Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GEMINI GROUP, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of GEMINI GROUP, INC. in 1101 BURGUNDY DR., EL PASO, TX 79907 (NAICS 326199). OSHA activity number 340679836.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Gemini Group, INC. — free Get an email when a new federal OSHA severe-injury report for Gemini Group, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
GEMINI GROUP, INC.
Site address
1101 BURGUNDY DR.
City
EL PASO
State
TX
ZIP
79907
Mailing
1101 BURGUNDY DR., EL PASO, TX 79907
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
326199
Employees
148
Ownership type
A

3 citations on file for this inspection.

1910.305 A04 II

Serious Gravity 10 20 instances 20 exposed
Issued
Nov 23, 2015
Abate by
Jan 11, 2016
Penalty
Initial $7,000 · Current $5,000 Reduced
29 CFR 1910.305(a)(4)(ii): Conductors smaller than No. 8 were not rigidly supported on noncombustible, nonabsorbent insulating materials and may not contact any other objects.    Production Line: On or about June 3, 2014, the employer did not ensure that conductors smaller than No. 8 were rigidly supported on noncombustible, nonabsorbent insulated material and not in contact with equipment. Employees were exposed to hazards associated with electrical shock, arcing, and burns.
Recent events (2)
  • — I (S) $5000
  • — Z (S) $7000

1910.303 A

Serious Gravity 10 20 instances 20 exposed
Issued
Nov 23, 2015
Abate by
Dec 11, 2015
Penalty
Initial $70,000 · Current $7,000 Reduced

Hazardous substances 8870

29 CFR 1910.303(a): The conductors and/or equipment required or permitted by this subpart were not approved:    Production Line Area: On or about June 3, 2015 the employer did not ensure that extruders, pre-setup carts, heater bands, and related accessories such as, but not limited to, conductors and electrical components were designed and/or approved for use in wet locations. Employees operating uncertified or unlabeled electrical energized equipment were exposed to hazards associated with electrical shock, arcing, and burns.
Recent events (2)
  • — I (S) $7000
  • — Z (W) $70000

1910.333 A

Other-than-serious 20 instances 20 exposed
Issued
Nov 23, 2015
Abate by
Jan 11, 2016
Penalty
Initial $7,000 · Current $3,500 Reduced

Hazardous substances 8870

29 CFR 1910.333(a): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work was performed near or on equipment or circuits which were or could be energized:    Production Line Cart-13: On or about June 3, 2014, the employer did not ensure that employee(s) were provided with and required to use proper procedures and/or safe work practices when working on or beside energized electrical circuit parts and related equipment. Employees were exposed to hazards associated with electrical shock, arcing, and burns.
Recent events (2)
  • — I (O) $3500
  • — Z (S) $7000

View Gemini Group, INC.'s full OSHA safety record →