Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DEPARTMENT OF VETERANS AFFAIRS

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPARTMENT OF VETERANS AFFAIRS in 1030 JEFFERSON AVE, MEMPHIS, TN 38104 (NAICS 622110). OSHA activity number 340383488.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Department of Veterans Affairs — free Get an email when a new federal OSHA severe-injury report for Department of Veterans Affairs is published. One employer, no account, unsubscribe in one click.
Site address
1030 JEFFERSON AVE
City
MEMPHIS
State
TN
ZIP
38104
Mailing
1030 JEFFERSON AVE, MEMPHIS, TN 38104
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
622110
Employees
2200
Ownership type
D

8 citations on file for this inspection.

1910.253 B04 I

Serious Gravity 5 3 instances 10 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(i): Oxygen cylinders were stored near highly combustible material, especially oil and grease; or near reserve stocks of carbide and acetylene or other fuel-gas cylinders, or near other substance likely to cause or accelerate fire;   a) Prosthetics - On or about 2/10/15 employees were exposed to explosion hazards when oxygen and acetylene cylinders were stored together.  b) AC Shop - On or about or 2/11/15 employees were exposed to explosion hazards when oxygen and acetylene cylinders were stored together.   In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (1)
  • — Z (S) $0

1910.304 B02

Repeat Gravity 1 1 instance 2 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(2): Outlet devices had an ampere rating less than the load being served:   (a)  Carpentry Shop - On or about 2/10/15, employees were exposed to electrical hazards when a power strip was being used to provide power to equipment that exceeded the ampere rating.  The Department of Veteran affairs was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.304(b)(2), which was contained in OSHA inspection number 966924, Notice number 1, Item number 2 and was affirmed as a final order on 9/15/14 with respect to a workplace located at 1500 Weiss Street, Saginaw, MI 48602.  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (1)
  • — Z (R) $0

1910.304 G05

Repeat Gravity 1 2 instances 2 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  a) Core Lab - On or about 2/11/15, employees were exposed to electrical hazards when the ground prong on the fan was missing.  b) Canteen - On or about 2/11/15, employees were exposed to electrical hazards when the ground prong on the vacuum was missing.  The Department of Veteran affairs was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.304(g)(5), which was contained in OSHA inspection number 912088, Notice number 1, Item number 2 and was affirmed as a final order on 12/12/13 with respect to a workplace located at 913 NW Garden Valley Blvd, Roseburg, OR 97470.  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (1)
  • — Z (R) $0

1910.147 C06 II

Other-than-serious 15 instances 15 exposed
Issued
Aug 10, 2015
Abate by
Sep 25, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(ii): The employer did not certify that periodic inspections of the energy control procedures had been performed:  (a) 1030 Jefferson Ave, Memphis, TN - On or about 2/10/15, the employer did not ensure that periodic inspections had been performed on the lock out/ tag out procedures.   In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (1)
  • — Z (O) $0

1910.212 B

Other-than-serious 10 instances 15 exposed
Issued
Aug 10, 2015
Abate by
Sep 11, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.212(b): Machine(s) designed for fixed location(s) were not securely anchored to prevent walking or moving:  a) E1-10 Machine Shop - On or about 2/10/15, various pieces of equipment, including but not limited to, a drill press, cutter and brake press  was not anchored to the floor to prevent movement.  b) E17-10 Electrical Shop - On or about 2/10/15, various pieces of equipment, including but not limited to, drill presses were not anchored to the floor to prevent movement.  c) E7-10 Carpentry Shop - On or about 2/10/15,  various pieces of equipment, including but not limited to, a band saw  and boring machine was not anchored to the floor to prevent movement.  d) Prosthetics - On or about 2/10/15,  various pieces of equipment, including but not limited to, drill presses were not anchored to the floor to prevent movement  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (1)
  • — Z (O) $0

1910.253 B02 IV

Other-than-serious 4 instances 5 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(2)(iv): Valve protection caps, where cylinders were designed to accept caps, were not always in place, hand-tight, except when cylinders were in use or connected for use:  (a) AC Shop - On or about 2/11/15, valve caps were not in place when cylinders were in storage.  b) Pipe Shop - On or about 2/10/15, valve caps were not in place when cylinders were in storage.  c) Prosthetics -- On or about 2/10/15, valve caps were not in place when cylinders were in storage.  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (1)
  • — Z (O) $0

1910.303 B02

Other-than-serious 1 instance 2 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) Carpentry Shop - On or about 2/10/15, employees were exposed to electrical hazards when relocatable power taps were daisy chained. in violation of the UL Listing/Labeling.  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (1)
  • — Z (O) $0

1910.305 G02 III

Other-than-serious 1 instance 2 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  (a) E1-10 Machine Shop - On or about 2/10/15, employees were exposed to electrical hazards when strain relief was not provided on the welding machine.  In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).
Recent events (1)
  • — Z (O) $0

View Department of Veterans Affairs's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340383488.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.