · C (S) $5000
  • · Z (S) $5000

1910.304 G05

Other-than-serious 1 instance 12 exposed
Issued
May 19, 2015
Abate by
Jul 9, 2015
Penalty
Initial $3,000 · Current $2,000 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:    Main Administration building, on or about November 25, 2014 and at times prior thereto, employees were exposed to electrical shock hazards while using office equipment that was plugged into electrical receptacles that were not grounded.
Recent events (3)
  • · F (O) $2000
  • · C (S) $3000
  • · Z (S) $3000

1910.305 B02 I

Other-than-serious 2 instances 12 exposed
Issued
May 19, 2015
Abate by
Jun 5, 2015
Penalty
Initial $5,000 · Current $7,000
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose.    On or about November 25, 2014 and at times prior thereto, electrical boxes were not covered to protect employees from accidental contact of the live electrical wires and parts, exposing employees to electrical shock and fire hazards:           a)  In the administration office, an outlet box hanging from the ceiling had energized electrical wiring exposed.         b)  In the maintenance shop, an junction box located on the west wall above the work bench had live electrical wiring exposed.
Recent events (3)
  • · F (O) $7000
  • · C (S) $5000
  • · Z (S) $5000

1910.305 G01 IV A

Serious Gravity 10 3 instances 5 exposed
Issued
May 19, 2015
Abate by
Jun 17, 2015
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    Main Administration room, on or about November 25, 2014 and at times prior thereto, employees were exposed to electrical shock hazards while operating office equipment such as, but not limited to computers which were plugged into temporary electrical wiring:    Management had rerouted some of the electrical equipment from the main administration area to a neighboring office by using an electrical cord attached to a surge protector and running it though the AC vent to the office next door.
Recent events (3)
  • · F (S) $7000
  • · C (S) $7000
  • · Z (S) $7000

1910.305 G01 IV A

Serious Gravity 10 3 instances 5 exposed
Issued
May 19, 2015
Abate by
Jun 17, 2015
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    Main Administration room, on or about November 25, 2014 and at times prior thereto, employees were exposed to electrical shock hazards while operating office equipment such as, but not limited to computers which were plugged into temporary electrical wiring:    At least 5 re-locatable power taps were being used with one electrical wall 120V receptacle provide power t at least 10 electrical devices such as, but not limited to, computers, office phone, cell phones charges, heaters, fax machine and printers.
Recent events (3)
  • · F (S) $7000
  • · C (S) $7000
  • · Z (S) $7000

1910.305 G01 IV A

Serious Gravity 10 3 instances 5 exposed
Issued
May 19, 2015
Abate by
Jun 17, 2015
Penalty
Initial $7,000 · Current $7,000
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    Main Administration room, on or about November 25, 2014 and at times prior thereto, employees were exposed to electrical shock hazards while operating office equipment such as, but not limited to computers which were plugged into temporary electrical wiring:    Several extension cords ran along a wall and up a set of steps to supply power to the neighboring offices, computer, phone, heater and calculator.
Recent events (3)
  • · F (S) $7000
  • · C (S) $7000
  • · Z (S) $7000

1910.37 B02

Other-than-serious 3 instances 12 exposed
Issued
May 19, 2015
Abate by
Jun 5, 2015
Penalty
Initial $1,000 · Current $2,000
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":    On or about November 25, 2014 and at times prior thereto, the emergency exit route was not clearly marked and visible in an approximately 1300 square foot building exposing employees to fire hazards.
Recent events (3)
  • · F (O) $2000
  • · C (O) $1000
  • · Z (O) $1000

1910.141 A05

Deleted Other-than-serious 1 instance 3 exposed
Issued
May 19, 2015
Abate by
Jun 17, 2015
Penalty
Initial $1,000 · Current $0 Reduced
29 CFR 1910.141(a)(5): A continuing and effective extermination program was not instituted where rodents, insects, or other vermin were detected:  On or about November 25, 2014 and at times prior thereto, the employer did not ensure that the workplace was kept free of rodents and vermin exposing employees to potentially infectious respiratory, dermal, and irritation hazards.
Recent events (3)
  • · F (O) $0
  • · C (O) $1000
  • · Z (O) $1000