BOTHELL, WA —
OSHA Inspection: U.S. DEPARTMENT OF HOMELAND SECURITY FEMA REGION 10 BOTHELL
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of U.S. DEPARTMENT OF HOMELAND SECURITY FEMA REGION 10 BOTHELL in 130 228TH STREET SW, BOTHELL, WA 98021 (NAICS 922190). OSHA activity number 340212554.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Site address
- 130 228TH STREET SW
- City
- BOTHELL
- State
- WA
- ZIP
- 98021
- Mailing
- 130 228TH STREET SW, BOTHELL, WA 98021
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 922190
- Employees
- 70
- Ownership type
- D
Citations
4 citations on file for this inspection.
1910.159 C10
- Issued
- Feb 3, 2015
- Abate by
- Mar 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and material below was not maintained: a) Office Suite, where the minimum vertical clearance was not maintained: 1. Server Room, where HP Printer boxes were stored beneath an automatic sprinkler reducing the vertical clearance to 5 1/4 inches. 2. Accountable Property Room, where boxes were stored beneath an automatic sprinkler reducing the vertical clearance to 9 inches. The U.S. Department of Homeland Security FEMA was previously cited for a violation of this standard which was contained in OSHA inspection no. 314898826, citation no. 1, item no. 4, issued on March 29, 2011 with respect to a workplace at Bothell, WA.
Recent events (1)
- — Z (R) $0
1910.303 B02
- Issued
- Feb 3, 2015
- Abate by
- Mar 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling: a) Facility, where equipment not used as listed or labeled included: 1. Room 219, where a relocatable power tap was used to supply power to appliances including the Toastmaster toaster oven, the Mr. Coffee Commercial Brewer, and the Whirlpool refrigerator. 2. Public Assistance Office, where a relocatable power tap was used to supply power to appliances including the Fahrenheat floor heater. 3. Room 224, where a relocatable power tap was used to supply power to appliances including the Keurig coffee maker. 4. ORA Office, where two relocatable power taps were daisy chained and used to supply power to computer equipment. 5. Room 120, where a relocatable power tap was used to supply power to appliances including the Cool Breeze fan. (Item Corrected) 6. Room 116-A, where a relocatable power tap was used to supply power to appliances including the floor heater. (Item Corrected) 7. IMAT Break Area, where a relocatable power tap was daisy chained with a blue extension cord and used to supply power appliances including the Cuisinart coffee maker. (Item Corrected) 8. Storage Bay A, where a relocatable power tap was daisy chained with a black extension cord and used to supply power to the Nautilus treadmill, the Pro-Tech treadmill, and the Nordic Track treadmill. (Item Corrected) The U.S. Department of Homeland Security FEMA was previously cited for a violation of this standard which was contained in OSHA inspection no. 314898826, citation no. 1, item no. 1, issued on March 29, 2011 with respect to a workplace at Bothell, WA.
Recent events (1)
- — Z (R) $0
1910.303 G01 II
- Issued
- Feb 3, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage: a) Response Division Bay, where items including stacked chairs, a mop bucket, a container of Ice Melt, and brooms were stored in front of the electrical panel. The U.S. Department of Homeland Security FEMA was previously cited for a violation of this standard which was contained in OSHA inspection no. 314898826, citation no. 1, item no. 5, issued on March 29, 2011 with respect to a workplace at Bothell, WA.
Recent events (1)
- — Z (R) $0
1910.303 G02 I D
- Issued
- Feb 3, 2015
- Abate by
- Mar 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(2)(i)(D): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by elevation of 2.44 m (8.0 ft) or more above the floor or other working surface: a) Back Hallway, where five florescent light fixtures located approximately 7 feet 9 inches above floor level were not equipped with guards.
Recent events (1)
- — Z (O) $0
More inspections at U.S. Department of Homeland Security Fema Region 10 Bothell
View U.S. Department of Homeland Security Fema Region 10 Bothell's full OSHA safety record →
More inspections in this industry (NAICS 922190)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340212554.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.