Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SUQUAMISH CLEARWATER CASINO RESORT

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of SUQUAMISH CLEARWATER CASINO RESORT in 15347 SUQUAMISH WAY NE, SUQUAMISH, WA 98392 (NAICS 721120). OSHA activity number 340779552.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Suquamish Clearwater Casino Resort — free Get an email when a new federal OSHA severe-injury report for Suquamish Clearwater Casino Resort is published. One employer, no account, unsubscribe in one click.
Site address
15347 SUQUAMISH WAY NE
City
SUQUAMISH
State
WA
ZIP
98392
Mailing
15347 SUQUAMISH WAY NE, SUQUAMISH, WA 98392
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
721120
Employees
870
Ownership type
A

6 citations on file for this inspection.

1910.215 B09

Serious Gravity 1 1 instance 10 exposed
Issued
Aug 4, 2015
Penalty
Initial $1,721 · Current $1,205 Reduced
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:  a) Engineering, where the tongue guard on the Ryobi bench grinder measured 3/4 inch from the abrasive wheel.
Recent events (2)
  • — I (S) $1204.7
  • — Z (S) $1721

1910.303 B02

Serious Gravity 1 5 instances 100 exposed
Issued
Aug 4, 2015
Abate by
Sep 21, 2015
Penalty
Initial $2,025 · Current $1,418 Reduced
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing or labeling:   a) Facility, where equipment not used as listed or labeled included:     1. IDF2 Room, where two extension cords were daisy chained and used to supply power to computer equipment. (Item Corrected)   2. Employee Dining Room, where a relocatable power tap was used to supply power to appliances including the Randell refrigerator and the Vector System light.   3. Employee Break Room, where a relocatable power tap was used to supply power to the Sure Vend vending machine. (Item Corrected)   4. Laundry, where a relocatable power tap was used to supply power to appliances including the Magic Chef microwave oven and the Sanyo refrigerator. (Item Corrected)   5. Environmental Supervisor Office, where two relocatable power taps were daisy chained with an orange extension cord and used to supply power to radio battery chargers and the battery charger on the Multiton pallet jack.
Recent events (2)
  • — I (S) $1417.5
  • — Z (S) $2025

1910.37 B02

Other-than-serious 2 instances 6 exposed
Issued
Aug 4, 2015
Abate by
Sep 21, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":   a) Slots Office Suite, where designated emergency exits not equipped with signage included:  1. The door located at the front entrance.  2. The Conference Room door that opened into the hallway.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 100 exposed
Issued
Aug 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(ii): Working space for equipment likely to require examination, adjustment, servicing, or maintenance while energized was used for storage:   a) First Floor Fire Panel Room, where items including foldable barricades, boxes of electrical supplies, and boxes of fire equipment were stored in front of circuit panels, SBSEC #1, SEC#2, and the brown panel.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 B02 I

Other-than-serious 2 instances 10 exposed
Issued
Aug 4, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:   a) Hotel, where outlets not equipped with covers included:  1. Beach Brew Cafe, where the receptacles located on the back wall that were used to supply power to equipment such as, the Hamilton Beach blender and the Luxus coffee maker were not equipped with  faceplates.  2. Beach Glass Cafe, where the receptacle adjacent to the wine dispenser was not equipped with a faceplate.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.305 G01 IV A

Other-than-serious 1 instance 25 exposed
Issued
Aug 4, 2015
Abate by
Sep 21, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(A): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used as a substitute for the fixed wiring of a structure:   a) Buffet Kitchen, where an orange extension cord was used to supply power to the Silver King sauce table.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Suquamish Clearwater Casino Resort's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340779552.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.