OSHA Inspection: USDA-FARM SERVICE AGENCY

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of USDA-FARM SERVICE AGENCY in 80 CALLE RODULFO GONZALEZ, STE 2, ADJUNTAS, PR 00601 (NAICS 925120). OSHA activity number 340803139.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Usda-Farm Service Agency — free Get an email when a new federal OSHA severe-injury report for Usda-Farm Service Agency is published. One employer, no account, unsubscribe in one click.
Site address
80 CALLE RODULFO GONZALEZ, STE 2
City
ADJUNTAS
State
PR
ZIP
00601
Mailing
80 RODULFO GONZALEZ STREET, STE 2, ADJUNTAS, PR 00601
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
925120
Employees
5
Ownership type
D

6 citations on file for this inspection.

1910.37 B07

Serious Gravity 1 2 instances 5 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(7): Each exit sign must have the word "Exit" in plainly legible letters not less than six inches (15.2 cm) high, with the principal strokes of the letters in the word "Exit" not less than three-fourths of an inch (1.9 cm) wide:  On or about 06/05/15, at 80 Rodulfo Gonzalez Street, Suite 2, Adjuntas, PR, throughout the facility, the exit signs text was not at least six inches height and the text width (stroke size) was not at least three-fourths of an inch.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.303 B02

Serious Gravity 1 1 instance 5 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Installation and use. Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling:    On or about 06/05/15, at 80 Rodulfo Gonzalez Street, Suite 2, Adjuntas, PR, in the IT room area, two uninterruptible power supplies were not directly connected to a permanently installed branch circuit receptacle.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.304 B03 I

Serious Gravity 1 2 instances 5 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.304(b)(3)(i): All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops shall have ground-fault circuit-interrupter protection for personnel:   a) On or about 06/05/15, at 80 Rodulfo Gonzalez Street, Suite 2, Adjuntas, PR, in the male bathroom area, an electrical receptacle was not equipped with ground-fault circuit-interrupter protection.   b) On or about 06/05/15, at 80 Rodulfo Gonzalez Street, Suite 2, Adjuntas, PR, in the female bathroom area, an electrical receptacle was not equipped with ground-fault circuit-interrupter protection.   PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 5 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear:  On or about 06/05/15, at 80 Rodulfo Gonzalez Street, Suite 2, Adjuntas, PR, in the file room area, an electrical outlet box was not covered.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (S) $0

1910.157 C01

Other-than-serious 1 instance 5 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.157(c)(1): The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury:  On or about 06/05/15, at 80 Rodulfo Gonzalez Street, Suite 2, Adjuntas, PR, in the IT room area, a portable fire extinguisher was not mounted.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (O) $0

1910.157 E03

Other-than-serious 1 instance 5 exposed
Issued
Aug 10, 2015
Abate by
Sep 3, 2015
Penalty
Initial $0 · Current $0
29 CFR 1910.157(e)(3): Portable fire extinguishers were not subjected to an annual maintenance check:  On or about 06/05/15, at 80 Rodulfo Gonzalez Street, Suite 2, Adjuntas, PR, throughout the facility, the portable fire extinguishers were not maintained annually.  PLEASE NOTE: CERTIFICATION OF ABATEMENT IS REQUIRED FOR THIS VIOLATION.
Recent events (1)
  • — Z (O) $0

View Usda-Farm Service Agency's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 340803139.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.