On , OSHA opened a complaint safety inspection of A TO Z TIRE & BATTERY, INC. in 901 W. 4TH AVENUE, AMARILLO, TX 79109 (NAICS 326212). OSHA activity number 340411784.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch A to Z Tire & Battery, INC. — free Get an email when a new federal OSHA severe-injury report for A to Z Tire & Battery, INC. is published. One employer, no account, unsubscribe in one click.
Site address
901 W. 4TH AVENUE
City
AMARILLO
State
TX
ZIP
79109
Mailing
812 W 4TH AVENUE AMARILLO, AMARILLO, TX 79101
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326212
Employees
8
Ownership type
A

8 citations on file for this inspection.

1910.178 L01

Serious Gravity 5 1 instance 8 exposed
Issued
Jun 4, 2015
Abate by
Jul 17, 2015
Penalty
Initial $4,000 · Current $2,400 Reduced
29 CFR 1910.178(l)(1):  Employer did not ensure that each powered industrial truck operator was competent to operate a powered industrial truck safely, and demonstrated by the successful completion of the training and evaluation specified in this paragraph (l):    On or about February 18, 2015, the employer did not ensure that each employee was trained in the safe operations of powered industrial trucks prior to operation.  Employees were exposed to struck-by hazards.
Recent events (2)
  • — I (S) $2400
  • — Z (S) $4000

1910.179 G01 V

Serious Gravity 5 1 instance 8 exposed
Issued
Jun 4, 2015
Abate by
Jul 17, 2015
Penalty
Initial $4,000 · Current $2,400 Reduced
29 CFR 1910.179(g)(1)(v):   Pendant control box(es) were not clearly marked for identification of function(s):    On February 18, 2015, employees were exposed to struck-by hazards in that the employer did not ensure the pendant control box to hoist by the Matteuzzi RAS-401 was not labeled with identification of function(s) and was missing a button.
Recent events (2)
  • — I (S) $2400
  • — Z (S) $4000

1910.303 B07 I

Other-than-serious 1 instance 8 exposed
Issued
Jun 4, 2015
Abate by
Jul 17, 2015
Penalty
Initial $3,000 · Current $1,800 Reduced
29 CFR 1910.303(b)(7)(i):  Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:    On or about February 18, 2015, in the production retread shop employees were exposed to electrical shock hazards when a breaker box was missing a knockout.
Recent events (2)
  • — I (O) $1800
  • — Z (S) $3000

1910.303 G01

Other-than-serious Gravity 1 1 instance 8 exposed
Issued
Jun 4, 2015
Abate by
Jul 17, 2015
Penalty
Initial $3,000 · Current $1,800 Reduced
29 CFR 1910.303(g)(1):  The employer did not ensure that sufficient access and working space was provided and maintained about all electric equipment to permit ready and safe operation and maintenance of such equipment:    On or about February 18, 2015, the employee were exposed to electrical shock hazards when employer did not ensure that sufficient access was provided around the breaker box in the production retread shop.
Recent events (2)
  • — I (O) $1800
  • — Z (S) $3000

1910.305 G01

Serious Gravity 5 3 instances 8 exposed
Issued
Jun 4, 2015
Abate by
Jul 17, 2015
Penalty
Initial $4,000 · Current $2,400 Reduced
29 CFR 1910.305(g)(1):  Flexible cords and cables may not be used where they are attached to building surfaces:    On or about February 18, 2015, employees were exposed to electrical shock hazards when flexible cords were being used as permanent wiring in the shop:    a)  Buffer area (2),    b)  Production retread area.
Recent events (2)
  • — I (S) $2400
  • — Z (S) $4000

1910.305 G02 III

Serious Gravity 5 4 instances 8 exposed
Issued
Jun 4, 2015
Abate by
Jul 17, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii):   Employer did not ensure the flexible cords and cables connected to devices and fittings had strain relief provided to prevent pull from being directly transmitted to joints or terminal screws:    On February 18, 2015, employees working in the production and retread areas were exposed to electrical shock hazards from flexible cords and cables to equipment not being provided strain relief:    a)  Marangoni-Ringtread 1000 E,    b)  Bosch extruder,    c)  Pendant to hoist by the Matteuzzi RAS 401,    d)  BIMBA Pneu-Turn CP-4.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.101 B

Other-than-serious 1 instance 8 exposed
Issued
Jun 4, 2015
Abate by
Jul 17, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.101(b):  Section 3.4.4, Compressed Gas Association Pamphlet P-1-1965, as adopted by 29 CFR 1910.101(b): Employer did not ensure compressed gas cylinder(s) in use were properly supported to prevent them from being knocked over:    On or about February 18, 2015, employees were exposed to struck-by hazard in that the employer did not ensure the nitrogen cylinder in shop was supported in a manner as to not be knocked over.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.157 C01

Other-than-serious 3 instances 8 exposed
Issued
Jun 4, 2015
Abate by
Jul 17, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1):  Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:    On or February 18, 2015, employees were exposed to burn hazards in that the employer did not ensure portable fire extinguishers were mounted, location identified for easy access:    a)  Tread storage area,     b)  Employees bathroom,    c)  Production retread shop.