SAN DIEGO, CA —
OSHA Inspection: NAVY EXCHANGE NORTH ISLAND
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NAVY EXCHANGE NORTH ISLAND in NAS NORTH ISLAND BLDG 2017, SAN DIEGO, CA 92135 (NAICS 452111). OSHA activity number 340114776.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NAVY EXCHANGE NORTH ISLAND
- Site address
- NAS NORTH ISLAND BLDG 2017
- City
- SAN DIEGO
- State
- CA
- ZIP
- 92135
- Mailing
- NAS NORTH ISLAND BLDG 2017, SAN DIEGO, CA 92135
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 452111
- Employees
- 150
- Ownership type
- D
Citations
6 citations on file for this inspection.
1910.36 B01
- Issued
- Dec 10, 2014
- Abate by
- Jan 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(b)(1): At least two exits routes were not available to permit prompt evacuation of employees during an emergency. Warehouse: The employer had one designated exit route at the loading dock for employees working in the warehouse and customer service, other potential routes for use as emergency exit routes were not marked or designated to create a second continuous and unobstructed path of exit travel for the employees.
Recent events (1)
- — Z (S) $0
1910.36 G02
- Issued
- Dec 10, 2014
- Abate by
- Jan 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. (a) Accounting office: Employee emergency exit access obstructed by the placement of the employees desk and other furniture restricting the emergency exit access to 26 inches. (b) Customer service: Employee emergency exit access obstructed by the placement of a shelving unit in the emergency exit access pathway restricting the access to 24 inches. (c) Warehouse: Employee emergency exit access obstructed in multiple locations throughout the warehouse where management has permitted boxes of merchandise to accumulate in the emergency exit accesses.
Recent events (1)
- — Z (S) $0
1910.37 B02
- Issued
- Dec 10, 2014
- Abate by
- Jan 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit". Charge back room: An exit sign was not posted on the emergency exit door.
Recent events (1)
- — Z (S) $0
1910.157 E03
- Issued
- Dec 10, 2014
- Abate by
- Jan 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check: Warehouse: A fire extinguisher located at the eye wash station was not inspected annually, lacking any record of annual inspection.
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Dec 10, 2014
- Abate by
- Jan 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Service Managers Desk: A power strip was connected in series with another power strip.
Recent events (1)
- — Z (S) $0
1910.303 G01
- Issued
- Dec 10, 2014
- Abate by
- Jan 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: Warehouse: Access to an electrical panel was obstructed by a metal cart and various display items.
Recent events (1)
- — Z (S) $0
More inspections at Navy Exchange North Island
View Navy Exchange North Island's full OSHA safety record →
More inspections in this industry (NAICS 452111)
More inspections in CA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340114776.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.