1,224,460Inspections Most recent open 2026-07-13 Last loaded 2026-07-16
Safety Incidents OSHA Severe Injury Reports · 2015–2025

OSHA Inspection: BELL CONTAINER CORP.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BELL CONTAINER CORP. in 615 FERRY ST P.O. BOX 5728, NEWARK, NJ 07105 (NAICS 322211). OSHA activity number 340793660.

Watch Bell Container Corp. — free Get an email when a new federal OSHA severe-injury report for Bell Container Corp. is published. One employer, no account, unsubscribe in one click.
Site address
615 FERRY ST P.O. BOX 5728
City
NEWARK
State
NJ
ZIP
07105
Mailing
615 FERRY ST P.O. BOX 5728, NEWARK, NJ 07105
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
322211
Employees
219
Ownership type
A

11 citations on file for this inspection.

5(a)(1)

Serious Gravity 5 2 instances 30 exposed
Issued
Abate by
Penalty
Initial $5400.00 · Current $3240.00 Reduced
OSH ACT of 1970 Section (5)(a)(1): Executive Order 12196 Section 1-201(a): The head of the agency did not furnish to employees places and conditions of employment that are free from recognized hazards that are causing or are likely to cause death or serious physical harm in that the employees were exposed to struck by hazards.   Location: 615 Ferry St., Newark, NJ.   On or about 7/20/15;    a) Employees worked at the shipping/storage area where there was a potential of an overhead structural collapse due to damaged support wood and concrete/brick columns.  The damage to the columns was caused by heavy forklift usage and lack of column guarding.
Recent events (2)
  • — I (S) $3240
  • — Z (S) $5400

1910.23 D01

Serious Gravity 5 1 instance 5 exposed
Issued
Penalty
Initial $3600.00 · Current $2160.00 Reduced
29 CFR 1910.23(d)(1): Every flight of stairs having four or more risers was not equipped with standard stair railings or standard handrails as specified in paragraphs (d)(1)(i) through (v) of this section, the width of the stair to be measured clear of all obstructions except handrails.  Location: 615 Ferry St., Newark, NJ.  a) There were no handrails provided for a stairway used by employees when working and/or accessing the recycling unit.  Employees were exposed to a potential fall hazard; on or about 7/20/15.
Recent events (2)
  • — I (S) $2160
  • — Z (S) $3600

1910.36 D01

Serious Gravity 5 1 instance 30 exposed
Issued
Penalty
Initial $4500.00 · Current $2700.00 Reduced
29 CFR 1910.36(d)(1): Employees must be able to open an exit route door from the inside at all times without keys, tools, or special knowledge. A device such as a panic bar that locks only from the outside was not provided.  Location: 615 Ferry St., Newark, NJ.  a) In the event of an emergency some employees may require special knowledge on how to operate the door in its current condition. There was no panic bar provided at the emergency discharge door; on or about 7/20/15.
Recent events (2)
  • — I (S) $2700
  • — Z (S) $4500

1910.37 B02

Serious Gravity 5 2 instances 30 exposed
Issued
Penalty
Initial $3600.00 · Current $2160.00 Reduced
29 CFR 1910.37(b)(2): Each exit must be clearly visible and marked by a sign reading "Exit."   Location: 615 Ferry St., Newark, NJ.  a) There were no exit signs at the establishment's shipping office and at the mechanic's storage room;  on or about 7/20/15.
Recent events (2)
  • — I (S) $2160
  • — Z (S) $3600

1910.157 C01

Serious Gravity 5 3 instances 30 exposed
Issued
Penalty
Initial $3600.00 · Current $2160.00 Reduced
29 CFR 1910.157(c)(1): The employer did not mount, locate and identify fire extinguishers so that they are readily accessible to employees without subjecting the employees to possible injury.  Location: 615 Ferry St., Newark, NJ.  a) Employer did not mount the portable fire extinguishers; on or about 7/20/15.
Recent events (2)
  • — I (S) $2160
  • — Z (S) $3600

1910.157 E01

Serious Gravity 5 3 instances 30 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.157(e)(1): The employer did not inspect the portable fire extinguishers in the workplace.  Location: 615 Ferry St., Newark, NJ.  a) Employer did not inspect the portable fire extinguishers; on or about 7/20/15.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.178 L04 III

Serious Gravity 1 3 instances 3 exposed
Issued
Abate by
Penalty
Initial $2700.00 · Current $1620.00 Reduced
29 CFR 1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not conducted at least once every three years.  Location: 615 Ferry St., Newark, NJ  a) Forklift operators at the establishment were not re-trained every three years as required; on or about 7/20/15.
Recent events (2)
  • — I (S) $1620
  • — Z (S) $2700

1910.178 Q07

Serious Gravity 5 1 instance 1 exposed
Issued
Penalty
Initial $3600.00 · Current $2160.00 Reduced
29 CFR 1910.178(q)(7): Industrial trucks were being placed in services after the examination showed condition(s) adversely affecting the safety of the vehicle.  Location: 615 Ferry St., Newark, NJ  a) A crown forklift was operated while the propene tank was loose.  The secure mounting bracket was broken and a daily inspection was performed; on or about 7/20/15.
Recent events (2)
  • — I (S) $2160
  • — Z (S) $3600

1910.213 A09

Serious Gravity 5 1 instance 3 exposed
Issued
Abate by
Penalty
Initial $4500.00 · Current $2700.00 Reduced
29 CFR 1910.213(a)(9): All belts, pulleys, gears, shafts, and moving parts were not guarded in accordance with the specific requirements of 1910.219.  Location: 615 Ferry St., Newark, NJ  a) The band saw utilized by the mechanics did not have a guard for the pulleys thereby exposing employees to moving parts; on or about 7/20/15.
Recent events (2)
  • — I (S) $2700
  • — Z (S) $4500

1910.303 B02

Serious Gravity 5 5 instances 5 exposed
Issued
Penalty
Initial $3600.00 · Current $2160.00 Reduced
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.  Location: 615 Ferry St., Newark., NJ.   a) Employer utilized light duty relocatable power taps (RPT) as a permanent connection to power/charge communication devices.  The RPTs' were not used as specified as employer used it to capacity daily thereby increasing overheating and thus creating a potential fire hazard at the shipping office; on or about 7/20/15.
Recent events (2)
  • — I (S) $2160
  • — Z (S) $3600

1910.303 G02 I

Serious Gravity 5 2 instances 3 exposed
Issued
Penalty
Initial $3600.00 · Current $2160.00 Reduced
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets of other forms of approved enclosures, or other means listed under this provision.  Location: 615 Ferry St., Newark, NJ.   a) The electrical panels at the mechanic's storage room did not have an enclosure.  Employees were exposed to electrical shock; on or about 7/20/15.
Recent events (2)
  • — I (S) $2160
  • — Z (S) $3600

View BELL CONTAINER CORP.'s full OSHA safety record →