DENALI NATIONAL PARK, AK —
OSHA Inspection: NATIONAL PARK SERVICE
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE in MILE 237 PARKS HIGHWAY, DENALI NATIONAL PARK, AK 99755 (NAICS 811111). OSHA activity number 340738319.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NATIONAL PARK SERVICE
- Site address
- MILE 237 PARKS HIGHWAY
- City
- DENALI NATIONAL PARK
- State
- AK
- ZIP
- 99755
- Mailing
- P.O. BOX 9, DENALI NATIONAL PARK, AK 99755
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811111
- Employees
- 300
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.305 A02 XI
- Issued
- Jul 9, 2015
- Abate by
- Aug 6, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(xi): Cable assemblies and flexible cords and cables were not supported in place at intervals that ensure that they will be protected from physical damage. Third floor, compressor room, on or about 22 June 2015 and times prior thereto; flexible electrical cable was not installed in a manner to prevent physical damage. Orange Romax Type NM-B AWG 10 Dozier/Claw flexible cable was attached via zip ties to two x four lumber mounted to steel beams. Wire was energized and provides electrical power to the compressor. This condition exposed employees to electrical shock and burn hazards.
Recent events (1)
- — Z (S) $0
1910.305 B01 II
- Issued
- Jul 9, 2015
- Abate by
- Aug 6, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed. Auto shop; on or about 22 June 2015 and times prior; three instances were noted where energized electrical openings were not effectively closed: a. Tank room - Electrical cover plate was partially closed. b. Air handler room 2nd floor - Outlet labeled EF3 had a knockout plug missing. c. 3rd floor storage area compressor room - Breaker box labeled 26 had a knockout plug missing. This condition exposed employees to electrical shock and electrical burn hazard.
Recent events (1)
- — Z (S) $0
1910.305 B02 I
- Issued
- Jul 9, 2015
- Abate by
- Aug 6, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy. Storage areas; on or about 22 June 2015 and times prior thereto; two instances were noted where covers were not installed on energized electrical outlet boxes: a. Air handler room, third floor; an energized electrical outlet box mounted overhead, located 79 inches from the floor did not have a cover plated installed. b. Second floor storage area; an energized electrical outlet box located below electrical panel labeled AHU-1 did not have a cover plate installed. This condition exposed employees to an electrical shock and electrical burn hazard.
Recent events (1)
- — Z (S) $0
1910.305 G01 IV D
- Issued
- Jul 9, 2015
- Abate by
- Aug 6, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces. Office, adjacent to doorway; on or about 22 June 2015 and times prior thereto; a blue 15 foot energized extension cord was used in lieu of permanent wiring. Cord was mounted to the wall with cable clamps. This condition exposed employees to electrical shock and electrical burn hazards.
Recent events (1)
- — Z (S) $0
1910.305 G02 III
- Issued
- Jul 9, 2015
- Abate by
- Aug 6, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws. Tank room, on or about 22 June 2015 and times prior thereto; strain relief was not provided on a cord and plug type emergency light. This condition exposed employees to an electrical shock hazard. The National Park Service was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.305(g)(2)(iii), which was contained in OSHA inspection number 559578, citation number 1, item number 3 and was affirmed as a final order on 01 October 2012, with respect to a workplace located at the Main Camp Auto Repair section Bay 2.
Recent events (1)
- — Z (R) $0
More inspections at National Park Service
View National Park Service's full OSHA safety record →
More inspections in this industry (NAICS 811111)
More inspections in AK
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340738319.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.