Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ROLANDO RODRIGUEZ

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of ROLANDO RODRIGUEZ in 4233 CAVEAT CT, FAIRBURN, GA 30213 (NAICS 238210). OSHA activity number 340232743.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Rolando Rodriguez — free Get an email when a new federal OSHA severe-injury report for Rolando Rodriguez is published. One employer, no account, unsubscribe in one click.
Establishment
ROLANDO RODRIGUEZ
Site address
4233 CAVEAT CT
City
FAIRBURN
State
GA
ZIP
30213
Mailing
953 DOESKIN DR. NW, CONYERS, GA 30012
Inspection type
Unprogrammed Other (I)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
3
Ownership type
A

4 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 2 instances 4 exposed
Issued
Apr 7, 2015
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:    a) 4233 Caveat Ct. Fairburn, GA: Employees were exposed to electrical shock hazards, in that; the employer was using a junction box to supply power to hand held tools. The box was not listing, labeled or certified for application in which it was being used.    b) 4233 Caveat Ct. Fairburn, GA: Employees were exposed to electrical shock hazards, in that; a flexible extension cord used to power a saw and other tools,  had been spliced to a non-metallic sheath cable.  The non-metallic sheath cable was not listing, labeled or certified for application in which it was being used.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

1926.404 F06

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 7, 2015
Penalty
Initial $2,000 · Current $1,200 Reduced
29 CFR 1926.404(f)(6): The path to ground from circuits, equipment, or enclosures was not permanent and continuous:    a) 4233 Caveat Ct. Fairburn, GA: Employees were exposed to electrical shock hazards, in that; a flexible extension cord used to power a saw and other tools,  had been spliced to a non-metallic sheath cable.  The grounding conductor was not connected.
Recent events (2)
  • — I (S) $1200
  • — Z (S) $2000

1926.405 G02 III

Serious Gravity 5 1 instance 4 exposed
Issued
Apr 7, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.405(g)(2)(iii): Flexible cords were not used in continuous lengths without splice or tap:  a) 4233 Caveat Ct. Fairburn, GA: Employees were exposed to electrical shock hazards, in that; a flexible extension cord used to power a saw and other tools,  had been spliced to a non-metallic sheath cable.  The splice was secured via wire nuts, which would not retain the cord's insulation, and outer sheath properties.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.403 I02 I

Serious Gravity 10 1 instance 4 exposed
Issued
Apr 7, 2015
Penalty
Initial $2,800 · Current $1,600 Reduced
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph.    a) 4233 Caveat Ct. Fairburn, GA: Employees were exposed to electrical shock hazards, in that; that the dead front cover was removed from the service feeder box, exposing energized 220 volt conductors.
Recent events (2)
  • — I (S) $1600
  • — Z (S) $2800

View Rolando Rodriguez's full OSHA safety record →