Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: HUEN ELECTRIC, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of HUEN ELECTRIC, INC. in 334 COUNTY ROUTE 16, CANTON, NY 13617 (NAICS 238210). OSHA activity number 340205145.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Huen Electric, INC. — free Get an email when a new federal OSHA severe-injury report for Huen Electric, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
HUEN ELECTRIC, INC.
Site address
334 COUNTY ROUTE 16
City
CANTON
State
NY
ZIP
13617
Mailing
6695 OLD COLLAMER ROAD, EAST SYRACUSE, NY 13057
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
30
Ownership type
A

3 citations on file for this inspection.

1926.403 B02

Deleted Serious Gravity 5 1 instance 9 exposed
Issued
Feb 27, 2015
Abate by
Mar 9, 2015
Penalty
Initial $3,500 · Current $0 Reduced
29 CFR 1926.403(b)(2): 29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:  a)  At the jobsite, on or about 1/14/15:  Employees were connecting energized extension cords to aerial lifts (one connection to each of 2 lifts), where those cords were were powered through an office style power strip not designed for construction use, then to a non GFI protected outlet.      Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $3500

1926.404 B01 II

Other-than-serious 1 instance 9 exposed
Issued
Feb 27, 2015
Abate by
Mar 9, 2015
Penalty
Initial $0 · Current $3,500
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupers for personal protection:    a)  At the jobsite, on or about 1/14/15:  Employees were connecting energized extension cords to aerial lifts (one connection each), where those cords were powered through a connection to an office type power strip, that was sequentially connected to an outlet without GFI protection.      Abatement certification must be submitted for this item.
Recent events (2)
  • — I (O) $3500
  • — Z (S) $0

1926.405 A02 II I

Deleted Serious Gravity 5 1 instance 9 exposed
Issued
Feb 27, 2015
Abate by
Mar 9, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(I): Flexible cords and cables used for temporary wiring were not protected from damage:  a)  At the jobsite, on or about 1/14/15:  Employees were connecting energized extension cords to aerial lifts (one connection to each of 2 lifts), where those cords were passed over and through a snow covered walkway (exposed to foot and vehicle traffic), then passed under an overhead doorway that was closed on the cords.  The cords were powered through an office style power strip and to a non GFI protected outlet.      Abatement certification must be submitted for this item.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View Huen Electric, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340205145.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.