On , OSHA opened a referral safety inspection of GENERAL ELECTRIC INTERNATIONAL, INC. in 22710 206TH AVE NORTH, CORDOVA, IL 61242 (NAICS 221118). OSHA activity number 340478924.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch General Electric International, INC. — free Get an email when a new federal OSHA severe-injury report for General Electric International, INC. is published. One employer, no account, unsubscribe in one click.
Site address
22710 206TH AVE NORTH
City
CORDOVA
State
IL
ZIP
61242
Mailing
4710 HUDSON DRIVE, STOW, OH 44224
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221118
Employees
8
Ownership type
A

2 citations on file for this inspection.

1910.269 D06 VII

Serious Gravity 10 1 instance 1 exposed
Issued
Aug 31, 2015
Abate by
Sep 4, 2015
Penalty
Initial $6,300 · Current $6,300
29 CFR 1910.269(d)(6)(vii): Before starting work on machines or equipment that have been locked out or tagged out, the authorized employee shall verify that isolation and de-energizing of the machine or equipment have been accomplished. If normally energized parts will be exposed to contact by an employee while the machine or equipment is de-energized, a test shall be performed to ensure that these parts are de-energized:    On March 14, 2015, the employee was directed to remove three electrical insulators located in close proximity to energized parts in Cubical 9, Bus 12 and failed to verify the equipment being maintained was de-energized before the start of work.  The employee was exposed to electrocution/high voltage electrical shock.
Recent events (2)
  • — I (S) $6300
  • — Z (S) $6300

1910.269 D08 IV

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Aug 31, 2015
Abate by
Sep 4, 2015
Penalty
Initial $6,300 · Current $0 Reduced
29 CFR 1910.269(d)(8)(iv): Whenever outside servicing personnel are to be engaged in activities covered by paragraph (d) of this section, the on-site employer and the outside employer shall inform each other of their respective lockout or tagout procedures, and each employer shall ensure that his or her personnel understand and comply with restrictions and prohibitions of the energy control procedures being used:   On March 14, 2015, the employee was directed to remove three electrical insulators in close proximity to energized parts, located in Cubical 9, Bus 12, and the employer failed to ensure the employee understood and complied with the procedures, restrictions or prohibitions of the energy control procedures being used by the on-site employer's system operator. The employee was exposed to electrocution/high voltage electric shock.