Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GOLD BEACH HOTEL SAIPAN

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of GOLD BEACH HOTEL SAIPAN in PUPULU DRIVE, SAIPAN, MP 96950 (NAICS 721110). OSHA activity number 340163450.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Gold Beach Hotel Saipan — free Get an email when a new federal OSHA severe-injury report for Gold Beach Hotel Saipan is published. One employer, no account, unsubscribe in one click.
Site address
PUPULU DRIVE
City
SAIPAN
State
MP
ZIP
96950
Mailing
P.O. BOX 502232, SAIPAN, MP 96950
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721110
Employees
17
Ownership type
A

6 citations on file for this inspection.

1910.106 E02 II B 1

Serious Gravity 1 10 instances 4 exposed
Issued
Apr 21, 2015
Abate by
May 1, 2015
Penalty
Initial $1,200 · Current $900 Reduced
29 CFR 1910.106(e)(2)(ii)(b)(1): The quantity of liquid that may be located outside of an inside storage room or storage cabinet in a building or in any one fire area of a building exceeded 25 gallons of Category 1 flammable liquids in containers      a) On January 26, 2015, inside the Maintenance Shop, over 40 gallons of gasoline were stored outside of a storage cabinet, exposing employees to a fire hazard.
Recent events (2)
  • — I (S) $900
  • — Z (S) $1200

1910.303 C03 I

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 21, 2015
Abate by
May 1, 2015
Penalty
Initial $1,600 · Current $900 Reduced
29 CFR 1910.303(c)(3)(i): Conductors were not spliced or joined with splicing devices identified for the use or by brazing, welding, or soldering with a fusible metal or alloy.   Soldered splices were not spliced or joined mechanically and electrically secured first without solder and then soldered.  All splices and joints and the free ends of conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose:      a) On January 26, 2015, inside the maintenance storage warehouse, electrical connections overhead lighting fixtures was made outside of a protected connection box without, exposing employees to electrical and fire hazards.      b) On January 26, 2015, inside the maintenance shop, the connection of the boiler timer control was made outside of a protected connection box, exposing employees to electrical and fire hazards.
Recent events (2)
  • — I (S) $900
  • — Z (S) $1600

1910.305 B02 I

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 21, 2015
Abate by
May 1, 2015
Penalty
Initial $1,600 · Current $900 Reduced
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:        a) On January 24, 2015, in the maintenance shop, a junction box powering the overhead lights did not have a cover.
Recent events (2)
  • — I (S) $900
  • — Z (S) $1600

1910.305 G01 IV A

Serious Gravity 5 2 instances 4 exposed
Issued
Apr 21, 2015
Abate by
Apr 29, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:   a) On January 24, 2015, in the maintenance shop, the employer was using flexible cords hard wired into an electrical box to power overhead light fixtures and electrical control systems a water heater.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1904.32 A02

Other-than-serious 1 instance 17 exposed
Issued
Apr 21, 2015
Abate by
May 1, 2015
Penalty
Initial $400 · Current $0 Reduced
29 CFR 1904.32(a)(2): The Summary of Work-Related Injuries and Illnesses (OSHA Form 300A or equivalent) was not created, certified, or posted:      a) On April 20, 2015, the employer did not create, certify, or post the Summary of Work-Related Injuries and Illnesses.
Recent events (2)
  • — I (O) $0
  • — Z (O) $400

1910.37 B02

Other-than-serious 1 instance 17 exposed
Issued
Apr 21, 2015
Abate by
May 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":   a) On January 26, 2015, in the maintenance shop, the emergency exit door was not labeled as an Exit.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Gold Beach Hotel Saipan's full OSHA safety record →