SUQUAMISH, WA —
OSHA Inspection: SUQUAMISH CLEARWATER CASINO RESORT
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of SUQUAMISH CLEARWATER CASINO RESORT in 15347 SUQUAMISH WAY NE, SUQUAMISH, WA 98392 (NAICS 721120). OSHA activity number 340779552.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- SUQUAMISH CLEARWATER CASINO RESORT
- Site address
- 15347 SUQUAMISH WAY NE
- City
- SUQUAMISH
- State
- WA
- ZIP
- 98392
- Mailing
- 15347 SUQUAMISH WAY NE, SUQUAMISH, WA 98392
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 721120
- Employees
- 870
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.215 B09
- Issued
- Aug 4, 2015
- Penalty
- Initial $1,721 · Current $1,205 Reduced
General-duty citation text
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch: a) Engineering, where the tongue guard on the Ryobi bench grinder measured 3/4 inch from the abrasive wheel.
Recent events (2)
- — I (S) $1204.7
- — Z (S) $1721
1910.303 B02
- Issued
- Aug 4, 2015
- Abate by
- Sep 21, 2015
- Penalty
- Initial $2,025 · Current $1,418 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling: a) Facility, where equipment not used as listed or labeled included: 1. IDF2 Room, where two extension cords were daisy chained and used to supply power to computer equipment. (Item Corrected) 2. Employee Dining Room, where a relocatable power tap was used to supply power to appliances including the Randell refrigerator and the Vector System light. 3. Employee Break Room, where a relocatable power tap was used to supply power to the Sure Vend vending machine. (Item Corrected) 4. Laundry, where a relocatable power tap was used to supply power to appliances including the Magic Chef microwave oven and the Sanyo refrigerator. (Item Corrected) 5. Environmental Supervisor Office, where two relocatable power taps were daisy chained with an orange extension cord and used to supply power to radio battery chargers and the battery charger on the Multiton pallet jack.
Recent events (2)
- — I (S) $1417.5
- — Z (S) $2025
1910.37 B02
- Issued
- Aug 4, 2015
- Abate by
- Sep 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit": a) Slots Office Suite, where designated emergency exits not equipped with signage included: 1. The door located at the front entrance. 2. The Conference Room door that opened into the hallway.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.303 G01 II
- Issued
- Aug 4, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage: a) First Floor Fire Panel Room, where items including foldable barricades, boxes of electrical supplies, and boxes of fire equipment were stored in front of circuit panels, SBSEC #1, SEC#2, and the brown panel.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 B02 I
- Issued
- Aug 4, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) Hotel, where outlets not equipped with covers included: 1. Beach Brew Cafe, where the receptacles located on the back wall that were used to supply power to equipment such as, the Hamilton Beach blender and the Luxus coffee maker were not equipped with faceplates. 2. Beach Glass Cafe, where the receptacle adjacent to the wine dispenser was not equipped with a faceplate.
Recent events (2)
- — I (O) $0
- — Z (O) $0
1910.305 G01 IV A
- Issued
- Aug 4, 2015
- Abate by
- Sep 21, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure: a) Buffet Kitchen, where an orange extension cord was used to supply power to the Silver King sauce table.
Recent events (2)
- — I (O) $0
- — Z (O) $0
More inspections at Suquamish Clearwater Casino Resort
View Suquamish Clearwater Casino Resort's full OSHA safety record →
More inspections in this industry (NAICS 721120)
More inspections in WA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340779552.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.