Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: COCA COLA REFRESHMENTS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of COCA COLA REFRESHMENTS in 1001 W. JACKSON ST, EL CAMPO, TX 77437 (NAICS 424490). OSHA activity number 340176924.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Coca Cola Refreshments — free Get an email when a new federal OSHA severe-injury report for Coca Cola Refreshments is published. One employer, no account, unsubscribe in one click.
Site address
1001 W. JACKSON ST
City
EL CAMPO
State
TX
ZIP
77437
Mailing
1001 W. JACKSON ST, EL CAMPO, TX 77437
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424490
Employees
78
Ownership type
A

5 citations on file for this inspection.

1910.303 B01 VIII

Other-than-serious 1 instance 45 exposed
Issued
Feb 3, 2015
Abate by
Mar 4, 2015
Penalty
Initial $2,100 · Current $2,100
29 CFR 1910.303(b)(1)(viii): Safety of equipment was not determined  using the following consideration:    At this facility site, in the break room, the outlet next to the sink was not equipped with GFCI protection.  Employees were not protected against electrical contact.
Recent events (2)
  • — I (O) $2100
  • — Z (S) $2100

1910.303 B02

Other-than-serious 1 instance 1 exposed
Issued
Feb 3, 2015
Abate by
Mar 4, 2015
Penalty
Initial $2,100 · Current $2,100
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.    At this establishment, in the mechanic shop, a 4-way metal, electrical outlet/receptacle box, was used to energize various equipment without permanently mounting the 4-way box. The 4-way box was not used as designed to prevent an electrical hazard.
Recent events (2)
  • — I (O) $2100
  • — Z (S) $2100

1910.22 B02

Other-than-serious 78 instances 16 exposed
Issued
Feb 3, 2015
Abate by
Mar 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.22(b)(2): Permanent aisles and passageways shall be appropriately marked.  At this establishment, aisles, and passageways were not properly marked or visible in the warehouse staging area. Employees work in this area at the same time forklift machinery is being used.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.132 D02

Other-than-serious 78 instances 78 exposed
Issued
Feb 3, 2015
Abate by
Mar 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(2): The employer did not verify that the required workplace hazard assessment has been performed through a written certification which included the requirements as outlined in 29 CFR 1910.132(d)(2).  At this establishment, the employer did not verify that a workplace hazard assessment had been performed through a written and signed document that identified the workplace evaluated, the person certifying that the evaluation has been performed, the dates of the hazard assessment, and which identifies the document as a certification of hazard assessment.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G02 III

Other-than-serious 1 instance 1 exposed
Issued
Feb 3, 2015
Abate by
Mar 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.  At  this facility, in the mechanic shop, cords connected to the 4 way/outlet box which was not fitted to prevent proper strain relief to prevent the pull from the joints.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Coca Cola Refreshments's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340176924.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.