MORRIS, IL —
OSHA Inspection: ALESSANDRINI INC.
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of ALESSANDRINI INC. in 721 W. BEDFORD RD., MORRIS, IL 60450 (NAICS 444110). OSHA activity number 340159714.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ALESSANDRINI INC.
- Site address
- 721 W. BEDFORD RD.
- City
- MORRIS
- State
- IL
- ZIP
- 60450
- Mailing
- 721 W. BEDFORD RD., MORRIS, IL 60450
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 444110
- Employees
- 7
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.36 G02
- Issued
- Feb 20, 2015
- Abate by
- Mar 12, 2015
- Penalty
- Initial $1,200 · Current $720 Reduced
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. Employees were exposed to burn hazards in the following area and the employer did not ensure that all exit accesses were at least 28" wide at all points. The back room exit located in the center of the building was blocked by a refrigerator and a series of stacked plastic boxes, creating a pathway approximately 13" wide. Abatement certification is required of this item in accordance with the requirements of 1903.19(c).
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1910.303 G01
- Issued
- Feb 20, 2015
- Abate by
- Mar 27, 2015
- Penalty
- Initial $2,400 · Current $1,440 Reduced
General-duty citation text
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: The employer did not provide sufficient access and working space about electrical equipment in the following areas: a) Employees were exposed to electrical shock and burn injuries from insufficient access to electrical panels located on the back wall of the back room which were blocked by a wooden storage bench and lawn and garden equipment. b) Employees were exposed to electrical shock and caught in/between injuries from insufficient access to a power disconnect that supplies power to the hydraulic lift used to load and unload trucks. The disconnect was blocked by a rolling cart full of various materials. Abatement certification is required for this item in accordance with the requirements of 1903.19(c).
Recent events (2)
- — I (S) $1440
- — Z (S) $2400
1910.304 F01 VIII
- Issued
- Feb 20, 2015
- Abate by
- Mar 27, 2015
- Penalty
- Initial $1,200 · Current $720 Reduced
General-duty citation text
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." The employer did not ensure that employees using circuit breakers used as switches in 120-volt and 277-volt fluorescent lighting circuits were marked and listed "SWD." Employees are exposed to fire hazards from switches that are not designed for regular on/off switching. Abatement certification is required for this item in accordance with the requirements of 1903.19(c).
Recent events (2)
- — I (S) $720
- — Z (S) $1200
1910.1200 E01
- Issued
- Feb 20, 2015
- Abate by
- Mar 27, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.1200(e)(1): The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program which describes how the criteria specified in 29 CFR 1910.1200(f), (g), and (h) will be met: The employer did not develop, implement, and/or maintain at the workplace a written hazard communication program. Employees were exposed to incidental contact with oils and cleaning materials sold at the store, and employees trained on the installation of natural gas powered equipment were not trained on hazard communciation. A written hazard communication program and safety data sheets were not maintained. Abatement certification is required of this item in accordance with the requirements of 29 CFR 1903.19(c).
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Alessandrini INC.
View Alessandrini INC.'s full OSHA safety record →
More inspections in this industry (NAICS 444110)
More inspections in IL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340159714.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.