BUFFALO, NY —
OSHA Inspection: VA WESTERN NY HEALTHCARE SYSTEM
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of VA WESTERN NY HEALTHCARE SYSTEM in 3495 BAILEY AVENUE, BUFFALO, NY 14215 (NAICS 622110). OSHA activity number 340797661.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- VA WESTERN NY HEALTHCARE SYSTEM
- Site address
- 3495 BAILEY AVENUE
- City
- BUFFALO
- State
- NY
- ZIP
- 14215
- Mailing
- 3495 BAILEY AVENUE, BUFFALO, NY 14215
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 622110
- Employees
- 1976
- Ownership type
- D
Citations
5 citations on file for this inspection.
1910.22 A01
- Issued
- Oct 20, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.22(a)(1): All places of employment, were not kept clean and orderly, or in a sanitary condition: a) On or about 6/22/15, in the subbasement (B wing) left of room S16, employer failed to provide a work environment clean and orderly and in a sanitary condition exposing employees to tripping hazards due to excessive accumulation debris and materials being stored in the hallway. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (S) $0
1910.36 A03
- Issued
- Oct 20, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.36(a)(3): An opening into an exit was not protected by a self-closing fire door that remains closed or automatically closes in an emergency upon the sounding of a fire alarm or employee alarm system. Each fire door, including its frame and hardware, must be listed or approved by a nationally recognized testing laboratory. Section 1910.155(c)(3)(iv)(A) of this part defines "listed" and � 1910.7 of this part defines a "nationally recognized testing laboratory." a) On or about 6/22/15, in Room S15 (Electrical Room), where the exit door was not self-closing, employees were exposed to fire hazards in case of an emergency. b) On or about 6/22/15, in Room S18 (Trash Room), where exit door was not self-closing, employees were exposed to fire hazards in case of an emergency. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (S) $0
1910.305 G01 IV A
- Issued
- Oct 20, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure a) On or about, 6/22/15, in the Chemistry Department (B Wing), employer failed to protect employees by using flexible cords as a substitute for permanent wiring, to plug in a power strip used to energize fans, potentially exposing employees to electrical shocks. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (S) $0
1910.303 B02
- Issued
- Oct 20, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) On or about 06/22/15, in Kitchen (Basement-A Wing), the electrical outlet 208-B #5 located to the right to the kitchen sink, used to power kitchen appliances, did not have a Ground-Fault Circuit-Interrupter as required by the National Electric Code (2014, section 422.52). NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (S) $0
1910.147 C06 II
- Issued
- Oct 20, 2015
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(ii): The periodic inspection certification of energy control procedures did not contain the required documentation on identification of the machine or equipment, inspection date, employees included, and the person performing the inspection. a) On or about 06/22/15, in the Plumbing/ A/C department, employer failed to provide periodic inspection certification of the Lockout/Tagout procedure for machines such as but not limited to, Floor band saw, Bench grinder and magnetic drill. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (O) $0
More inspections at VA Western NY Healthcare System
View VA Western NY Healthcare System's full OSHA safety record →