BILLINGS, MT —
OSHA Inspection: HIGHLAND PROJECTS LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of HIGHLAND PROJECTS LLC in 301 ORCHARD LN, BILLINGS, MT 59101 (NAICS 331210). OSHA activity number 340133420.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- HIGHLAND PROJECTS LLC
- Site address
- 301 ORCHARD LN
- City
- BILLINGS
- State
- MT
- ZIP
- 59101
- Mailing
- 301 ORCHARD LN, BILLINGS, MT 59101
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 331210
- Employees
- 55
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.107 C06
- Issued
- Mar 12, 2015
- Abate by
- Apr 7, 2015
- Penalty
- Initial $3,500 · Current $2,450 Reduced
General-duty citation text
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations: (a) Quonset: On or about December 10, 2014 and at times prior, employees were exposed to fire and explosion hazards when non explosion proof flexible extension cords were used in the spray area to energize electrical equipment.
Recent events (2)
- — I (S) $2450
- — Z (S) $3500
1910.307 C02 I
- Issued
- Mar 12, 2015
- Abate by
- Apr 7, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present: (a) Quonset: On or about December 10, 2014 and at times prior, employees were exposed to fire and explosion hazards when non explosion proof flexible extension cords were used in the spray area.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.107 E02
- Issued
- Mar 12, 2015
- Abate by
- Apr 7, 2015
- Penalty
- Initial $3,500 · Current $2,450 Reduced
General-duty citation text
29 CFR 1910.107(e)(2): The quantity of flammable liquids or liquids with a flashpoint greater than 199.4 °F (93 °C) kept in the vicinity of spraying operations shall be the minimum required for operations and should ordinarily not exceed a supply for 1 day or one shift: (a) Quonset: On or about December 10, 2014 and at times prior, employees were exposed to fire and explosion hazards to include but not limited to, Toluene/SW (flash point 40 deg Fahrenheit), KEM 4000 High Solids Acrylic Alkyd Enamel (Black- flash point 95 deg Fahrenheit), and KEM 4000 High Solids Acrylic Alkyd Enamel (Ultra Deep Base- flash Point 95 deg Fahrenheit), when approximately 500 gallons of flammable liquids were stored in the spray area.
Recent events (2)
- — I (S) $2450
- — Z (S) $3500
1910.107 I06
- Issued
- Mar 12, 2015
- Abate by
- Apr 7, 2015
- Penalty
- Initial $3,500 · Current $2,450 Reduced
General-duty citation text
29 CFR 1910.107(i)(6): Grounding - general. All electrically conductive objects in the spraying area shall be adequately grounded. This requirement shall apply to paint containers, wash cans, and any other objects or devices in the area. The equipment shall carry a prominent permanently installed warning regarding the necessity for this grounding feature. (a) Quonset: On or about December 10, 2014 and at times prior, employees were exposed to fire and explosion hazards to include but not limited to, Toluene/SW (flash point 40 deg Fahrenheit), KEM 4000 High Solids Acrylic Alkyd Enamel (Black- flash point 95 deg Fahrenheit), and KEM 4000 High Solids Acrylic Alkyd Enamel (Ultra Deep Base- flash Point 95 deg Fahrenheit), when approximately 500 gallons of flammable liquids were stored in the spray area.
Recent events (2)
- — I (S) $2450
- — Z (S) $3500
More inspections at Highland Projects LLC
View Highland Projects LLC's full OSHA safety record →
More inspections in this industry (NAICS 331210)
More inspections in MT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340133420.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.