Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: HANSON PIPE & PRECAST

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of HANSON PIPE & PRECAST in 801 AIRPORT BLVD, AUSTIN, TX 78702 (NAICS 327332). OSHA activity number 340458736.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hanson Pipe & Precast — free Get an email when a new federal OSHA severe-injury report for Hanson Pipe & Precast is published. One employer, no account, unsubscribe in one click.
Site address
801 AIRPORT BLVD
City
AUSTIN
State
TX
ZIP
78702
Mailing
801 AIRPORT BLVD, AUSTIN, TX 78702
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327332
Employees
45
Ownership type
A

3 citations on file for this inspection.

1910.29 A04 II

Serious Gravity 5 1 instance 15 exposed
Issued
Jun 3, 2015
Abate by
Jun 17, 2015
Penalty
Initial $3,500 · Current $2,100 Reduced
29 CFR 1910.29(a)(4)(ii): All scaffold casters were not provided with a positive wheel and/or swivel lock to prevent movement.   On or about 9 March 2015, the employer did not provide a means for locking the wheels of five (5) job fabricated, manually-propelled mobile ladders during use, exposing employees to a fall hazard.
Recent events (2)
  • — I (S) $2100
  • — Z (S) $3500

1910.253 B04 III

Other-than-serious 1 instance 15 exposed
Issued
Jun 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one-half hour.  On or about 9 March 2015, the oxygen cylinders and acetylene cylinders were stored without a 20 foot separation or a fire resistance barrier, exposing employees working in the area to a fire or explosion hazard.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 E01

Other-than-serious 1 instance 15 exposed
Issued
Jun 3, 2015
Abate by
Jun 17, 2015
Penalty
Initial $500 · Current $300 Reduced
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed so as to prevent moisture or water from entering and accumulating within the enclosures.   On or about 9 March 2015, water from a roof leak was dripping onto an electrical socket that was not rated for moist environments. Although it had a GFCI, it did not have barriers for preventing moisture from entering into the socket exposing employees to an electrical shock hazard.
Recent events (2)
  • — I (O) $300
  • — Z (O) $500

View Hanson Pipe & Precast's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340458736.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.