RIVERHEAD, NY —
OSHA Inspection: ADCHEM CORP.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of ADCHEM CORP. in 1852 OLD COUNTRY RD, RIVERHEAD, NY 11901 (NAICS 322220). OSHA activity number 340494756.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ADCHEM CORP.
- Site address
- 1852 OLD COUNTRY RD
- City
- RIVERHEAD
- State
- NY
- ZIP
- 11901
- Mailing
- 1852 OLD COUNTRY RD, RIVERHEAD, NY 11901
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 322220
- Employees
- 120
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.147 C04 I
- Issued
- Sep 23, 2015
- Abate by
- Nov 10, 2015
- Penalty
- Initial $6,300 · Current $6,300
General-duty citation text
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) Workplace, Solvent Mixing Dept. - The employer did not develop, document and utilize procedures to control hazardous electrical and mechanical energy for employees performing cleaning, maintenance, repair or adjustments to Marathon Solvent mixing machine, Model EL283TTGN18038AAL; on or about 3/27/15. b) Workplace, Solvent Mixing Dept. - The employer did not develop, document and utilize procedures to control hazardous electrical and mechanical energy for employees performing cleaning, maintenance, repair or adjustments to S & H Equipment Corp. mixing machine, Model HVR 25, Serial #76-1068; on or about 3/27/15. Note: In addition to abatement certification the employer is required to submit abatement documentation for this item in accordance with 29 CFR 1903.19.
Recent events (2)
- — I (S) $6300
- — Z (S) $6300
1910.147 C05 I
- Issued
- Sep 23, 2015
- Abate by
- Nov 10, 2015
- Penalty
- Initial $6,300 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(5)(i): Locks, tags, chains, wedges, key blocks, adapter pins, self-locking fasteners, or other hardware shall be provided by the employer for isolating, securing or blocking of machines or equipment from energy sources: a) Workplace, Solvent Mixing Dept.- There were no devices for isolating machines or equipment from electrical or mechanical energy sources when employees performed cleaning or maintenance on the Marathon Solvent mixing machine, Model EL283TTGN18038AAL; on or about 3/27/15. b) Workplace, Solvent Mixing Dept. - There were no devices for isolating machines or equipment from electrical or mechanical energy sources when employees performed cleaning or maintenance on the S & H Equipment Corp. mixing machine, Model HVR 25, Serial #76-1068; on or about 3/27/15. Note: In addition to abatement certification the employer is required to submit abatement documentation for this item in accordance with 29 CFR 1903.19.
Recent events (2)
- — I (S) $0
- — Z (S) $6300
1910.147 C07 I
- Issued
- Sep 23, 2015
- Abate by
- Nov 10, 2015
- Penalty
- Initial $6,300 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(7)(i): The employer did not provide training to ensure that the purpose and function of the energy control program are understood by employees and that the knowledge and skills required for the safe application, usage, and removal of the energy controls are acquired by employees: a) Workplace, Solvent Mixing Dept. -The employees were performing cleaning functions on machines such as Marathon Solvent mixing machine, Model EL283TTGN18038AAL and S & H Equipment Corp. mixing machine, Model HVR 25, Serial #76-1068 without having received adequate instruction on the safe application, usage, and removal of the electrical and mechanical energy controls are acquired by employees; on or about 3/27/15. Note: In addition to abatement certification the employer is required to submit abatement documentation for this item in accordance with 29 CFR 1903.19.
Recent events (2)
- — I (S) $0
- — Z (S) $6300
1910.212 A01
- Issued
- Sep 23, 2015
- Abate by
- Oct 1, 2015
- Penalty
- Initial $6,300 · Current $6,300
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: a) Workplace, Solvent Mixing Dept. - The Marathon Solvent Mixing Machine, Model EL283TTGN18038AAL, did not have a fixed guard protecting the employee from rotating parts of the shaft and mixing blades; on or about 3/27/15. b) Workplace, Solvent Mixing Dept. - The S & H Mixing Machine, Model HVR 25, Serial #76-1068, did not have a fixed guard protecting the employee from rotating parts of the shaft and mixing blades; on or about 3/27/15. Note: In addition to abatement certification the employer is required to submit abatement documentation for this item in accordance with 29 CFR 1903.19.
Recent events (2)
- — I (S) $6300
- — Z (S) $6300
More inspections at Adchem Corp.
View Adchem Corp.'s full OSHA safety record →
More inspections in this industry (NAICS 322220)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340494756.