OSHA Inspection: DEPARTMENT OF THE INTERIOR, U.S. FISH AND WILDLIFE SERVICE, PENDILLS CREEK NATIONAL FISH HATCHERY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of DEPARTMENT OF THE INTERIOR, U.S. FISH AND WILDLIFE SERVICE, PENDILLS CREEK NATIONAL FISH HATCHERY in 21990 W. TROUT LANE, BRIMLEY, MI 49715 (NAICS 112511). OSHA activity number 340529783.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Department of the Interior, U.S. Fish and Wildlife Service, Pendills Creek National Fish Hatchery — free Get an email when a new federal OSHA severe-injury report for Department of the Interior, U.S. Fish and Wildlife Service, Pendills Creek National Fish Hatchery is published. One employer, no account, unsubscribe in one click.
Site address
21990 W. TROUT LANE
City
BRIMLEY
State
MI
ZIP
49715
Mailing
21990 W. TROUT LANE, BRIMLEY, MI 49715
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
112511
Employees
13
Ownership type
D

8 citations on file for this inspection.

1910.147 C04 I

Serious Gravity 5 1 instance 13 exposed
Issued
Sep 30, 2015
Abate by
Nov 18, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(4)(i) as required by 1960.8(b): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:  The employer did not develop procedures to control and isolate hazardous energy exposing employees to mechanical and electrical energy hazards while performing servicing and/or maintenance work on machines or equipment such as but not limited to Hydrolox Traveling Screen, and Hydrotech Drum Filter system.
Recent events (1)
  • — Z (S) $0

1910.147 C06 I

Serious Gravity 5 1 instance 13 exposed
Issued
Sep 30, 2015
Abate by
Nov 18, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(6)(i) as required by 1960.8(b):  The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:   The employer did not conduct an inspection of the energy control procedures to ensure that they were properly implemented during servicing and/or maintenance on equipment.
Recent events (1)
  • — Z (S) $0

1910.147 C07 I B

Serious Gravity 5 1 instance 13 exposed
Issued
Sep 30, 2015
Abate by
Nov 18, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.147(c)(7)(i)(B) as required by 1960.8(b): Affected employee(s) was not instructed in the purpose and use of the energy control procedure.  The employer did not provide training to "affected" employees on applicable hazardous energy sources, types and magnitude of energy, and the means and methods of isolating and/or controlling energy, and the means of verification of effective energy control, and the purpose of the procedure to be used.
Recent events (1)
  • — Z (S) $0

1910.219 F03

Serious Gravity 1 1 instance 7 exposed
Issued
Sep 30, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.219(f)(3) as required by 1960.8(b): Sprocket wheels and chains which were seven -7 feet or less above floors or platforms were not enclosed:   In the Traveling Screen Building, a sprocket and chain was not guarded on the Hydrolox Travel Screen, there by exposing employees to caught in and amputation hazard.
Recent events (1)
  • — Z (S) $0

1910.304 G05

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 30, 2015
Abate by
Oct 27, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5) as required by 1960.8(b): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:   In the Maintenance shop,  a Rigid wet/dry shop vacuum used to clean up debris in the shop was missing a ground plug on the power cord and did not have a continuous ground there by exposing employees to an electrical shock hazard.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 2 instances 1 exposed
Issued
Sep 30, 2015
Abate by
Oct 27, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i) as required by 1960.8(b): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose:   a. In the maintenance shop, a junction box near the drill press was missing a cover plate, wires were protruding from the box and not all wires were capped off exposing employees to an electrical hazards.  b. In the maintenance shop, a toggle and duplex combination wall plate was not used or installed in accordance with manufacturer's instructions. The wall plate was being used to cover a duplex outlet, there was no toggle switch installed leaving an opening in the wall plate there by exposing employees to an electrical and fire hazards.
Recent events (1)
  • — Z (S) $0

1910.242 B

Repeat Gravity 1 1 instance 7 exposed
Issued
Sep 30, 2015
Abate by
Oct 27, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.242(b) as required by 1960.8(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:   In the boiler room , a locally manufactured air nozzle used for cleaning purposes did not reduce the air pressure to 30 p.s.i. The air pressure was set at approximately 90 p.s.i., there by exposing employees to a struck by hazard.    The U. S. Fish and Wildlife Service was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.242(b), which was contained in OSHA Inspection number 923101, Notice number 1, Item number 3 issued on July 31, 2013 with respect to a workplace located at 1390 Buskin River Road in Kodiak, Alaska which became a final order on August 8, 2013.
Recent events (1)
  • — Z (R) $0

1910.305 B01 II

Other-than-serious 2 instances 7 exposed
Issued
Sep 30, 2015
Abate by
Oct 27, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii) as required by 1960.8(b):  Unused openings in boxes, cabinets, or fittings were not effectively closed:  The employer failed to ensure unused openings (knockouts) in boxes and cabinets were effectively closed:  (a) In the Maintenance Shop, One Phase circuit breaker panel was missing one knockout.  (b) In the Drum Filter building, electrical panel was missing one knockout.