Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NATIONAL PARK SERVICE

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NATIONAL PARK SERVICE in MILE 237 PARKS HIGHWAY, DENALI NATIONAL PARK, AK 99755 (NAICS 562111). OSHA activity number 340738863.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch National Park Service — free Get an email when a new federal OSHA severe-injury report for National Park Service is published. One employer, no account, unsubscribe in one click.
Site address
MILE 237 PARKS HIGHWAY
City
DENALI NATIONAL PARK
State
AK
ZIP
99755
Mailing
P.O. BOX 9, DENALI NATIONAL PARK, AK 99755
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
562111
Employees
300
Ownership type
D

4 citations on file for this inspection.

1910.303 G02 II

Serious Gravity 1 1 instance 10 exposed
Issued
Jul 9, 2015
Abate by
Aug 6, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage:  Hazcom storage locker; on or about 22 June 2015 and times prior thereto, the electrical conduit supplying power to the Hazcom locker was damaged. This condition exposed employees to electrical  shock and burn hazards.
Recent events (1)
  • — Z (S) $0

1910.304 G05

Repeat Gravity 10 1 instance 10 exposed
Issued
Jul 9, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The paths to ground from circuits, equipment, and enclosures were not permanent, continuous, and effective.  Hazcom locker; on or about 22 June 2015 and times prior thereto, the hazcom storage locker was electrically energized. Stored inside the locker was compressed oxygen, dissolved acetylene, and gasoline. Ground wire was actively charged. This condition exposed employees to fire, explosion, and electrical shock and burn hazards.   The National Park Service was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.304(g)(5), which was contained in OSHA inspection number 307506618, citation number 2, item number 1 and was affirmed as a final order on 14 October 2010, with respect to a workplace located at the Main Camp.
Recent events (1)
  • — Z (R) $0

1910.305 B02

Repeat Gravity 1 1 instance 10 exposed
Issued
Jul 9, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy.  Building 44065, north wall; on or about 22 June 2015 and times prior thereto; an energized electrical outlet was missing the faceplate. This condition exposed employees to electrical shock and burn hazards.  The National Park Service was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.305(b)(2), which was contained in OSHA inspection number 307506618 citation number 1, item number 4 and was affirmed as a final order on 14 October 2010, with respect to a workplace located at the Main Camp.
Recent events (1)
  • — Z (R) $0

1910.305 D02

Repeat Gravity 5 1 instance 10 exposed
Issued
Jul 9, 2015
Abate by
Jul 23, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and/or were not dead front.  Fuel Truck Garage; on or about 22 June 2015 and times prior thereto; an energized electrical panel was missing the deadfront. This condition exposed employees to electrical shock and burn hazards.   The National Park Service was previously cited for a violation of this occupational safety and health standard 29 CFR 1910.305(d)(2), which was contained in OSHA inspection number 307506618, citation number 2, item number 2 and was affirmed as a final order on 14 October 2010, with respect to a workplace located at the Main Camp.
Recent events (1)
  • — Z (R) $0

View National Park Service's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340738863.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.