OSHA Inspection: AIR NATIONAL GUARD

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of AIR NATIONAL GUARD in 176TH MXS, JBER, AK 99506 (NAICS 488190). OSHA activity number 340119478.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch AIR National Guard — free Get an email when a new federal OSHA severe-injury report for AIR National Guard is published. One employer, no account, unsubscribe in one click.
Establishment
AIR NATIONAL GUARD
Site address
176TH MXS
City
JBER
State
AK
ZIP
99506
Mailing
176TH WING 17441 AIRLIFTER DRIVE, JBER, AK 99506
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
488190
Employees
309
Ownership type
D

4 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 1 1 instance 2 exposed
Issued
Dec 15, 2014
Abate by
Jan 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.  Electrical shop;  on or about 03 December 2014 and times prior; an energized electrical outlet had a knockout missing on the top of the box.  This condition exposed employees to electrical shock and electrical burn hazard.
Recent events (1)
  • — Z (S) $0

1910.334 A02 I

Serious Gravity 1 1 instance 2 exposed
Issued
Dec 15, 2014
Abate by
Jan 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket).  Welding shop; on or about 03 December 2014 and times prior thereto; a Reelcraft spring driven retractable extension cord had damage to the protective outer jacket. This condition exposed employees to an electrical shock hazard.
Recent events (1)
  • — Z (S) $0

1910.184 F05 III

Other-than-serious 1 instance 2 exposed
Issued
Dec 15, 2014
Abate by
Jan 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.184(f)(5)(iii): Wire rope sling(s) that had kinking, crushing, bird caging or other damage resulting in distortion of the wire rope structure were not immediately removed from service.  Engine shop, prop house; on or about 03 December 2014 and times prior; a braided wire rope used for installation and removal of aircraft props was kinked. This condition exposed employees to a struck by hazard.
Recent events (1)
  • — Z (O) $0

1910.303 B02

Other-than-serious 1 instance 2 exposed
Issued
Dec 15, 2014
Abate by
Jan 20, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  Machinist shop room 133B; on or about 03 December 2014 and times prior; locally fabricated junction box was not used as per the manufactures recommendation.  This condition exposed employees to an electrical shock and burn hazard.
Recent events (1)
  • — Z (O) $0

View AIR National Guard's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340119478.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.