NORTH GRAFTON, MA —
OSHA Inspection: WYMAN GORDON COMPANY
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of WYMAN GORDON COMPANY in 244 WORCESTER STREET, NORTH GRAFTON, MA 01536 (NAICS 332112). OSHA activity number 340694652.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- WYMAN GORDON COMPANY
- Site address
- 244 WORCESTER STREET
- City
- NORTH GRAFTON
- State
- MA
- ZIP
- 01536
- Mailing
- PO BOX 8001 244 WORCESTER STREET, NORTH GRAFTON, MA 01536
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 332112
- Employees
- 1500
- Ownership type
- A
Citations
17 citations on file for this inspection.
5(a)(1)
- Issued
- Dec 4, 2015
- Abate by
- Dec 23, 2015
- Penalty
- Initial $5,500 · Current $5,500
General-duty citation text
Section 5(a)(1) of the Occupational Safety and Health Act of 1970: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or serious physical harm to employees in that, employees were exposed to crushing and struck by injuries: While performing a site specific targeting inspection walkthrough from June 8 through June 12, 2015 at the Wyman Gordon facility in North Grafton, Massachusetts, four employees were observed operating powered industrial trucks without wearing seat belts exposing them to serious injuries in the event of a tip-over or other accident.
Recent events (2)
- — I (S) $5500
- — Z (S) $5500
1910.22 A01
- Issued
- Dec 4, 2015
- Abate by
- Jan 25, 2016
- Penalty
- Initial $4,400 · Current $4,400
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, passageways, storerooms or service rooms were not kept clean and orderly or in a sanitary condition. Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; The facility was not kept clean to the extent that the nature of the work allowed. a. Catwalk - unused equipment and dust/oil on the catwalk creating slip and fall hazard b. 35,000 ton press - extension cords and equipment creating a tripping hazard c. 50,000 ton press pump room - oil and water on steel grating creating slip, trip, fall hazards
Recent events (2)
- — I (S) $4400
- — Z (S) $4400
1910.37 B04
- Issued
- Dec 4, 2015
- Abate by
- Jan 31, 2016
- Penalty
- Initial $5,500 · Current $5,500
General-duty citation text
29 CFR 1910.37(b)(4): Signs were not posted along the exit access indicating the direction of travel to the nearest exit and exit discharge when the direction of travel to the exit or exit discharge was not immediately apparent: Forge Shop and Office Building, Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; The employer did not ensure signs were posted along exit access to indicate the direction of travel to the nearest exit. a. Forge Shop - large space in aisle ways and grinding area where no exits are visible b. Main Office Building - hallways are not straight and exit signs are blocked which could confuse employees in an emergency
Recent events (2)
- — I (S) $5500
- — Z (S) $5500
1910.37 B05
- Issued
- Dec 4, 2015
- Abate by
- Dec 23, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(5): Each doorway or passage along an exit access that could be mistaken for an exit was not marked "Not an Exit" or similar designation, or be identified by a sign indicating its actual use (e.g. closet): Facility wide, Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; The employer did not ensure that each doorway or passage along an exit route that could be mistaken for an exit was identified as "not an exit" or similar designation. a. Door by the Forge Shop Office not marked b. Door in the 50,000 ton press pump room c. Several doors in the office area that go to offices and closets
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.151 C
- Issued
- Dec 4, 2015
- Abate by
- Dec 10, 2015
- Penalty
- Initial $5,500 · Current $5,500
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: 50,000 ton press pump room, Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; Sodium hydroxide is used in the pump room to limit bacteria growth in pressurized cylinders that have water in them. The eyewash in the pump room did not have sufficient pressure to clear an employee's eyes of chemicals in the event of an accidental exposure.
Recent events (2)
- — I (S) $5500
- — Z (S) $5500
1910.157 C01
- Issued
- Dec 4, 2015
- Abate by
- Jan 31, 2016
- Penalty
- Initial $4,400 · Current $4,400
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: Facility wide, Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; The employer did not mount, locate or identify fire extinguishers so that they were accessible without subjecting employees to injuries. Multiple fire extinguishers were blocked or not mounted, preventing ready access to employees. a. Spray area - blocked by debris, wood, and barrels b. Forge shop - blocked by barrels, trash, and dunnage c. Forge shop - blocked by a metal bench d. Supervisor's desk in Forge shop - Fire extinguisher on the floor and not mounted.
Recent events (2)
- — I (S) $4400
- — Z (S) $4400
1910.212 A05
- Issued
- Dec 4, 2015
- Abate by
- Dec 14, 2015
- Penalty
- Initial $5,500 · Current $5,500
General-duty citation text
29 CFR 1910.212(a)(5): Fan blade guard(s) were not provided where the periphery of the blades was less than seven feet from the floor or working level: Die Shop, Oil heater for machine 6045, Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; The employer did not ensure fan blades were provided with guards where the periphery of the blades was less than seven feet from the working level and approximately 4 inches from the open side of the machine. The side cover of the oil heater had been removed, exposing employees to unguarded fan blades.
Recent events (2)
- — I (S) $5500
- — Z (S) $5500
1910.303 B01 IV
- Issued
- Dec 4, 2015
- Abate by
- Dec 16, 2015
- Penalty
- Initial $7,000 · Current $7,000
8870
General-duty citation text
29 CFR 1910.303(b)(1)(iv): Electric equipment was not free from the recognized hazard of damaged insulation. Forge Shop, Wyman and Gordon, 244 Worcester Street, North Grafton, Massachusetts; Extension cords were in use with damage to the outer jackets and some with exposed, energized conductors, exposing employees to electric shock hazards from the 120 VAC circuits. a. the cord used to charge the JLG lift had exposed conductors b. the cord used to charge Instrument Department Golf Cart #3 had exposed conductors c. the cord used to power the spotlight for PIT repairs in the hut had exposed conductors after a forklift was driven off with the light attached and pulled the wires free from the light.
Recent events (2)
- — I (S) $7000
- — Z (S) $7000
1910.303 B02
- Issued
- Dec 4, 2015
- Abate by
- Jan 31, 2016
- Penalty
- Initial $4,400 · Current $4,400
8870
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; The employer did not ensure that listed and labeled equipment was used in accordance with the instructions included in the listing or labeling. On or about June 9, 2015, employees were exposed to electric shock hazards where 120 VAC electrical equipment was used outside of the approved listing labeling as tested by a National Recognized Testing Laboratory. a. Dimensional inspectors, by the Marvel Saws, were using a cart with a relocatable power tap which was powered via an extension cord. b. Photo shop employees were using testing equipment powered by a series of extension cords and relocatable power taps. c. Spray booth, relocatable power tap was used to power pumps.
Recent events (2)
- — I (S) $4400
- — Z (S) $4400
1910.304 G05
- Issued
- Dec 4, 2015
- Penalty
- Initial $0 · Current $0
8870
General-duty citation text
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: Shipping area, Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; The microwave used by employees in the shipping area was plugged into a relocatable power tap (RPT). The RPT had a two prong adapter that defeated the grounding of the RPT which exposed employees to an electric shock hazard while using the microwave oven.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.305 B02 I
- Issued
- Dec 4, 2015
- Abate by
- Dec 14, 2015
- Penalty
- Initial $5,500 · Current $5,500
8870
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each pull box, junction box, and fitting was not provided with a cover identified for that purpose. Utility Laborers Hut, Wyman Gordon Company, 244 Worcester Street, North Grafton, Massachusetts; A junction box located near the Utility Laborers Hut by the KO pins did not have a cover and had exposed conductors exposing employees to 120 volt electric shock hazards.
Recent events (2)
- — I (S) $5500
- — Z (S) $5500
1910.305 G01 IV A
- Issued
- Dec 4, 2015
- Abate by
- Jan 31, 2016
- Penalty
- Initial $4,400 · Current $4,400
8870
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: Facility wide, Wyman and Gordon, 244 Worcester Street, North Grafton, Massachusetts; Flexible cords were used throughout the facility to provide power for equipment in lieu of permanent wiring. a. the employee break area providing power to refrigerators b. power to equipment in the photo shop c. to power the air compressor in furnace 9505 in the forge shop
Recent events (2)
- — I (S) $4400
- — Z (S) $4400
1910.305 G01 IV D
- Issued
- Dec 4, 2015
- Abate by
- Dec 16, 2015
- Penalty
- Initial $0 · Current $0
8870
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces: Furnace 9505 in Forge Shop, Wyman and Gordon, 244 Worcester Street, North Grafton, Massachusetts; The flexible cords being used to power equipment were attached to the building with wire ties. a. The air compressor on the lower level of the 9505 furnace was permanently attached to the metal decking using wire ties. b. Flexible cord was attached to the conduit powering a fire control cabinet in the 50,000 ton press pump room
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.212 A01
- Issued
- Dec 4, 2015
- Abate by
- Mar 31, 2016
- Penalty
- Initial $38,500 · Current $38,500
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: a. Marvel 25 bandsaws, Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; The employer did not provide guards sufficient to protect employees from exposed blades while operating Marvel bandsaws to trim metal parts. 1. Gap from the part to the blade guard on the first part was approximately 3 inches 2. Gap from the part to the blade guard on the second part was approximately 4 inches b. Wyman Gordon Company, 244 Worcester Street, North Grafton, Massachusetts; Milling machines were not guarded to prevent employees from coming into contact with the point of operation: 1. Machine shop, Olympia Milling Machine - The milling machine was not guarded at the point of operation to protect the employees from amputation hazards. 2. Maintenance Hut - The Bridgeport milling machine in the maintenance shop was not guarded to prevent employees from access at the point of operations. 3. Machine shop, multi-spindle milling machine with rotating table, was not guarded at the point of operation to protect the employees from amputation hazards. Wyman Gordon was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.212(a)(1), which was contained in OSHA inspection number 315110767, citation number 1, item number 1 and was affirmed as a final order on April 29, 2011, with respect to a workplace located at 3097 E. 61st Street, Cleveland, Ohio.
Recent events (2)
- — I (R) $38500
- — Z (R) $38500
1910.303 G02 II
- Issued
- Dec 4, 2015
- Abate by
- Dec 16, 2015
- Penalty
- Initial $38,500 · Current $38,500
8870
General-duty citation text
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage: Forge Shop and Hut, Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; Employees were exposed to live electric equipment operating at 50 volts or more due to insufficient guarding provided by damaged wall hung distribution panels. The lack of protection for electrical panels exposed employees to electric shock, arc blast, and electrical fire hazards. a. Panel at column A-1-19, 120 volt panel - struck by Powered Industrial Truck exposing conductors observed June 8, 2015 b. Panel 2H, 240 volt panel, in Hut struck by Powered Industrial Truck exposing conductors observed June 10, 2015 Wyman Gordon was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.303(g)(2)(i), which was contained in OSHA inspection number 912469, citation number 1, item number 7a and was affirmed as a final order on August 8, 2013, with respect to a workplace located at 244 Worcester Street, North Grafton, Massachusetts.
Recent events (2)
- — I (R) $38500
- — Z (R) $38500
1910.304 F01 IV
- Issued
- Dec 4, 2015
- Abate by
- Dec 14, 2015
- Penalty
- Initial $16,500 · Current $16,500
8870
General-duty citation text
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: Wyman Gordon, 244 Worcester Street, North Grafton, Massachusetts; The employer did not ensure that overcurrent devices for circuits rated 600 volts, nominal, or less, were readily accessible to each employee or authorized building management personnel. Wall hung distribution panels were blocked by equipment preventing ready access to employees or authorized building management personnel. a. 240V Panels at the bottom of the stairway to maintenance office - blocked by blowers b. Stockcutting area 480V panels are blocked by stock and debris c. Employee break area - 240V panel blocked by refrigerator, water cooler, and water bottles Wyman Gordon was previously cited for a violation of this occupational safety and health standard or its equivalent standard 1910.304(f)(1)(iv), which was contained in OSHA inspection number 912469, citation number 1, item number 8a and was affirmed as a final order on August 8, 2013, with respect to a workplace located at 244 Worcester Street, North Grafton, Massachusetts.
Recent events (2)
- — I (R) $16500
- — Z (R) $16500
1910.101 B
- Issued
- Dec 4, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.101(b): The in-plant handling, storage, and utilization of all compressed gases in cylinders, portable tanks, rail tankcars, or motor vehicle cargo tanks were not in accordance with Compressed Gas Association Pamphlet P-1-1965, which is incorporated by reference as specified in CFR 1910.6: Forge Weld Warehouse, Wyman and Gordon, 244 Worcester Street, North Grafton, Massachusetts; Three oxygen cylinders were stored without having valve cover caps attached.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Wyman Gordon Company
View Wyman Gordon Company's full OSHA safety record →
More inspections in this industry (NAICS 332112)
More inspections in MA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340694652.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.