Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NATIONAL PARK SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE in MILE 237 PARKS HIGHWAY, DENALI NATIONAL PARK, AK 99755 (NAICS 811111). OSHA activity number 340738319.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Park Service — free Get an email when a new federal OSHA severe-injury report for National Park Service is published. One employer, no account, unsubscribe in one click.
Site address
MILE 237 PARKS HIGHWAY
City
DENALI NATIONAL PARK
State
AK
ZIP
99755
Mailing
P.O. BOX 9, DENALI NATIONAL PARK, AK 99755
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811111
Employees
300
Ownership type
D

5 citations on file for this inspection.

1910.305 A02 XI

Serious Gravity 1 1 instance 2 exposed
Issued
Jul 9, 2015
Abate by
Aug 6, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(a)(2)(xi): Cable assemblies and flexible cords and cables were not supported in place at intervals that ensure that they will be protected from physical damage.  Third floor, compressor room, on or about 22 June 2015 and times prior thereto; flexible electrical cable was not installed in a manner to prevent physical damage. Orange Romax Type NM-B AWG 10 Dozier/Claw flexible cable was attached via zip ties to two x four lumber mounted to steel beams. Wire was energized and provides electrical power to the compressor. This condition exposed employees to electrical shock and burn hazards.
Recent events (1)
  • — Z (S) $0

1910.305 B01 II

Serious Gravity 1 3 instances 5 exposed
Issued
Jul 9, 2015
Abate by
Aug 6, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed.   Auto shop; on or about 22 June 2015 and times prior; three instances were noted where energized electrical openings were not effectively closed:       a. Tank room  - Electrical cover plate was partially closed.        b. Air handler room 2nd floor - Outlet labeled EF3 had a knockout plug missing.       c. 3rd floor storage area compressor room - Breaker box labeled 26 had a knockout plug missing.   This condition exposed employees to electrical shock and electrical burn hazard.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 1 2 instances 5 exposed
Issued
Jul 9, 2015
Abate by
Aug 6, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.   Storage areas; on or about 22 June 2015 and times prior thereto; two instances were noted where covers were not installed on energized electrical outlet boxes:       a. Air handler room, third floor; an energized electrical outlet box mounted overhead, located 79 inches from the floor did not have a cover plated installed.       b. Second floor storage area; an energized electrical outlet box located below electrical panel labeled AHU-1 did not have a cover plate installed.    This condition exposed employees to an electrical shock and electrical burn hazard.
Recent events (1)
  • — Z (S) $0

1910.305 G01 IV D

Serious Gravity 1 1 instance 3 exposed
Issued
Jul 9, 2015
Abate by
Aug 6, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces.  Office, adjacent to doorway; on or about 22 June 2015 and times prior thereto; a blue 15 foot energized extension cord was used in lieu of permanent wiring. Cord was mounted to the wall with cable clamps. This condition exposed employees to electrical shock and electrical burn hazards.
Recent events (1)
  • — Z (S) $0

1910.305 G02 III

Repeat Gravity 1 1 instance 1 exposed
Issued
Jul 9, 2015
Abate by
Aug 6, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws.  Tank room, on or about 22 June 2015 and times prior thereto; strain relief was not provided on a cord and plug type emergency light. This condition exposed employees to an electrical shock hazard.      The National Park Service was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.305(g)(2)(iii), which was contained in OSHA inspection number 559578, citation number 1, item number 3 and was affirmed as a final order on 01 October 2012, with respect to a workplace located at the Main Camp Auto Repair section Bay 2.
Recent events (1)
  • — Z (R) $0

View National Park Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340738319.