Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,191,288Inspections Most recent open 2026-07-24 Last loaded 2026-07-29

OSHA Inspection: AIR NATIONAL GUARD

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AIR NATIONAL GUARD in 176TH AMXS, JBER, AK 99506 (NAICS 488190). OSHA activity number 340119411.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch AIR National Guard — free Get an email when a new federal OSHA severe-injury report for AIR National Guard is published. One employer, no account, unsubscribe in one click.
Establishment
AIR NATIONAL GUARD
Site address
176TH AMXS
City
JBER
State
AK
ZIP
99506
Mailing
176TH WING 17441 AIRLIFTER DRIVE, JBER, AK 99506
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488190
Employees
309
Ownership type
D

3 citations on file for this inspection.

1910.212 A05

Serious Gravity 1 2 instances 2 exposed
Issued
Dec 15, 2014
Abate by
Jan 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(5): Fan blade guards, where the periphery of the blades was less than seven feet above the floor or working level, had openings larger than one half inch.   Armament shop; on or about 03 December 2014 and times prior; a ceiling mounted Sterling unit heater, labeled 11-05, The periphery fan blades were not guarded with protective barrier one-half inch or less. The measured distance from the floor to blade was 66 inches. This condition exposed employees to a caught in hazard.
Recent events (1)
  • — Z (S) $0

1910.303 B07 IV

Serious Gravity 1 1 instance 2 exposed
Issued
Dec 15, 2014
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(iv): Electrical equipment had damaged parts that may adversely affect safe operation or mechanical strength of the equipment, such as parts that are broken, bent, cut, or deteriorated by corrosion, chemical action, or overheating.  Hangar 18 East bay; on or about 03 December 2014 and times prior thereto; a 50 foot electrical extension cord had damage to the protective outer jacket. This condition exposed employees to an electrical shock hazard.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV C

Serious Gravity 1 1 instance 2 exposed
Issued
Dec 15, 2014
Abate by
Jan 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(C): Flexible cords and cables were used where run through doorways, windows, or similar openings.   Tool crib; on or about 03 December 2014 and times prior; a 15 foot energized electrical power tap was used as permanent wiring and routed through a wall opening. This condition exposed employees to electrical shock and electrical burn hazard.
Recent events (1)
  • — Z (S) $0

View AIR National Guard's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340119411.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.