PEACH SPRINGS, AZ —
OSHA Inspection: INDIAN HEALTH SERVICE - PEACH SPRINGS HEALTH CENTER
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of INDIAN HEALTH SERVICE - PEACH SPRINGS HEALTH CENTER in 943 HUALAPAI WAY, PEACH SPRINGS, AZ 86434 (NAICS 923120). OSHA activity number 340678234.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- INDIAN HEALTH SERVICE - PEACH SPRINGS HEALTH CENTER
- Site address
- 943 HUALAPAI WAY
- City
- PEACH SPRINGS
- State
- AZ
- ZIP
- 86434
- Mailing
- 12033 AGENCY ROAD, PARKER, AZ 85344
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 923120
- Employees
- 14000
- Ownership type
- D
Citations
7 citations on file for this inspection.
1910.37 B02
- Issued
- Aug 13, 2015
- Abate by
- Aug 27, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) At the Dental Unit exit door was not marked or labeled "EXIT".
Recent events (1)
- — Z (S) $0
1910.37 B04
- Issued
- Aug 13, 2015
- Abate by
- Aug 27, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent. a) At the Dental Unit spaces, no signs were posted indicating the direction of nearest exit or exit discharge.
Recent events (1)
- — Z (S) $0
1910.304 G05
- Issued
- Aug 13, 2015
- Abate by
- Aug 27, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective. a) At the Gym, Wellness and Training room 139, the Life Fitness Treadmill's power cord used for exercising is missing its ground pin.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Aug 13, 2015
- Abate by
- Aug 27, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and cables were used as a substitute for fixed wiring of a structure. a) At the Dental reception area, an extension cord was used to energize the Fellowes 58-89C shredder for more than six months.
Recent events (1)
- — Z (S) $0
1910.36 G02
- Issued
- Aug 13, 2015
- Abate by
- Aug 27, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(g)(2): Exit access(es) were not at least 28 inches (71.1 cm) wide at all points. a) At the Medical Unit Contract Health Room 134, exit/egress was narrowed down to 18 inches wide. The Indian Health Services was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.36(g)(2), which was contained in OSHA inspection number 315492090, citation number 1, item number 1 and was affirmed as a final order on 10/14/2011, with respect to a workplace located at IHS, 1 Cibercue Circle, Bldg 392, San Carlos AZ 85000.
Recent events (1)
- — Z (R) $0
1910.176 B
- Issued
- Aug 13, 2015
- Abate by
- Aug 27, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.176(b): Secure storage. Storage of material created hazards. Bags, containers, bundles, etc., stored in tiers were not stacked, blocked, interlocked and limited in height so that they are stable and secure against sliding or collapse. a) At the Medical Unit Pharmacy room 149, materials stored on top of shelves were not secured against sliding or collapse. The Indian Health Services was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.176(b), which was contained in OSHA inspection number 315491944, citation number 1, item number 2 and was affirmed as a final order on 02/03/2012, with respect to a workplace located at IHS, Chinle Comp Health Care Facility, HWY 191 Hospital Road, Chinle, AZ 86503.
Recent events (1)
- — Z (R) $0
1910.303 B02
- Issued
- Aug 13, 2015
- Abate by
- Aug 27, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling. a) At the Sterile room 109, a re-locatable power tap was used to energized the Absocold and the Hotpoint refrigerators. The Indian Health Services was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.303(b)(2), which was contained in OSHA inspection number 315491936, citation number 1, item number 2 and was affirmed as a final order on 11/23/2011, with respect to a workplace located at IHS, Navajo Area Warehouse, HWY 264, Bldg. 2, St. Michaels, AZ 86511.
Recent events (1)
- — Z (R) $0
More inspections at Indian Health Service - Peach Springs Health Center
View Indian Health Service - Peach Springs Health Center's full OSHA safety record →