STUART, FL —
OSHA Inspection: VIESEL FUEL, LLC
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of VIESEL FUEL, LLC in 3041 SE DOMINICA TERRACE, STUART, FL 34997 (NAICS 311225). OSHA activity number 340519826.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VIESEL FUEL, LLC
- Site address
- 3041 SE DOMINICA TERRACE
- City
- STUART
- State
- FL
- ZIP
- 34997
- Mailing
- 3041 SE DOMINICA TERRACE, STUART, FL 34997
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 311225
- Employees
- 45
- Ownership type
- A
Citations
8 citations on file for this inspection.
1910.157 C01
- Issued
- Aug 11, 2015
- Abate by
- Aug 28, 2015
- Penalty
- Initial $3,850 · Current $3,850
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: (a) On or about April 3, 2015, at the above addressed worksite, in the diesel fuel storage area, a fire extinguisher was mounted on the wall blocked by the 1000 gallon diesel fuel tank, exposing employees to the hazards of fire and/or burns in the event of a fire.
Recent events (2)
- — I (S) $3850
- — Z (S) $3850
1910.305 G01 IV A
- Issued
- Aug 11, 2015
- Abate by
- Aug 28, 2015
- Penalty
- Initial $5,390 · Current $5,390
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: (a) On or about April 3, 2015, at the above addressed worksite, the Fill-Rite pumps on two 1000 gallon diesel storage tanks were wired with temporary wiring and plugged into a wall receptacle, exposing the employees to the hazards of electrical shock/burns and/or fire and explosions. (b) On or about April 3, 2015, at the above addressed worksite, the NexGen Coriolis Flow Transmitter in the biodiesel storage area was wired with temporary wiring and plugged into a multiple outlet strip then further plugged into a wall receptacle, exposing employees to the hazards of electrical shock/burns and/or fire and explosions. (c) On or about April 3, 2015, at the above addressed worksite, the ChemTech PulsaFeeder pump on top of the BioExtend tote in the biodiesel storage area was wired with temporary wiring, run in series with another flow switch and then plugged into a wall receptacle, exposing employees to the hazards of electrical shock/burns and/or fire and explosions. (d) On or about April 3, 2015, at the above addressed worksite, the McDonnell & Miller Flow Switch located in the biodiesel storage area was wired with temporary wiring, run in series with the ChemTech PulsaFeeder and then plugged into a wall receptacle, exposing employees to the hazards of electrical shock/burns and/or fire and explosions.
Recent events (2)
- — I (S) $5390
- — Z (S) $5390
1910.305 G01 IV D
- Issued
- Aug 11, 2015
- Abate by
- Aug 28, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces: (a) On or about April 3, 2015, at the above addressed worksite, the flexible cords used for the wiring of the ChemTech PulsaFeeder run in series with the McDonnell & Miller Flow Switch were attached to the overhead piping in the biodiesel storage area and along the wall to the electrical outlet, exposing employees to the hazards of electrical shock/burns and/or fire and explosion.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 G02 II
- Issued
- Aug 11, 2015
- Abate by
- Aug 28, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(ii): Flexible cords were not used in continuous lengths without splice or tap: (a) On or about April 3, 2015, at the above addressed worksite, the Fill-Rite pumps on two 1000 gallon diesel storage tanks were wired with spliced temporary wiring and plugged into a wall receptacle, exposing the employees to the hazards of electrical shock/burns and/or fire and explosions. (b) On or about April 3, 2015, at the above addressed worksite, the NexGen Coriolis Flow Transmitter in the biodiesel storage area was wired with spliced temporary wiring and plugged into a multiple outlet strip then further plugged into a wall receptacle, exposing employees to the hazards of electrical shock/burns and/or fire and explosions. (c) On or about April 3, 2015, at the above addressed worksite, the ChemTech PulsaFeeder pump on top of the BioExtend tote in the biodiesel storage area was wired with spliced temporary wiring, run in series with another flow switch and then plugged into a wall receptacle, exposing employees to the hazards of electrical shock/burns and/or fire and explosions. (d) On or about April 3, 2015, at the above addressed worksite, the McDonnell & Miller Flow Switch located in the biodiesel storage area was wired with spliced temporary wiring, run in series with the ChemTech PulsaFeeder and then plugged into a wall receptacle, exposing employees to the hazards of electrical shock/burns and/or fire and explosions.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B01 II
- Issued
- Aug 11, 2015
- Abate by
- Aug 28, 2015
- Penalty
- Initial $3,080 · Current $3,080
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: (a) On or about April 3, 2015, at the above addressed worksite, in the centrifuge area an electrical box on the back wall had a metal knockout missing, exposing employees to the hazards of electrical shock and/or burns in the event of contact.
Recent events (2)
- — I (S) $3080
- — Z (S) $3080
1910.147 C06 I
- Issued
- Aug 11, 2015
- Abate by
- Aug 28, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: (a) On or about April 3, 2015, at the above addressed worksite, the employer had established a program but did not conduct an annual periodic inspection of the energy control procedures for tasks such as maintenance on pumps, exposing the employees to the hazards of electrical shock and/or burns, in the event of unexpected energization.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.147 C07 I
- Issued
- Aug 11, 2015
- Abate by
- Aug 28, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that employees acquired the knowledge and skills required for the safe application, usage and removal of energy control devices: (a) On or about April 3, 2015, at the above addressed worksite, the employer had established a program but did not provide adequate training, exposing the employees to the hazards of electrical shock and/or burns in the event of unexpected energization.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.1200 H01
- Issued
- Aug 11, 2015
- Abate by
- Aug 28, 2015
- Penalty
- Initial $770 · Current $770
General-duty citation text
29 CFR 1910.1200(h)(1): Employees were not provided effective information and training on hazardous chemicals in their work area at the time of their initial assignment and whenever a new hazard that the employees had not been previously trained about was introduced into their work area: (a) On or about April 3, 2015, at the above addressed worksite, employees had not received training upon their initial assignment, exposing the employees to the hazards of chemicals such as caustic soda and sulfuric acid.
Recent events (2)
- — I (O) $770
- — Z (O) $770
More inspections at Viesel Fuel, LLC
View Viesel Fuel, LLC's full OSHA safety record →
More inspections in this industry (NAICS 311225)
More inspections in FL
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340519826.