Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MARINE CORPS AIR GROUND COMBAT CENTER, MAGTFTC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of MARINE CORPS AIR GROUND COMBAT CENTER, MAGTFTC in PWD, FACILITIES MAINT., BLDG. 1123, TWENTYNINE PALMS MCB, CA 92278 (NAICS 928110). OSHA activity number 340507078.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Marine Corps AIR Ground Combat Center, Magtftc — free Get an email when a new federal OSHA severe-injury report for Marine Corps AIR Ground Combat Center, Magtftc is published. One employer, no account, unsubscribe in one click.
Site address
PWD, FACILITIES MAINT., BLDG. 1123
City
TWENTYNINE PALMS MCB
State
CA
ZIP
92278
Mailing
MAGTFTC, MCAGCC - SAFETY BLDG. 1447, TWENTYNINE PALMS MCB, CA 92278
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
928110
Employees
2200
Ownership type
D

8 citations on file for this inspection.

1910.22 D01

Serious Gravity 5 1 instance 4 exposed
Issued
Jul 16, 2015
Abate by
Aug 10, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.22(d)(1): On every building or other structure, or part thereof, used for mercantile, business, industrial or storage purposes, the loads approved by the building official were not marked on plates of approved design and securely affixed in a conspicuous place in each space to which they relate.  (a) At the Facilities Maintenance Bldg. 1123, in the sign shop, the load limit for the upper mezzanine was not posted.
Recent events (1)
  • — Z (S) $0

1910.215 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 16, 2015
Abate by
Jul 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.215(a)(1): Abrasive wheel(s) used on grinding machinery were not used with safety guard(s).  (a) At the Facilities Maintenance Bldg. 1123, welding shop, the portable Milwaukee grinder used for grinding metals did not have its guard installed.
Recent events (1)
  • — Z (S) $0

1910.215 A04

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 16, 2015
Abate by
Jul 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:  (a) At the Facilities Maintenance Bldg. 1123, welding shop, thework rest for the CQ grinder was approximately one fourth inch from the wheel.
Recent events (1)
  • — Z (S) $0

1910.215 B09

Serious Gravity 5 1 instance 2 exposed
Issued
Jul 16, 2015
Abate by
Jul 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9): Guard for abrasive wheel machine where the operator stands in front of the machine was not constructed so that the peripheral protecting member could be adjusted to the constantly decreasing diameter of the wheel.  (a) At the Facilities Maintenance Bldg. 1123, welding shop, the CQ grinder used for grinding metals did not have its tongue guard installed.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 5 2 instances 4 exposed
Issued
Jul 16, 2015
Abate by
Jul 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling.  (a) At the Facilities Maintenance Bldg. 1123, carpenter shop, a re-locatable power tap was permanently mounted on the side of the shear table.  (b) At the Facilities Maintenance Bldg. 1123, carpenter shop, the re-locatable power taps were daisy chained, one re-locatable power tap was connected to the other.
Recent events (1)
  • — Z (S) $0

1910.304 F01 IV

Serious Gravity 1 1 instance 4 exposed
Issued
Jul 16, 2015
Abate by
Jul 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel.  (a) At the Facilities Maintenance Bldg. 1123, welding shop, the square D safety switch was obstructed by a miller matic 252 welder and work benches.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 4 exposed
Issued
Jul 16, 2015
Abate by
Jul 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws.  (a) At the Facilities Maintenance Bldg. 1123, carpenter shop, the shear table's power cord did not have strain relief, insulation separated from the cord showing conductors.
Recent events (1)
  • — Z (S) $0

1910.157 E02

Other-than-serious 2 instances 2 exposed
Issued
Jul 16, 2015
Abate by
Jul 24, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(2): Portable fire extinguishers were not visually inspected at least monthly.  (a) At the Facilities Maintenance Bldg. 1123, carpenter shop, the portable fire extinguisher was last inspected November, 2014.
Recent events (1)
  • — Z (O) $0

View Marine Corps AIR Ground Combat Center, Magtftc's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340507078.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.