Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: HIGHLAND PROJECTS LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of HIGHLAND PROJECTS LLC in 301 ORCHARD LN, BILLINGS, MT 59101 (NAICS 331210). OSHA activity number 340133420.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Highland Projects LLC — free Get an email when a new federal OSHA severe-injury report for Highland Projects LLC is published. One employer, no account, unsubscribe in one click.
Site address
301 ORCHARD LN
City
BILLINGS
State
MT
ZIP
59101
Mailing
301 ORCHARD LN, BILLINGS, MT 59101
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
331210
Employees
55
Ownership type
A

4 citations on file for this inspection.

1910.107 C06

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 12, 2015
Abate by
Apr 7, 2015
Penalty
Initial $3,500 · Current $2,450 Reduced
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations:  (a) Quonset: On or about December 10, 2014 and at times prior, employees were exposed to fire and explosion hazards when non explosion proof flexible extension cords were used in the spray area to energize electrical equipment.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $3500

1910.307 C02 I

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 12, 2015
Abate by
Apr 7, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present:  (a) Quonset: On or about December 10, 2014 and at times prior, employees were exposed to fire and explosion hazards when non explosion proof flexible extension cords were used in the spray area.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.107 E02

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 12, 2015
Abate by
Apr 7, 2015
Penalty
Initial $3,500 · Current $2,450 Reduced
29 CFR 1910.107(e)(2): The quantity of flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) kept in the vicinity of spraying operations shall be the minimum required for operations and should ordinarily not exceed a supply for 1 day or one shift:  (a) Quonset: On or about December 10, 2014 and at times prior, employees were exposed to fire and explosion hazards to include but not limited to, Toluene/SW (flash point 40 deg Fahrenheit), KEM 4000 High Solids Acrylic Alkyd Enamel (Black- flash point 95 deg Fahrenheit), and KEM 4000 High Solids Acrylic Alkyd Enamel (Ultra Deep Base- flash Point 95 deg Fahrenheit), when approximately 500 gallons of flammable liquids were stored in the spray area.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $3500

1910.107 I06

Serious Gravity 5 1 instance 2 exposed
Issued
Mar 12, 2015
Abate by
Apr 7, 2015
Penalty
Initial $3,500 · Current $2,450 Reduced
29 CFR 1910.107(i)(6): Grounding - general. All electrically conductive objects in the spraying area shall be adequately grounded. This requirement shall apply to paint containers, wash cans, and any other objects or devices in the area. The equipment shall carry a prominent permanently installed warning regarding the necessity for this grounding feature.  (a) Quonset: On or about December 10, 2014 and at times prior, employees were exposed to fire and explosion hazards to include but not limited to, Toluene/SW (flash point 40 deg Fahrenheit), KEM 4000 High Solids Acrylic Alkyd Enamel (Black- flash point 95 deg Fahrenheit), and KEM 4000 High Solids Acrylic Alkyd Enamel (Ultra Deep Base- flash Point 95 deg Fahrenheit), when approximately 500 gallons of flammable liquids were stored in the spray area.
Recent events (2)
  • — I (S) $2450
  • — Z (S) $3500

View Highland Projects LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340133420.