Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: JJMS INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of JJMS INC. in 733 BROADWAY, ALBANY, NY 12207 (NAICS 238210). OSHA activity number 340710649.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Jjms INC. — free Get an email when a new federal OSHA severe-injury report for Jjms INC. is published. One employer, no account, unsubscribe in one click.
Establishment
JJMS INC.
Site address
733 BROADWAY
City
ALBANY
State
NY
ZIP
12207
Mailing
1 BARNEY RD. #204, CLIFTON PARK, NY 12065
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
17
Ownership type
A

5 citations on file for this inspection.

1926.403 B02

Serious Gravity 5 3 instances 4 exposed
Issued
Aug 26, 2015
Abate by
Sep 1, 2015
Penalty
Initial $2,800 · Current $1,000 Reduced
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification:     a) 733 Broadway, Albany NY. - On or about June 16th, 2015 - Three steel double gang square boxes with 1/2-Inch and 3/4-Inch Knockouts were not mounted to the walls in their areas.  The conduit boxes were not designed for the application.  Employees were exposed to electrical shock hazards.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2800

1926.405 A02 II F

Serious Gravity 5 1 instance 4 exposed
Issued
Aug 26, 2015
Abate by
Sep 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.405(a)(2)(ii)(F): Temporary lights were suspended by their electric cords when such lights and cords were not designed for suspension:  a) 733 Broadway, Albany NY. - On or about June 16th, 2015 - Temporary string lighting was suspended by its cord throughout the work site.  The stringers were not designed for the application.  Employees were exposed to fire and electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 B01

Serious Gravity 5 1 instance 4 exposed
Issued
Aug 26, 2015
Abate by
Sep 1, 2015
Penalty
Initial $2,000 · Current $1,000 Reduced
29 CFR 1926.405(b)(1): Unused openings in cabinets, boxes, and fittings were not effectively closed:    a) 733 Broadway, Albany NY. - On or about June 16th, 2015 - A panel box providing temporary power for the job site had various unused openings that were not closed.  Employees were exposed to electrical shock hazards due to the openings.
Recent events (2)
  • — I (S) $1000
  • — Z (S) $2000

1926.405 B02

Serious Gravity 5 2 instances 4 exposed
Issued
Aug 26, 2015
Abate by
Sep 1, 2015
Penalty
Initial $0 · Current $0
29 CFR 1926.405(b)(2): All pull boxes, junction boxes, and fittings were not provided with covers:    a) 733 Broadway, Albany NY. - On or about June 16th, 2015 - A panel box was installed and providing power to various areas of the work site.  The panel box was not provided with a cover.  Employees were exposed to electrical shock hazards.    b) 733 Broadway, Albany NY. - On or about June 16th, 2015 - Three double gang outlets that were mounted next to a panel box did not have covers.  Employees were exposed to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1926.405 J01 I

Serious Gravity 1 1 instance 4 exposed
Issued
Aug 26, 2015
Abate by
Sep 1, 2015
Penalty
Initial $1,200 · Current $0 Reduced
29 CFR 1926.405(j)(1)(i): Fixtures, lampholders, lamps, rosettes, or receptacles had live parts normally exposed to employee contact:    a) 733 Broadway, Albany NY. - On or about June 16th, 2015 - A temporary light receptacle was missing its cover and bulb.  The 120 volt fixture was exposed to employee contact while lying on the floor.  Employees were exposed to electrical shock hazards.
Recent events (2)
  • — I (S) $0
  • — Z (S) $1200

View Jjms INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340710649.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.